Loading...
HomeMy WebLinkAboutDDW-2024-012003Sanitary Survey - Deficiency Report PWS Number:UTAH22001 Deficiency Points:45 Survey Date:10/02/2024 Survey Name:CLUFF WARD PIPELINE CO Surveyor:Rocky Pace Sanitary Survey Category: SO SDWIS Severity Code: Significant Deficiency Springs | WS001 | WILDE (PASTURE) SPRING 66A. Spring box has shoe box type lid with 2 inch overlap around frame Rule: R309-515-7(7)(d), R309-545-14 (2)Access openings shall comply with R309-545 and be provided with a close-fitting, solid shoebox-type cover that extends down around the frame at least 2 inches. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:Spring box has a shoebox lid, but the overlap is only about 1". Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: SS09 SPRING BOX LID NOT SHOEBOX STYLE Sanitary Survey Category: SO SDWIS Severity Code: Minor Deficiency Springs | WS001 | WILDE (PASTURE) SPRING 67. Is a spring box vent present? ... if yes, answer the following question(s) Rule: R309-515-7(7)(d), R309-545-15 Rule requires junction boxes and collection boxes to comply with R309-545 with respect to venting. Therefore, a junction or collection box requires a vent to be fitted with #14 mesh or finer non-corrodible screen, be fitted with a protective heavy-gauge screen or covering if 6 inches in diameter or greater, be down-turned and shielded to prevent the entrance of contaminants, be located and sized to avoid blockage during winter, and have the end of the vent discharge a minimum of 24 inches above the earth on buried structures. Notes: Deficiency Points: 5 Days until points become effective on IPS: 0 SDWIS Deficiency Description: SS11 SPRING BOX LACKS A MEANS OF VENTING Sanitary Survey Category: TR SDWIS Severity Code: Minor Deficiency Gaseous Chlorination | TP001 | WILDE (PASTURE) CHLORINATOR 165. If continuous disinfection is needed, automatic switch over of chlorine cylinders is provided. Rule: R309-520-7(2)(a), R309-520-6(1)Rule requires automatic switch over of chlorine cylinders be provided if continuous disinfection is required. Notes:There is no automatic switch over of Chlorine Cylinders Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: TD01 CONTINUOUS DISINFECTION IS REQUIRED BUT CHLORINATOR LACKS AUTOMATIC SWITCHOVER