HomeMy WebLinkAboutDDW-2024-012136Sanitary Survey - Deficiency Report
PWS Number:UTAH18051 Deficiency Points:300 Survey Date:08/29/2024
Survey Name:WEBB WELL WATER USERS Surveyor:Ryan Taggart
Sanitary Survey Category: SM
SDWIS Severity Code: Recommendation
Management and Operations | DS001 | UTAH18051 DISTRIBUTION SYSTEM
31. Does your water system have an Emergency Response Plan?
Rule: R309-105-18 All suppliers are advised to develop contingency plans to cope with possible emergency
situations. In many areas of the state the possibility of earthquake damage shall be
realistically considered.
Notes:They have never put one in writing.
Deficiency Points: 0
Days until points become effective on IPS: 0
SDWIS Deficiency Description: M001 NO CURRENT EMERGENCY RESPONSE PROGRAM
Sanitary Survey Category: SM
SDWIS Severity Code: Minor Deficiency
Cross Connection and Operator Certification | DS001 | UTAH18051 DISTRIBUTION SYSTEM
35. Legally adopted authority statement
Rule: R309-105-12(2)Rule requires each public water system to have a cross connection control program
that includes a legally adopted and functional local authority to enforce the program
(i.e., ordinance, bylaw, or policy).
Notes:Did not receive documentation before deadline
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: M003 CCC-LACKS LOCAL AUTHORITY
Sanitary Survey Category: SM
SDWIS Severity Code: Minor Deficiency
Cross Connection and Operator Certification | DS001 | UTAH18051 DISTRIBUTION SYSTEM
36. Documentation of annual public awareness and/or employee training
Rule: R309-105-12(2)Rule requires each public water system to have a cross connection control program
that includes providing public education or awareness material or presentations.
Notes:Did not receive documentation before deadline
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: M004 CCC-NO ANNUAL PUBLIC EDUCATION OR AWARENESS
Sanitary Survey Category: SM
SDWIS Severity Code: Minor Deficiency
Cross Connection and Operator Certification | DS001 | UTAH18051 DISTRIBUTION SYSTEM
37. Documentation of personnel trained to manage the program (ALL COMUNITY WATER SYSTEMS REQUIRE A DDW CERTIFIED CCC
PROGRAM ADMINISTRATOR. ALL OTHER WATER SYSTEMS REQUIRE AT A MINIMUM BACKFLOW 101 OR EQUIVALENT/
GREATER CCC TRAINING)
Rule: R309-105-12(2)Rule requires each public water system to have a cross connection control program
that includes an operator with adequate training in the area of cross connection control
or backflow prevention.
Notes:Did not receive documentation before deadline
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: M005 CCC-LACKS OPERATOR TRAINING
Sanitary Survey Category: SM
SDWIS Severity Code: Minor Deficiency
Cross Connection and Operator Certification | DS001 | UTAH18051 DISTRIBUTION SYSTEM
38. Does the water system have detailed records of cross connection control activities? (inventories of backflow assemblies, devices, and air gaps
installed within the system)
Rule: R309-105-12(2)Rule requires each public water system to have a cross connection control program
that includes written records of cross connection control activities.
Notes:Did not receive documentation before deadline
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: M006 CCC-LACKS WRITTEN RECORDS OF CCC ACTIVITIES
Sanitary Survey Category: SM
SDWIS Severity Code: Minor Deficiency
Cross Connection and Operator Certification | DS001 | UTAH18051 DISTRIBUTION SYSTEM
39. Does the water system have records of on-going enforcement activities? (test history, enforcement activities, hazard assessments)
Rule: R309-105-12(2)Rule requires each public water system to have a cross connection control program
that includes test history and documentation of on-going enforcement activities.
