HomeMy WebLinkAboutDDW-2024-011842Sanitary Survey - Deficiency Report
PWS Number:UTAH22010 Deficiency Points:55 Survey Date:09/25/2024
Survey Name:OAKLEY TOWN WATER
SYSTEM
Surveyor:Julie Cobleigh
Sanitary Survey Category: SM
SDWIS Severity Code: Significant Deficiency
Management and Operations | DS001 | UTAH22010 DISTRIBUTION SYSTEM
24. Are there any individual home booster pumps installed in the distribution system (not for fire suppression)?
Rule: R309-550-11(3)R309-550-11(3)
Notes:one home above the Spring Tanks has a booster pump in a vault
Deficiency Points: 50
Days until points become effective on IPS: 120
SDWIS Deficiency Description: M008 SERVICE CONNECTIONS IN DISTRIBUTION SYSTEM RELY ON INDIVIDUAL
HOME BOOSTER PUMP DUE TO INADEQUATE PRESSURE
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Springs | WS001 | COTTONWOOD SPRING
77. Is a spring box vent present? ... if yes, answer the following question(s)
Rule: R309-515-7(7)(d), R309-545-15 Rule requires junction boxes and collection boxes to comply with R309-545 with respect
to venting. Therefore, a junction or collection box requires a vent to be fitted with #14
mesh or finer non-corrodible screen, be fitted with a protective heavy-gauge screen or
covering if 6 inches in diameter or greater, be down-turned and shielded to prevent the
entrance of contaminants, be located and sized to avoid blockage during winter, and
have the end of the vent discharge a minimum of 24 inches above the earth on buried
structures.
Notes:no vent
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: SS11 SPRING BOX LACKS A MEANS OF VENTING