Loading...
HomeMy WebLinkAboutDDW-2024-011651Sanitary Survey - Deficiency Report PWS Number:UTAH25044 Deficiency Points:45 Survey Date:09/13/2024 Survey Name:DESERET FEEDLOT Surveyor:Russ Franklin Sanitary Survey Category: SO SDWIS Severity Code: Significant Deficiency Management and Operations | DS001 | UTAH25044 DISTRIBUTION SYSTEM 22. For a community water system with water sources that require power to produce sufficient flow, system is equipped with standby power option. Rule: R309-515-6(2)(a)Rule requires a community water system without naturally flowing water sources, such as springs or flowing wells, to have one or more of the system's sources equipped for operation during power outages. To ensure continuous service when the primary power has been interrupted, a redundant power supply is required. A redundant power supply may include a transfer switch for auxiliary power such as a generator or a power supply service with coverage from two independent substations. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:No generator for well. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: S033 COM SYSTEM WITHOUT NATURALLY FLOWING SOURCES LACKS BACKUP POWER FOR AT LEAST ONE WATER SOURCE Sanitary Survey Category: TR SDWIS Severity Code: Minor Deficiency Management and Operations | DS001 | UTAH25044 DISTRIBUTION SYSTEM 31A. Does your Emergency Response Plan include cybersecurity? Rule: R309-105-7, 8 & 18, R309-100 through 605 Trigger for regulatory followup to address concerns. Notes:No SCADA system and not connected to internet Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: TGR9 TRIGGER FOR REGULATORY FOLLOWUP TO ADDRESS CONCERNS Sanitary Survey Category: SO SDWIS Severity Code: Minor Deficiency Wells | WS001 | DESERET FEED WELL 58. Provisions available to periodically measure water levels Rule: R309-515-6(12)(e ), R309-515-6(12)(c)(vi)Rule requires provisions be made to permit periodic measurement of water levels in the completed well. Notes:Is looking into this to see what they can do about it Deficiency Points: 5 Days until points become effective on IPS: 0 SDWIS Deficiency Description: S015 WELL LACKS A MEANS TO MEASURE WATER LEVELS PERIODICALLY