HomeMy WebLinkAboutDDW-2024-012003Sanitary Survey - Deficiency Report
PWS Number:UTAH22001 Deficiency Points:45 Survey Date:10/02/2024
Survey Name:CLUFF WARD PIPELINE CO Surveyor:Rocky Pace
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Springs | WS001 | WILDE (PASTURE) SPRING
66A. Spring box has shoe box type lid with 2 inch overlap around frame
Rule: R309-515-7(7)(d), R309-545-14 (2)Access openings shall comply with R309-545 and be provided with a close-fitting, solid
shoebox-type cover that extends down around the frame at least 2 inches. This
significant deficiency must be corrected within 120 days of notification or have a
corrective action plan approved by DDW.
Notes:Spring box has a shoebox lid, but the overlap is only about 1".
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: SS09 SPRING BOX LID NOT SHOEBOX STYLE
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Springs | WS001 | WILDE (PASTURE) SPRING
67. Is a spring box vent present? ... if yes, answer the following question(s)
Rule: R309-515-7(7)(d), R309-545-15 Rule requires junction boxes and collection boxes to comply with R309-545 with respect
to venting. Therefore, a junction or collection box requires a vent to be fitted with #14
mesh or finer non-corrodible screen, be fitted with a protective heavy-gauge screen or
covering if 6 inches in diameter or greater, be down-turned and shielded to prevent the
entrance of contaminants, be located and sized to avoid blockage during winter, and
have the end of the vent discharge a minimum of 24 inches above the earth on buried
structures.
Notes:
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: SS11 SPRING BOX LACKS A MEANS OF VENTING
Sanitary Survey Category: TR
SDWIS Severity Code: Minor Deficiency
Gaseous Chlorination | TP001 | WILDE (PASTURE) CHLORINATOR
165. If continuous disinfection is needed, automatic switch over of chlorine cylinders is provided.
Rule: R309-520-7(2)(a), R309-520-6(1)Rule requires automatic switch over of chlorine cylinders be provided if continuous
disinfection is required.
Notes:There is no automatic switch over of Chlorine Cylinders
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: TD01 CONTINUOUS DISINFECTION IS REQUIRED BUT CHLORINATOR LACKS
AUTOMATIC SWITCHOVER