Notes:Did not receive documentation before deadline
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: M007 CCC-LACKS ON-GOING ENFORCEMENT IMPLEMENTATION
Sanitary Survey Category: OC
SDWIS Severity Code: Significant Deficiency
Cross Connection and Operator Certification | DS001 | UTAH18051 DISTRIBUTION SYSTEM
40. Operator meets required level of certification for water system. ( IF NO CERTIFIED OPERATOR IS REQUIRED MARK COMPLIANT )
Rule: R309-105-11, R309-300-5(3)Rule requires every community and NTNC water system and public water systems that
utilize treatment/filtration to have at least one operator certified at the classified grade
of the water system. Certification must be appropriate for the type of system operated
(treatment and/or distribution). This significant deficiency must be corrected within
120 days of notification or have a corrective action plan approved by DDW.
Notes:Did not receive documentation before deadline
Deficiency Points: 50
Days until points become effective on IPS: 120
SDWIS Deficiency Description: C001 SYSTEM DIRECT RESPONSIBLE CHARGE OPERATORS NOT CERTIFIED AT THE
REQUIRED LEVEL
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Wells | WS001 | SOUTH WELL #1
61. Provisions available to periodically measure water levels
Rule: R309-515-6(12)(e ), R309-515-6(12)(c)(vi)Rule requires provisions be made to permit periodic measurement of water levels in the
completed well.
Notes:Lacks means to measure water levels
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: S015 WELL LACKS A MEANS TO MEASURE WATER LEVELS PERIODICALLY
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Wells | WS001 | SOUTH WELL #1
67. Well discharge line has a check valve.
Rule: R309-515-6(12)(d)(iv)Rule requires the discharge piping to be equipped with (in order of placement from the
wellhead) a smooth nosed sampling tap, a check valve, a pressure gauge, a means of
measuring flow, and a shutoff valve.
Notes:NO CHECK VALVE
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: S024 NO CHECK VALVE ON WELL DISCHARGE PIPING
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Wells | WS001 | SOUTH WELL #1
68. Well discharge line has a pressure gauge.
Rule: R309-515-6(12)(d)(iv)Rule requires the discharge piping to be equipped with (in order of placement from the
wellhead) a smooth nosed sampling tap, a check valve, a pressure gauge, a means of
measuring flow, and a shutoff valve.
Notes:NO PRESSURE GAUGE
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: S025 NO PRESSURE GAUGE ON WELL DISCHARGE PIPING
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Wells | WS001 | SOUTH WELL #1
69. Well discharge line has a means to measure flow.
Rule: R309-515-6(12)(d)(iv)Rule requires the discharge piping to be equipped with (in order of placement from the
wellhead) a smooth nosed sampling tap, a check valve, a pressure gauge, a means of
measuring flow, and a shutoff valve.
Notes:NO FLOW METER
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: S026 NO FLOW METER ON WELL DISCHARGE PIPING
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Wells | WS002 | NORTH WELL #2
82. Provisions available to periodically measure water levels
Rule: R309-515-6(12)(e ), R309-515-6(12)(c)(vi)Rule requires provisions be made to permit periodic measurement of water levels in the
completed well.
Notes:WELL LACKS A MEANS TO MEASURE WATER LEVELS
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: S015 WELL LACKS A MEANS TO MEASURE WATER LEVELS PERIODICALLY
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Wells | WS002 | NORTH WELL #2
88. Well discharge line has a check valve.
Rule: R309-515-6(12)(d)(iv)Rule requires the discharge piping to be equipped with (in order of placement from the
wellhead) a smooth nosed sampling tap, a check valve, a pressure gauge, a means of
measuring flow, and a shutoff valve.
Notes:NO CHECK VALVE
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: S024 NO CHECK VALVE ON WELL DISCHARGE PIPING
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Wells | WS002 | NORTH WELL #2
89. Well discharge line has a pressure gauge.
Rule: R309-515-6(12)(d)(iv)Rule requires the discharge piping to be equipped with (in order of placement from the
wellhead) a smooth nosed sampling tap, a check valve, a pressure gauge, a means of
measuring flow, and a shutoff valve.
Notes:NO PRESSURE GAUGE
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: S025 NO PRESSURE GAUGE ON WELL DISCHARGE PIPING
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Wells | WS002 | NORTH WELL #2
90. Well discharge line has a means to measure flow.
Rule: R309-515-6(12)(d)(iv)Rule requires the discharge piping to be equipped with (in order of placement from the
wellhead) a smooth nosed sampling tap, a check valve, a pressure gauge, a means of
measuring flow, and a shutoff valve.
