HomeMy WebLinkAboutDDW-2024-012058Sanitary Survey - Deficiency Report
PWS Number:UTAH02007 Deficiency Points:55 Survey Date:09/05/2024
Survey Name:ELWOOD TOWN Surveyor:Ben Harker
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Springs | WS002 | NORTH CANYON SPRING
72. Area of equal or higher elevation within 50 feet of spring collection devices is fenced.
Rule: R309-515-7(7)(e)Rule requires a stock-tight fence around the spring collection area.
Notes:Still deficient, but exception may be sought when re-developed
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: SS02 SPRING COLLECTION AREA NOT FENCED
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Springs | WS002 | NORTH CANYON SPRING
74. Spring box has a means to release overflow?
Rule: R309-515-7(7)(d), R309-545-13(1)All junction boxes and collection boxes, must comply with R309-545 with respect to
access openings, venting, and tank overflow. Lids for these spring boxes shall be
gasketed and the box adequately vented.
Notes:Still deficient, but will be remediated upon re-development.
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: SS23 SPRING BOX LACKS A MEANS OF PROVIDING OVERFLOW
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Springs | WS002 | NORTH CANYON SPRING
79. No roots seen in collection boxes and junctions.
Rule: R309-105-10(4)(a), R309-515-8(1)(a)Spring collection areas shall be periodically (preferably annually) cleared of deep-
rooted vegetation to prevent root growth from clogging collection lines. This significant
deficiency must be corrected within 120 days of notification or have a corrective action
plan approved by DDW.
Notes:Still deficient, but will be remediated upon re-development.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: SS08 ROOTS IN SPRING COLLECTION PIPES