HomeMy WebLinkAboutDERR-2024-0110871
FACILITY ID# …
LHD USE ONLY
Date Received
Reviewer
Date LHD Approved
Date mailed to State
Closure Plan prepared at the request of the owner/operator (identified below) by
of (company name) Phone #
Address City State Zip
A Contractor may prepare this Closure Plan as the owner/operator's agent. In preparing the Closure Plan, the Contractor must act with
the owner/operator's knowledge and approval. The owner/operator must sign the Closure Plan. Submit Closure Plan to: DERR/UST,
P.O. Box 144840, Salt Lake City, Utah, 84114-4840
This Closure Plan is submitted in compliance with the requirements contained in 40 CFR 280 Subpart G and R311-204 (U.A.C.)
Piping closure only Tank #
Tank Type (Steel,FRP,etc.)
Piping Type (Steel,FRP,etc.)
Date Installed
Capacity
Substance stored*
Date last operated
Removal/In Place/Change in
Service (CIS)?
*Indicate the specific substance stored in each tank to be closed (gasoline, diesel, new oil, waste oil, etc.)
For waste oil tanks: Have degreasing or other types of solvents been stored or mixed with the waste oil?
Yes (identify if known) . No Not Known
Analysis for lead or other contaminants may be required prior to disposal of contaminated soil or other material. (Check with your
disposal facility.)
STATE USE ONLY
Date Received
Date Mailed to LHD
Date Received From LHD
Reviewer/Date Approved
Mgr. Review/Date
FACILITY INFORMATION
Tank Owner Phone #
Address City State Zip
Facility Name
Address City State Zip
Contact person Phone #
Total number of regulated underground tanks at this site
Total number of regulated underground tanks at this site to be closed
4001039
Anna Skinner
Stantec Consulting Services, Inc.
2890 East Cottonwood Parkway, Suite 300
801-261-0090
Salt Lake City UT 84121
7-Eleven, Inc.214-415-0146
PO Box 711 (Loc. 0148)Dallas TX 75221-0711
7-Eleven Store No. 25117
287 West 3300 South South Salt Lake UT 84115
Marc Westfall
3
3
1 2 3
steel
FRP
4/15/1984
10,000
GASOLINE
removal
currently in use
214-415-0146
steel
4/15/1984
10,000
GASOLINE
removal
currently in use
steel
4/15/1984
10,000
GASOLINE
removal
currently in use
FRP FRP
UNDERGROUND STORAGE TANK CLOSURE PLAN (rev. 7/13)
9/25/2024
9/25/2024KV -
2
Before the closure plan is submitted for approval, the local health and fire departments where the facility is located
must be contacted.
CONTACT LOCAL HEALTH DISTRICT: Name of Dist. Date
Contact Title Phone#
CONTACT LOCAL FIRE DEPT. Name of Dept. Date
Contact Title Phone#
DISPOSAL INFORMATION
Tank(s) will be disposed at: Facility
Address City State Zip
Contact person Phone#
Product lines will either be: removed or cleaned, secured in place, and capped.
Vent lines will either be: removed or cleaned and secured open.
Piping will be disposed at: Facility
Address City State Zip
Contact person Phone#
Tank(s) will be emptied by: company Phone#
Tank(s) will be cleaned by: company Phone#
Contaminated water in the tank/rinsate will be disposed at: Facility
Contact person Phone#
Tank(s) will be: purged or rendered inert by the following method:
Residual sludges will be disposed at the following facility:
Address City State Zip
Contact person Phone#
FOR CLOSURE IN PLACE ONLY
For this closure method, you are subject to the requirements of UAC R315-302-2(6), which requires annotating the property title and
submitting documentation to the Division of Solid and Hazardous Waste (DSHW). For information on how to comply with these
requirements, contact the DSHW Solid Waste Landfills Section Manager at (801) 536-0200.
Approval for in-place closure has been granted by the Local Fire Department. (Must submit approval in writing with Closure Plan)
Fire Dept. Phone#Contact person Date
Approval for in-place closure has been granted by the Local Health Department.
Health Dept. Phone#Contact person Date
Substance to be used to fill tanks:
TANK REMOVER Name Cert. # TR Exp. Date
Company Phone #
Address City State Zip
SOIL/GROUNDWATER SAMPLER Name Cert. # GS Exp. Date
Company Phone #
Address City State Zip
Traci Gee 0464 8/16/2025
ET Technologies
3110 W. California Ave, Ste D Salt Lake City UT
801-977-0731
84104
Steve Yorgason 1630 4/15/2025
Stantec Consulting Services, Inc.
2890 East Cottonwood Parkway, Suite 300 Salt Lake City UT
801-261-0090
3150 West 900 South Salt Lake City UT 84104
84121
Scale House
x
x
801-328-2051
STC Industrial Services, Inc.
STC Industrial Services, Inc.
801-595-8151
801-595-8151
STC Industrial Services, Inc.
Shane Adolf 801-595-8151
x dry ice
STC Industrial Services, Inc.