Notes:NO FLOW METER
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: S026 NO FLOW METER ON WELL DISCHARGE PIPING
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST001 | WATER TANK
100C. Vent covered with #14 or finer non-corrodible mesh screen.
Rule: R309-545-15(4)Rule requires a water storage tank vent to be fitted with #14 mesh or finer non-
corrodible screen and vents 6-inches or greater in diameter to be fitted with additional
heavy gauge screen or substantial covering to protect the #14 mesh screen from
vandalism or damage. This significant deficiency must be corrected within 120 days of
notification or have a compliance action plan approved by DDW.
Notes:Could not verify before deadline
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V007 STORAGE TANK VENT LACKS NO. 14 SCREEN
Sanitary Survey Category: FW
SDWIS Severity Code: Minor Deficiency
Storage Tanks | ST001 | WATER TANK
100D. Vent 6-inch diameter and larger protected with additional heavy-gauge screen or substantial covering.
Rule: R309-545-15(5)Rule requires vents that are 6-inch diameter or greater to be fitted with additional
heavy gauge screen or substantial covering, which will protect the No. 14 mesh screen
against vandalism or damage.
Notes:Could not verify before deadline
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: V035 STORAGE TANK VENT LARGER THAN 6 INCHES IN DIAMETER LACKS
PROTECTIVE SCREEN
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST001 | WATER TANK
101C. Access opening lid properly gasketed
Rule: R309-545-14(2)Rule requires the access opening to a tank to be furnished with a gasket between the lid
and frame. This significant deficiency must be corrected within 120 days of notification
or have a corrective action plan approved by DDW.
Notes:Could not verify before deadline
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V009 STORAGE TANK LID LACKS A FUNCTIONING GASKET BETWEEN THE LID AND
FRAME
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST002 | TANK #2
114C. Vent covered with #14 or finer non-corrodible mesh screen.
Rule: R309-545-15(4)Rule requires a water storage tank vent to be fitted with #14 mesh or finer non-
corrodible screen and vents 6-inches or greater in diameter to be fitted with additional
heavy gauge screen or substantial covering to protect the #14 mesh screen from
vandalism or damage. This significant deficiency must be corrected within 120 days of
notification or have a compliance action plan approved by DDW.
Notes:Could not verify before deadline
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V007 STORAGE TANK VENT LACKS NO. 14 SCREEN
Sanitary Survey Category: FW
SDWIS Severity Code: Minor Deficiency
Storage Tanks | ST002 | TANK #2
114D. Vent 6-inch diameter and larger protected with additional heavy-gauge screen or substantial covering.
Rule: R309-545-15(5)Rule requires vents that are 6-inch diameter or greater to be fitted with additional
heavy gauge screen or substantial covering, which will protect the No. 14 mesh screen
against vandalism or damage.
Notes:Could not verify before deadline
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: V035 STORAGE TANK VENT LARGER THAN 6 INCHES IN DIAMETER LACKS
PROTECTIVE SCREEN
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST002 | TANK #2
115C. Access opening lid properly gasketed
Rule: R309-545-14(2)Rule requires the access opening to a tank to be furnished with a gasket between the lid
and frame. This significant deficiency must be corrected within 120 days of notification
or have a corrective action plan approved by DDW.
Notes:Could not verify before deadline
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V009 STORAGE TANK LID LACKS A FUNCTIONING GASKET BETWEEN THE LID AND
FRAME
Sanitary Survey Category: TR
SDWIS Severity Code: Significant Deficiency
Treatment - General | TPPOU | POINT OF USE ARSENIC REMOVAL
141. Raw water compliance samples are collected before any treatment. R309-215-4(4)
Rule: R309-525-15(10)(a)(i)R309-525-15(10)(a)(i)
Notes:Revers osmosis in residences
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: T006 NO SAMPLE TAP OR MEANS TO SAMPLE RAW WATER OR FINISHED WATER