HomeMy WebLinkAboutDERR-2024-011330Recommended Practices for the Testing and Verification of Spill, Overfill, Leak Detection and Secondary Containment Equipment at UST Facilities
APPENDIX C-7
AUTOMATIC TANK GAUGE
OPERATION INSPECTION
Facility Name: Owner:
Address: Address:
City, State, Zip Code: City, State, Zip Code:
Facility I.D. #: Phone#:
Testing Company: Phone#: I Date:
This procedure is to determine whether the automatic tank guage (ATG) is operating properly. See PEI/RP1200 Section 8.2 for the inspection procedure. This procedure is applicable to tank level monitor stems that touch the bottom of the tank when in place.
Tank Number
Product Stored
ATG Brand and Model
1. Tank Volume, gallons
2. Tank Diameter, inches
3. After removing the ATG from the tank, it has been inspected and any damaged or missing □Yes □No □Yes □ No □Yes □No □Yes □Noparts replaced?
4. Float moves freely on the stem without □Yes □No □Yes □ No □Yes □No □Yes □Nobinding?
5. Fuel float level agrees with the value pro-□Yes □No □Yes □ No □Yes □No □Yes □Nogrammed into the console?
6. Water float level agrees with the value pro-□Yes □No □Yes □ No □Yes □No □Yes □Nogrammed into the console?
7. Inch level from bottom of stem when 90% alarm is triggered.
8. Inch level at which the overfill alarm activates corresponds with value programmed in the □Yes □No □Yes □ No □Yes □No □Yes □Nogauge?
9.Inch level from the bottom when the waterfloat first triggers an alarm.
10.Inch level at which the water float alarm acti-vates corresponds with value programmed in □Yes □No □Yes □ No □Yes □No □Yes □Nothe gauge?
If any answers in Lines 3, 4, 5, or 6 are "No," the system has failed the test.
Test Results □Pass □ Fail □Pass □ Fail □Pass □ Fail □Pass □ Fail
Comments:
Tester's Name (print) _______________ _ Tester's Signature _______________ _