HomeMy WebLinkAboutDDW-2024-012185Sanitary Survey - Deficiency Report PWS Number:UTAH06012 Deficiency Points:305 Survey Date:09/18/2024 Survey Name:SYRACUSE CITY WATER SYSTEM Surveyor:Angela Jones Sanitary Survey Category: SO SDWIS Severity Code: Significant Deficiency Management and Operations | DS001 | UTAH06012 DISTRIBUTION SYSTEM 28B. System lacks more than 20% of required source capacity Rule: R309-510-7(1)Rule requires a water system's source capacity to legally and physically meet the peak day demand and the average yearly demand. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:Based on calculation sheet they lack 28.6% Deficiency Points: 50 Days until points become effective on IPS: 120 SDWIS Deficiency Description: S094 SYSTEM LACKS MORE THAN 20% OF REQUIRED SOURCE CAPACITY Sanitary Survey Category: SO SDWIS Severity Code: Significant Deficiency Wells | WS001 | WELL 2 58. Well casing is at least 18 inches above finished ground surface and 12 inches above well house floor. Rule: R309-515-6(6)(b)(vi), R309-515- 6(12)(c)(ii), R309-515-6(13)(a) Rule requires the permanent well casing to project at least 18 inches above the final ground surface and 12 inches above the pump house floor; at sites subject to flooding, the top of the casing must terminate at least 3 feet above the 100-year flood level or highest known flood elevation, whichever is higher. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:Not connected. Unable to see inside wellhouse. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: S003 WELL CASING TERMINATES LESS THAN 12 INCHES ABOVE FLOOR OR LESS THAN 18 INCHES ABOVE GROUND SURFACE Sanitary Survey Category: SO SDWIS Severity Code: Significant Deficiency Wells | WS001 | WELL 2 59. Wellhead is sealed to prevent contamination. Rule: R309-515-6(6)(i)R309-515-6(6)(i) and R309-515-6(12)(b,c,d)require a sanitary seal be installed and maintained at the wellhead and discharge piping. This significant deficiency should be corrected within 120 days of notification or have a corrective action plan approved by Notes:Not connected. Deficiency Points: 50 Days until points become effective on IPS: 120 SDWIS Deficiency Description: S013 WELL LACKS THE REQUIRED WELL SEAL Sanitary Survey Category: SO SDWIS Severity Code: Significant Deficiency Wells | WS001 | WELL 2 65. There are no unprotected cross-connections in well discharge piping. Rule: R309-105-12(1), R309-515-6(12)(d)(iii)Rule requires the well discharge piping to be protected against the entrance of contamination. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:Not connected. Deficiency Points: 50 Days until points become effective on IPS: 120 SDWIS Deficiency Description: S021 CROSS CONN EXISTS IN WELL HOUSE OR AT WELL HEAD Sanitary Survey Category: TR SDWIS Severity Code: Minor Deficiency Wells | WS001 | WELL 2 66. No toxic chemicals, hazardous or flammable materials, or lubricants inside the well house or near well head? Rule: R309-105-7, 8 & 18, R309-100 through 605 Trigger for regulatory followup to address concerns. Notes:Not connected. Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: TGR9 TRIGGER FOR REGULATORY FOLLOWUP TO ADDRESS CONCERNS Sanitary Survey Category: SO SDWIS Severity Code: Minor Deficiency Wells | WS001 | WELL 2 67. Well discharge line has a smooth-nosed sampling tap, which samples the well water before any chemical injection. (first item from the wellhead). Rule: R309-515-6(12)(d)(iv)Rule requires the discharge piping to be equipped with a smooth nosed sampling tap, a check valve, a pressure gauge, a means of measuring flow, and a shutoff valve. (smooth nosed sampling tap being the first item from the well head and the shut-off valve as the last item) Notes:Not connected. Deficiency Points: 5 Days until points become effective on IPS: 0 SDWIS Deficiency Description: S023 NO SMOOTH NOSED SAMPLING TAP ON DISCHARGE PIPING Sanitary Survey Category: SO SDWIS Severity Code: Minor Deficiency Wells | WS001 | WELL 2 68. Well discharge line has a check valve. Rule: R309-515-6(12)(d)(iv)Rule requires the discharge piping to be equipped with (in order of placement from the wellhead) a smooth nosed sampling tap, a check valve, a pressure gauge, a means of measuring flow, and a shutoff valve. Notes:Not connected. Deficiency Points: 5 Days until points