Loading...
HomeMy WebLinkAboutDDW-2024-011842Sanitary Survey - Deficiency Report PWS Number:UTAH22010 Deficiency Points:55 Survey Date:09/25/2024 Survey Name:OAKLEY TOWN WATER SYSTEM Surveyor:Julie Cobleigh Sanitary Survey Category: SM SDWIS Severity Code: Significant Deficiency Management and Operations | DS001 | UTAH22010 DISTRIBUTION SYSTEM 24. Are there any individual home booster pumps installed in the distribution system (not for fire suppression)? Rule: R309-550-11(3)R309-550-11(3) Notes:one home above the Spring Tanks has a booster pump in a vault Deficiency Points: 50 Days until points become effective on IPS: 120 SDWIS Deficiency Description: M008 SERVICE CONNECTIONS IN DISTRIBUTION SYSTEM RELY ON INDIVIDUAL HOME BOOSTER PUMP DUE TO INADEQUATE PRESSURE Sanitary Survey Category: SO SDWIS Severity Code: Minor Deficiency Springs | WS001 | COTTONWOOD SPRING 77. Is a spring box vent present? ... if yes, answer the following question(s) Rule: R309-515-7(7)(d), R309-545-15 Rule requires junction boxes and collection boxes to comply with R309-545 with respect to venting. Therefore, a junction or collection box requires a vent to be fitted with #14 mesh or finer non-corrodible screen, be fitted with a protective heavy-gauge screen or covering if 6 inches in diameter or greater, be down-turned and shielded to prevent the entrance of contaminants, be located and sized to avoid blockage during winter, and have the end of the vent discharge a minimum of 24 inches above the earth on buried structures. Notes:no vent Deficiency Points: 5 Days until points become effective on IPS: 0 SDWIS Deficiency Description: SS11 SPRING BOX LACKS A MEANS OF VENTING