HomeMy WebLinkAboutDERR-2024-011453Overfill Prevention Equipment Inspection OPW 61 and 71 Series Overfill Prevention Device Inspection (Non Testable) Customer Name: Facility ID #: Address: Street Date: City, State Tank Designation 1 2 3 Part 1 - Proper Height Setting Calculation YES NO PASS FAIL OPW Installation Manual H15524PA Rev L 1/30/2014) Maximum Tank Volume (Gallons) Shown on customers provided tank chart Gallons 15,041 8,050 7,099 Max Shut off requirement for flapper is 95% %95%95%95% Multiply maximum tank volume by 95% (Gallons)95%Gallons 14,289 7,648 6,744 Find the dip stick number on the tank chart that corresponds with 95%X Inches 106.000''105.250''106.875'' Measure top of fill riser threads, or face seal adapter A Inches 49.750''48.750''48.500'' Find the Dip Stick Volume that corresponds with 100% (FROM TANK CHART)Y Inches 118.375''118.375''118.375'' Upper Tube in tank (Y) -(X) = (Z)Z Inches 12.375''13.125''11.500'' Subtract 2 inches from upper tube in tank Formula: (Z) - 2" = (C )C Inches 10.375''11.125''9.500'' Calculated minimum upper tube length Formula: (C ) + (A) = Upper Tube Length Calculated Inches 60.125''59.875''58.000'' Actual measured upper tube length (without fill adapter)Actual Inches 61.375''61.875''61.875'' Part 2 - Device Certification Citeria Evaluation Criteria 1 Does the overfill prevention device meet the 95% requirement?YES YES YES (If Actual is greater than or equal to calculated ( YES) (If Actual is less than or equal to calculated ( NO) Criteria 2 Is the actual measured upper tube length 6.5 inches or more than the fill riser?YES YES YES (C must be 6.5" if not then the upper tube length is 6.5 plus measurement A) (For testable models ending in "T" upper tube length is (C)+ (A) - 1 -1/2". If less than 6.5" than it is 6.5" +(A) - 1-1/2") Criteria 3 Does the overfill prevention device function function as required?YES YES YES (Inspect the device for damage, contamination, freedom of movement, weakening due to wear and corrosion) Part 3 - Device Certification PASS / FAIL PASS PASS PASS Technician certifies that the device is operationally compliant. If the response to Criteria 1, 2, and 3 above are YES. Date: OPW 71SO-410C Overfill Drop Tube Make and Model Tank Chart Comments: 9/6/2023 Signature of Technician: Tank Chart Provided by Speedway Number 9432 4002155 524 West 4500 South Murray, Utah 84123 Xerxes 9/6/2023 PVVC tested ==>RUL Manifolded Final Test Result (Pass / Fail) ==>Fail PVVC Manuf. ==>Husky Model Number ==>5885 Is this Original or Replacement? Original If this cap is being replaced, check here: Manf Spec (CFH) Measured Leak Rate in ml/Min; Cracking (in H2O) Calc CFH (ml/min x .00212) Result (Pass /Fail) Pos Leak Rate(CFH)0.05 25 0.0530 Fail Low High Measured Pos Cracking (in H2O)2.50 6.00 2.10 Fail Neg Leak Rate (CFH)0.21 100 0.2120 Fail Low High Measured Neg Cracking (in H2O)-10.00 -6.00 -5.12 Fail PVVC tested ==>RUL Manifolded Final Test Result (Pass / Fail) ==>Pass PVVC Manuf. ==>OPW Model Number ==>723V Is this Original or Replacement? Replacement Manf Spec (CFH) Measured Leak Rate in ml/Min; Cracking (in H2O) Calc CFH (ml/min x .00212) Result (Pass /Fail) Pos Leak Rate(CFH)0.05 10 0.0212 Pass Low High Measured Pos Cracking (in H2O)2.50 6.00 3.61 Pass Neg Leak Rate (CFH)0.21 60 0.1272 Pass Low High Measured Neg Cracking (in H2O)-10.00 -6.00 -8.81 Pass PVVC tested ==>PUL Manifolded Final Test Result (Pass / Fail) ==>Fail PVVC Manuf. ==>Husky Model Number ==>5885 Is this Original or Replacement? Original If this cap is being replaced, check here: Manf Spec (CFH) Measured Leak Rate in ml/Min; Cracking (in H2O) Calc CFH (ml/min x .00212) Result (Pass /Fail) Pos Leak Rate(CFH)0.05 25 0.0530 Fail Low High Measured Pos Cracking (in H2O)2.50 6.00 1.98 Fail Neg Leak Rate (CFH)0.21 100 0.2120 Fail Low High Measured Neg Cracking (in H2O)-10.00 -6.00 -4.83 Fail PVVC tested ==>PUL Manifolded Final Test Result (Pass / Fail) ==>Pass PVVC Manuf. ==>OPW Model Number ==>723V Is this Original or Replacement? Replacement Manf Spec (CFH) Measured Leak Rate in ml/Min; Cracking (in H2O) Calc CFH (ml/min x .00212) Result (Pass /Fail) Pos Leak Rate(CFH)0.05 10 0.0212 Pass Low High Measured Pos Cracking (in H2O)2.50 6.00 3.58 Pass Neg Leak Rate (CFH)0.21 60 0.1272 Pass Low High Measured Neg Cracking (in H2O)-10.00 -6.00 -8.77 Pass PVVC tested ==> Manifolded Final Test Result (Pass / Fail) ==> PVVC Manuf. ==>Model Number ==> Is this Original or Replacement? Manf Spec (CFH) Measured Leak Rate in ml/Min; Cracking (in H2O) Calc CFH (ml/min x .00212) Result (Pass /Fail) Pos Leak Rate(CFH) Low High Measured Pos Cracking (in H2O) Neg Leak Rate (CFH) Low High Measured Neg Cracking (in H2O) PVVC tested ==> Manifolded Final Test Result (Pass / Fail) ==> PVVC Manuf. ==>Model Number ==> Is this Original or Replacement? Manf Spec (CFH) Measured Leak Rate in ml/Min; Cracking (in H2O) Calc CFH (ml/min x .00212) Result (Pass /Fail) Pos Leak Rate(CFH) Low High Measured Pos Cracking (in H2O) Neg Leak Rate (CFH) Low High Measured Neg Cracking (in H2O) 11000 N. MOPAC EXPRESSWAY, SUITE 500, AUSTIN, TX 78759 (800) 800-4633 QP-08-03-FF-02 Pressure Vacuum Vent Cap TP-201.1E Field Form Rev C 1/27/2011 Site Overall Test Results: Pass Total +ve LR: 0.0424 Total -ve LR: 0.2544 Test Date 9/27/2022 Technician Name David Mathie WO #2355399 Facility Name / Loc #7-ELEVEN 45957/9432 45957/9432 Street 524 W. 4500 SOUTH State ID 4002155 City, St, Zip MURRAY, UT 84123 Pressure Vacuum Vent Cap Test Form TP-201.1E Site Diagram (This site diagram is for reference only and is not drawn to scale) Work Order:2355399 Site ID / Name:45957/9432 / 7-ELEVEN 45957/9432 Address:524 W. 4500 SOUTH State ID 4002155 City:MURRAY State:UT Zip:84123