HomeMy WebLinkAboutDDW-2024-012048Sanitary Survey - Deficiency Report PWS Number:UTAH29069 Deficiency Points:70 Survey Date:09/11/2024 Survey Name:FEENY FAMILY LC Surveyor:Tiffany Rivera Sanitary Survey Category: FW SDWIS Severity Code: Minor Deficiency Management and Operations | DS001 | UTAH29069 DISTRIBUTION SYSTEM 30A. System lacks up to 20% of required storage capacity (fire demand not included) Rule: R309-510-8(1)(a)Rule requires a public water system to provide equalization storage volume (to meet average day demands for indoor and irrigation water use), fire flow storage volume (if equipped with fire hydrants for fire suppression or required by the local fire code official), and emergency storage (if deemed appropriate by the water system or the Director). Notes: Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: V031 SYSTEM LACKS UP TO 20% OF REQUIRED STORAGE CAPACITY (FIRE DEMAND NOT INCLUDED) Sanitary Survey Category: FW SDWIS Severity Code: Significant Deficiency Management and Operations | DS001 | UTAH29069 DISTRIBUTION SYSTEM 30B. System lacks more than 20% of required storage capacity (fire demand not included) Rule: R309-510-8(1)(a)Rule requires a public water system to provide equalization storage volume (to meet average day demands for indoor and irrigation water use), fire flow storage volume (if equipped with fire hydrants for fire suppression or required by the local fire code official), and emergency storage (if deemed appropriate by the water system or the Director). This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes: Deficiency Points: 50 Days until points become effective on IPS: 120 SDWIS Deficiency Description: V034 SYSTEM LACKS MORE THAN 20% OF REQUIRED STORAGE CAPACITY (FIRE DEMAND NOT INCLUDED) Sanitary Survey Category: SO SDWIS Severity Code: Minor Deficiency Wells | WS001 | CAFE WELL 70. Well discharge line has a shut-off valve (last item from the well head). Rule: R309-515-6(12)(d)(iv)Rule requires the discharge piping to be equipped with (in order of placement from the wellhead) a smooth nosed sampling tap, a check valve, a pressure gauge, a means of measuring flow, and a shutoff valve. Notes:A shutoff valve was not observed. Deficiency Points: 5 Days until points become effective on IPS: 0 SDWIS Deficiency Description: S027 NO SHUT OFF VALVE ON WELL DISCHARGE PIPING