become effective on IPS: 0 SDWIS Deficiency Description: S024 NO CHECK VALVE ON WELL DISCHARGE PIPING Sanitary Survey Category: SO SDWIS Severity Code: Minor Deficiency Wells | WS001 | WELL 2 69. Well discharge line has a pressure gauge. Rule: R309-515-6(12)(d)(iv)Rule requires the discharge piping to be equipped with (in order of placement from the wellhead) a smooth nosed sampling tap, a check valve, a pressure gauge, a means of measuring flow, and a shutoff valve. Notes:Not connected. Deficiency Points: 5 Days until points become effective on IPS: 0 SDWIS Deficiency Description: S025 NO PRESSURE GAUGE ON WELL DISCHARGE PIPING Sanitary Survey Category: SO SDWIS Severity Code: Minor Deficiency Wells | WS001 | WELL 2 70. Well discharge line has a means to measure flow. Rule: R309-515-6(12)(d)(iv)Rule requires the discharge piping to be equipped with (in order of placement from the wellhead) a smooth nosed sampling tap, a check valve, a pressure gauge, a means of measuring flow, and a shutoff valve. Notes:Not connected. Deficiency Points: 5 Days until points become effective on IPS: 0 SDWIS Deficiency Description: S026 NO FLOW METER ON WELL DISCHARGE PIPING Sanitary Survey Category: SO SDWIS Severity Code: Minor Deficiency Wells | WS001 | WELL 2 71. Well discharge line has a shut-off valve (last item from the well head). Rule: R309-515-6(12)(d)(iv)Rule requires the discharge piping to be equipped with (in order of placement from the wellhead) a smooth nosed sampling tap, a check valve, a pressure gauge, a means of measuring flow, and a shutoff valve. Notes:Not connected. Deficiency Points: 5 Days until points become effective on IPS: 0 SDWIS Deficiency Description: S027 NO SHUT OFF VALVE ON WELL DISCHARGE PIPING Sanitary Survey Category: SO SDWIS Severity Code: Significant Deficiency Wells | WS002 | WELL 3 79. Well casing is at least 18 inches above finished ground surface and 12 inches above well house floor. Rule: R309-515-6(6)(b)(vi), R309-515- 6(12)(c)(ii), R309-515-6(13)(a) Rule requires the permanent well casing to project at least 18 inches above the final ground surface and 12 inches above the pump house floor; at sites subject to flooding, the top of the casing must terminate at least 3 feet above the 100-year flood level or highest known flood elevation, whichever is higher. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:Not connected Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: S003 WELL CASING TERMINATES LESS THAN 12 INCHES ABOVE FLOOR OR LESS THAN 18 INCHES ABOVE GROUND SURFACE Sanitary Survey Category: FW SDWIS Severity Code: Minor Deficiency Storage Tanks | ST002 | CLEARFIELD STORAGE 137A. Access opening framed at least 4 inches above roof surface or 18 inches above earthen cover. Rule: R309-545-14(1)Rule requires tank access opening to be framed at least 4 inches above the surface of the roof, or on a buried tank, to be at least 18 inches above any earthen cover over the tank. Notes:Approximately 4 inches above earthen cover. Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: V008 TANK ACCESS HEIGHT LESS THAN 4 INCHES ABOVE TANK ROOF OR LESS THAN 18 INCHES ABOVE EARTHEN COVER Sanitary Survey Category: FW SDWIS Severity Code: Significant Deficiency Storage Tanks | ST002 | CLEARFIELD STORAGE 143A. Overflow line discharges at least 12 inches above ground or the flood rim of receiving basin? Rule: R309-545-13 Rule requires all water storage tanks to be provided with an overflow that discharges at an elevation between 12 and 24 inches above the ground surface or the rim of the receiving basin. Notes:Discharges below flood rim receiving basin. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: V011 END OF STORAGE TANK OVERFLOW LACKS A CLEARANCE OF BETWEEN 12 AND 24 INCHES FROM GROUND SURFACE Sanitary Survey Category: FW SDWIS Severity Code: Significant Deficiency Storage Tanks | ST002 | CLEARFIELD STORAGE 143B. Overflow line covered with #4 mesh non-corrodible screen Rule: R309-545-13(3)Rule requires overflow pipes to be screened with #4 mesh non-corrodible screens installed at a location least susceptible to damage by vandalism. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:No screen present. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: V012 END OF STORAGE TANK OVERFLOW PIPE LACKS NO. 4 SCREEN