HomeMy WebLinkAboutDDW-2024-011875Sanitary Survey - Deficiency Report
PWS Number:UTAH27069 Deficiency Points:80 Survey Date:09/25/2024
Survey Name:BIG PLAINS WATER SSD -
APPLE VALLEY
Surveyor:J. Paul Wright
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Wells | WS003 | GREGERSON WELL
80. Wellhead is sealed to prevent contamination.
Rule: R309-515-6(6)(i)R309-515-6(6)(i) and R309-515-6(12)(b,c,d)require a sanitary seal be installed and
maintained at the wellhead and discharge piping. This significant deficiency should be
corrected within 120 days of notification or have a corrective action plan approved by
Notes:A new sounding tube had been installed and needed caulk. It was deficient at time of visit,
but they fixed it on site. A photo will be sent with the sanitary survey to show the fix and to
resolve the deficiency.
Deficiency Points: 50
Days until points become effective on IPS: 120
SDWIS Deficiency Description: S013 WELL LACKS THE REQUIRED WELL SEAL
Sanitary Survey Category: FW
SDWIS Severity Code: Minor Deficiency
Storage Tanks | ST001 | STORAGE FACILITY ST001
107A. Mild deterioration or spalling?
Rule: R309-545-6(1) and 545-9(1)Rule requires all water storage tanks to have suitable watertight roofs and sidewalls
that shall also exclude birds, animals, insects, and excessive dust.
Notes:Existing on IPS Report, they are looking to replace these tanks.
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: V021 STORAGE TANK ROOF OR SIDEWALLS SHOW SIGNS OF MILD OR MODERATE
DETERIORATION
Sanitary Survey Category: FW
SDWIS Severity Code: Minor Deficiency
Storage Tanks | ST002 | STORAGE FACILITY ST002
121A. Mild deterioration or spalling?
Rule: R309-545-6(1) and 545-9(1)Rule requires all water storage tanks to have suitable watertight roofs and sidewalls
that shall also exclude birds, animals, insects, and excessive dust.
Notes:Existing on IPS Report, they are looking to replace these tanks.
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: V021 STORAGE TANK ROOF OR SIDEWALLS SHOW SIGNS OF MILD OR MODERATE
DETERIORATION