Loading...
HomeMy WebLinkAboutDDW-2024-012265Sanitary Survey - Deficiency Report PWS Number:UTAH29047 Deficiency Points:50 Survey Date:09/30/2024 Survey Name:CAUSEY ESTATES Surveyor:Tiffany Rivera Sanitary Survey Category: DS SDWIS Severity Code: Significant Deficiency Distribution | DS001 | UTAH29047 DISTRIBUTION SYSTEM 44A. Open end of vent line covered with #14 mesh screen Rule: R309-550-6(6)(b)Rule states the open end of the air relief vent pipe from automatic valves shall be provided with a #14 mesh, non-corrodible screen and a downward elbow, and where possible, be extended to at least one foot above grade. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:Downturned pipes were removed from two locations, so no screens were present. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: D004 AIR RELIEF VALVE PIPE LACKS NO. 14 SCREEN Sanitary Survey Category: DS SDWIS Severity Code: Significant Deficiency Distribution | DS001 | UTAH29047 DISTRIBUTION SYSTEM 44D. Open end of vent line down-turned. Rule: R309-550-6(6)(b)Rule states the open end of the air relief vent pipe from automatic valves shall be provided with a #14 mesh, non-corrodible screen and a downward elbow, and where possible, be extended to at least one foot above grade. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:Downturned pipes were not present in two locations. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: D006 AIR RELIEF VALVE PIPE NOT DOWNTURNED