HomeMy WebLinkAboutDDW-2024-012038Sanitary Survey - Deficiency Report
PWS Number:UTAH02062 Deficiency Points:5 Survey Date:09/16/2024
Survey Name:WILLOW CREEK WATER CO Surveyor:Deidre Beck
Sanitary Survey Category: FW
SDWIS Severity Code: Minor Deficiency
Storage Tanks | ST004 | 250,000 GAL CONCRETE TANK
103D. Vent 6-inch diameter and larger protected with additional heavy-gauge screen or substantial covering.
Rule: R309-545-15(5)Rule requires vents that are 6-inch diameter or greater to be fitted with additional
heavy gauge screen or substantial covering, which will protect the No. 14 mesh screen
against vandalism or damage.
Notes:ONE VENT HAS A MISSING/DAMAGED HEAVY GAUGE SCREEN.
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: V035 STORAGE TANK VENT LARGER THAN 6 INCHES IN DIAMETER LACKS
PROTECTIVE SCREEN