HomeMy WebLinkAboutDDW-2024-012306Sanitary Survey - Deficiency Report PWS Number:UTAH17010 Deficiency Points:110 Survey Date:09/13/2024 Survey Name:BEAR LAKE WATER COMPANY Surveyor:Matt Hinckley Sanitary Survey Category: FW SDWIS Severity Code: Significant Deficiency Storage Tanks | ST003 | STORAGE FACILITY ST003 151C. Vent covered with #14 or finer non-corrodible mesh screen. Rule: R309-545-15(4)Rule requires a water storage tank vent to be fitted with #14 mesh or finer non- corrodible screen and vents 6-inches or greater in diameter to be fitted with additional heavy gauge screen or substantial covering to protect the #14 mesh screen from vandalism or damage. This significant deficiency must be corrected within 120 days of notification or have a compliance action plan approved by DDW. Notes:#14 SCREEN HAS A LARGE HOLE IN IT AND NEEDS TO BE REPLACED. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: V007 STORAGE TANK VENT LACKS NO. 14 SCREEN Sanitary Survey Category: FW SDWIS Severity Code: Significant Deficiency Storage Tanks | ST003 | STORAGE FACILITY ST003 158B. Overflow line covered with #4 mesh non-corrodible screen Rule: R309-545-13(3)Rule requires overflow pipes to be screened with #4 mesh non-corrodible screens installed at a location least susceptible to damage by vandalism. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:OVERFLOW LINE IS MISSING A #4 SCREEN. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: V012 END OF STORAGE TANK OVERFLOW PIPE LACKS NO. 4 SCREEN Sanitary Survey Category: FW SDWIS Severity Code: Minor Deficiency Storage Tanks | ST004 | STORAGE FACILITY ST004 171A. Mild deterioration or spalling? Rule: R309-545-6(1) and 545-9(1)Rule requires all water storage tanks to have suitable watertight roofs and sidewalls that shall also exclude birds, animals, insects, and excessive dust. Notes:THE TANK ROOF HAS MILD CRACKING AND SOME AREAS OF SPALLING/DETERIORATION. Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: V021 STORAGE TANK ROOF OR SIDEWALLS SHOW SIGNS OF MILD OR MODERATE DETERIORATION Sanitary Survey Category: TR SDWIS Severity Code: Minor Deficiency Liquid Hypochlorination | TP001 | MAIN WELL CHLORINATION STATION 276. There are adequate spill containment provisions for acid and caustic liquids. Rule: R309-525-11(6)(a)(iv)(B), R309-525- 11(8)(b)(viii) Rule requires liquid chemical storage tanks to have an overflow and receiving basin or drain capable of receiving accidental spills or overflows, and meeting all the requirements of R309-525-23. Notes:SOLUTION TANK LACKS CONTAINMENT METHOD. Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: TG59 LACKS CONTAINMENT PROVISIONS TO HANDLE SOLUTION TANK SPILLS OR OVERFLOWS Sanitary Survey Category: TR SDWIS Severity Code: Minor Deficiency Liquid Hypochlorination | TP002 | SWEETWATER PARKWAY SOUTH CHLORINATOR 284. There are adequate spill containment provisions for acid and caustic liquids. Rule: R309-525-11(6)(a)(iv)(B), R309-525- 11(8)(b)(viii) Rule requires liquid chemical storage tanks to have an overflow and receiving basin or drain capable of receiving accidental spills or overflows, and meeting all the requirements of R309-525-23. Notes:SOLUTION TANK LACKS CONTAINMENT METHOD. Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: TG59 LACKS CONTAINMENT PROVISIONS TO HANDLE SOLUTION TANK SPILLS OR OVERFLOWS Sanitary Survey Category: TR SDWIS Severity Code: Minor Deficiency Liquid Hypochlorination | TP003 | COUNTRY CLUB DRIVE WELL CHLORINATOR 292. There are adequate spill containment provisions for acid and caustic liquids. Rule: R309-525-11(6)(a)(iv)(B), R309-525- 11(8)(b)(viii) Rule requires liquid chemical storage tanks to have an overflow and receiving basin or drain capable of receiving accidental spills or overflows, and meeting all the requirements of R309-525-23. Notes:SOLUTION TANK LACKS CONTAINMENT METHOD. Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: TG59 LACKS CONTAINMENT PROVISIONS TO HANDLE SOLUTION TANK SPILLS OR OVERFLOWS