HomeMy WebLinkAboutDDW-2024-012058Sanitary Survey - Deficiency Report PWS Number:UTAH02007 Deficiency Points:55 Survey Date:09/05/2024 Survey Name:ELWOOD TOWN Surveyor:Ben Harker Sanitary Survey Category: SO SDWIS Severity Code: Minor Deficiency Springs | WS002 | NORTH CANYON SPRING 72. Area of equal or higher elevation within 50 feet of spring collection devices is fenced. Rule: R309-515-7(7)(e)Rule requires a stock-tight fence around the spring collection area. Notes:Still deficient, but exception may be sought when re-developed Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: SS02 SPRING COLLECTION AREA NOT FENCED Sanitary Survey Category: SO SDWIS Severity Code: Minor Deficiency Springs | WS002 | NORTH CANYON SPRING 74. Spring box has a means to release overflow? Rule: R309-515-7(7)(d), R309-545-13(1)All junction boxes and collection boxes, must comply with R309-545 with respect to access openings, venting, and tank overflow. Lids for these spring boxes shall be gasketed and the box adequately vented. Notes:Still deficient, but will be remediated upon re-development. Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: SS23 SPRING BOX LACKS A MEANS OF PROVIDING OVERFLOW Sanitary Survey Category: SO SDWIS Severity Code: Significant Deficiency Springs | WS002 | NORTH CANYON SPRING 79. No roots seen in collection boxes and junctions. Rule: R309-105-10(4)(a), R309-515-8(1)(a)Spring collection areas shall be periodically (preferably annually) cleared of deep- rooted vegetation to prevent root growth from clogging collection lines. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:Still deficient, but will be remediated upon re-development. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: SS08 ROOTS IN SPRING COLLECTION PIPES