HomeMy WebLinkAboutDDW-2024-011867Sanitary Survey - Deficiency Report
PWS Number:UTAH18003 Deficiency Points:250 Survey Date:08/27/2024
Survey Name:KENNECOTT - SECTION 21 Surveyor:Brad Johnson
Sanitary Survey Category: DS
SDWIS Severity Code: Significant Deficiency
Distribution | DS001 | UTAH18003 DISTRIBUTION SYSTEM
43. No unprotected connection between the distribution system and a source of contamination. (If there is an unprotected connection, describe
the location in detail.)
Rule: R309-550-5(11)R309-550-5(11)
Notes:Observed a hose submerged in a horse trough next to well #14
Deficiency Points: 50
Days until points become effective on IPS: 120
SDWIS Deficiency Description: D009 WATER MAINS SUSCEPTIBLE TO NEARBY CONTAMINATION SOURCES
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Wells | WS001 | WELL # 11
76. Well discharge line has a pressure gauge.
Rule: R309-515-6(12)(d)(iv)Rule requires the discharge piping to be equipped with (in order of placement from the
wellhead) a smooth nosed sampling tap, a check valve, a pressure gauge, a means of
measuring flow, and a shutoff valve.
Notes:No pressure gauge.
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: S025 NO PRESSURE GAUGE ON WELL DISCHARGE PIPING
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Wells | WS009 | WELL #14 REPLACEMENT
118. Well discharge line has a pressure gauge.
Rule: R309-515-6(12)(d)(iv)Rule requires the discharge piping to be equipped with (in order of placement from the
wellhead) a smooth nosed sampling tap, a check valve, a pressure gauge, a means of
measuring flow, and a shutoff valve.
Notes:Broken gauge.
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: S025 NO PRESSURE GAUGE ON WELL DISCHARGE PIPING
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST001 | MAGNA CULINARY RESERV
156B. Severe deterioration or spalling?
Rule: R309-545-6(1) and 545-9(1)Rule requires all water storage tanks to have suitable watertight roofs and sidewalls
that shall also exclude birds, animals, insects, and excessive dust. This significant
deficiency must be corrected within 120 days of notification or have a corrective action
plan approved by DDW.
Notes:Tank is actively leaking in at least 3 locations. Signs of old leaks present.
Deficiency Points: 50
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V022 STORAGE TANK ROOF OR SIDEWALLS SHOW SIGNS OF SEVERE
DETERIORATION
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST001 | MAGNA CULINARY RESERV
157. Is a tank overflow present? ... if yes, answer the following question(s)
Rule: R309-545-13 Rule requires all storage tanks to be provided with an overflow that discharges at an an
elevation between 12 and 24 inches above the ground surface or the rim of the receiving
basin. This significant deficiency must be corrected within 120 days of notification or
have a corrective action plan approved by DDW.
Notes:Could not locate to verify
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: VL01 STORAGE TANK LACKS AN OVERFLOW
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST001 | MAGNA CULINARY RESERV
158A. Drain line shall terminate at least 12 inches above ground or flood rim of receiving basin
Rule: R309-545-10(1)(d)If the local authority allows discharge to a storm drain, the rule requires the drain
discharge to have a physical clearance of at least 12 inches between the discharge end of
the pipe and the overflow rim of the receiving basin. This significant deficiency must be
corrected within 120 days of notification or have a corrective action plan approved by
DDW.
Notes:Could not locate to verify
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V016 END OF TANK DRAIN LINE LACKS A CLEARANCE OF AT LEAST 12 INCHES
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST005 | UPPER REFINERY TANK
193C. Access opening lid properly gasketed
Rule: R309-545-14(2)Rule requires the access opening to a tank to be furnished with a gasket between the lid
and frame. This significant deficiency must be corrected within 120 days of notification
or have a corrective action plan approved by DDW.
Notes:Gasket in need of repair.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V009 STORAGE TANK LID LACKS A FUNCTIONING GASKET BETWEEN THE LID AND
FRAME
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST005 | UPPER REFINERY TANK
200A. Drain line shall terminate at least 12 inches above ground or flood rim of receiving basin
Rule: R309-545-10(1)(d)If the local authority allows discharge to a storm drain, the rule requires the drain
discharge to have a physical clearance of at least 12 inches between the discharge end of
the pipe and the overflow rim of the receiving basin. This significant deficiency must be
corrected within 120 days of notification or have a corrective action plan approved by
DDW.
Notes:Could not locate to verify.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V016 END OF TANK DRAIN LINE LACKS A CLEARANCE OF AT LEAST 12 INCHES
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST006 | LOWER REFINERY TANK
214A. Drain line shall terminate at least 12 inches above ground or flood rim of receiving basin
Rule: R309-545-10(1)(d)If the local authority allows discharge to a storm drain, the rule requires the drain
discharge to have a physical clearance of at least 12 inches between the discharge end of
the pipe and the overflow rim of the receiving basin. This significant deficiency must be
corrected within 120 days of notification or have a corrective action plan approved by
DDW.
Notes:Could not locate
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V016 END OF TANK DRAIN LINE LACKS A CLEARANCE OF AT LEAST 12 INCHES
Sanitary Survey Category: TR
SDWIS Severity Code: Minor Deficiency
Liquid Hypochlorination | TP001 | SCT 21 PUMPHOUSE LSD1078 CHLORINATOR
335. There are adequate spill containment provisions for acid and caustic liquids.
Rule: R309-525-11(6)(a)(iv)(B), R309-525-
11(8)(b)(viii)
Rule requires liquid chemical storage tanks to have an overflow and receiving basin or
drain capable of receiving accidental spills or overflows, and meeting all the
requirements of R309-525-23.
Notes:Chlorine tank was leaking at time of inspection.
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: TG59 LACKS CONTAINMENT PROVISIONS TO HANDLE SOLUTION TANK SPILLS OR
OVERFLOWS