618 South 4050 West Salt Lake City UT 84104
Shane Adolf 801-595-8151
9/25/2024
Kim Viehweg Environmental Scientist 385-251-0894
8/29/2024
Nolan Cragun
DERR
801-483-6043Deputy Fire Marshal
South Salt Lake Fire Department
Salt Lake County Landfill
6030 West California Ave.Salt Lake City UT 84104
Scale House 385-468-6370
Metro Group
3
SITE ASSESSMENT
A site assessment must be performed for all UST closures and change-in-service. Site assessments must be performed as outlined in 40 CFR
280.72 and R311-205 (U.A.C.). If contamination is suspected, additional samples must be collected at the location where contamination is
most likely to be present. If groundwater is encountered, a soil sample must be collected, in the unsaturated zone, in addition to each
groundwater sample. Soil and groundwater samples must be analyzed for the compounds shown in the following table, using appropriate lab
methods.
Substance or
Product Type
Contaminant Compounds to be Analyzed for Each
Substance or Product Type
ANALYTICAL METHODS1
Soil, Groundwater
or Surface Water
Gasoline
Total Petroleum Hydrocarbons (purgeable TPH as gasoline
range organics C6 - C10)
EPA 8015 or EPA 8260
Benzene, Toluene, Ethyl benzene, Xylenes, Naphthalene,
(BTEXN) and MTBE
EPA 8021 or EPA 8260
Diesel
Total Petroleum Hydrocarbons (extractable TPH as diesel
range organics C10 – C28)
EPA 8015
Benzene, Toluene, Ethyl benzene, Xylenes, and Naphthalene
(BTEXN)
EPA 8021 or EPA 8260
Used Oil
Oil and Grease (O&G) or
Total Recoverable Petroleum Hydrocarbons (TRPH)
EPA 1664 or
EPA 1664 (SGT*)
Benzene, Toluene, Ethyl benzene, Xylenes, Naphthalene
(BTEXN) & MTBE; and Halogenated Volatile Organic
Compounds (VOX)
EPA 8021 or EPA 8260
New Oil Oil and Grease (O&G) or
Total Recoverable Petroleum Hydrocarbons (TRPH)
EPA 1664 or
EPA 1664 (SGT*)
Other Type of analyses will be based upon the substance or product
stored, and as approved by the DERR Division Director
Method will be based upon the
substance or product type
Unknown
Total Petroleum Hydrocarbons (purgeable TPH as gasoline
range organics C6 - C10)
EPA 8015 or EPA 8260
Total Petroleum Hydrocarbons (extractable TPH as diesel
range organics C10 – C28)
EPA 8015
Oil and Grease (O&G) or
Total Recoverable Petroleum Hydrocarbons (TRPH)
EPA 1664 or
EPA 1664 (SGT*)
Benzene, Toluene, Ethyl benzene, Xylenes, and Naphthalene
(BTEXN) and MTBE; and Halogenated Volatile Organic
Compounds (VOX)
EPA 8021 or EPA 8260
1 The following modifications to these certified methods are considered acceptable by the DERR Division Director:
Dual column confirmation may not be required for TPH and BTEXN/MTBE analysis.
A micro-extraction or scale-down technique may be used for aqueous samples, but only for the determination of extractable TPH as diesel range
organics (C10 – C28).
Hexane may be used as an extraction solvent.
*Silica Gel Treatment (SGT) may be used in the determination of Total Recoverable Petroleum Hydrocarbons.
NOTE: The sample preparation method and any modification(s) to a certified method must be reported by the laboratory.
4
CONTAMINATED MATERIALS MUST BE DISPOSED AT AN ACCEPTABLE FACILITY:
All materials generated from UST closures must be managed and disposed in a manner that does not place those materials in direct contact
with the environment. On-site stockpiling of contaminated soils may be required prior to any soil management activities. Any person
providing remedial assistance for a fee, including aeration and over-excavation (of more than 50 yd3), must be a Certified UST Consultant.
Contaminated soils generated as part of tank removal are to be disposed at the following facility:
Address City State Zip
Contact person Phone
Complete the Facility Site Plat and Sample Information Table on pages 4 and 5 to provide site assessment information.
CONTAMINATION INFORMATION
If contamination at the facility is suspected or confirmed, the information must be reported to the DERR Division Director at (801) 536-
4100 within 24 hours. The Division of Water Quality must be notified at (801) 536-4300 if Free Product is encountered or if surface water
has been impacted. If contamination is confirmed, any person assisting in the remediation process for a fee must be a Certified UST
Consultant.
SAMPLE INFORMATION TABLE
Complete table for all samples to be taken for closure.
1 Soil (SS), Groundwater (GW), or Unified Soil Classification (USC). 2 Approx. depth in feet below grade. The required minimum site assessment samples must be taken at 0-2 feet below the backfill/native soil interface. 3 Contaminant compounds to be analyzed for each sample (from table on p. 3). 4 Appropriate analysis methods for contaminant compound(s) in each sample (from table on p. 3).
Sample
#
Substance
stored in
tank
Sample
type1 Depth2 Compounds3 Analysis method(s)4
ET Technologies
6030 West 1300 South Salt Lake City UT 84104
(801) 973-2065Sarah Smart
SS-1 gasoline SS 12-14 MBTEXN and TPH-GRO 8260
SS-2 gasoline SS 12-14 MBTEXN and TPH-GRO 8260
SS-3 gasoline SS 12-14 MBTEXN and TPH-GRO 8260
SS-4 gasoline SS 12-14 MBTEXN and TPH-GRO 8260
SS-5 gasoline SS 12-14 MBTEXN and TPH-GRO 8260
gasoline MBTEXN and TPH-GRO 8260
USC-1 gasoline USC 12-14 USC ASTM-D2487
SS-6 gasoline SS 12-14 MBTEXN and TPH-GRO 8260
SS-7 gasoline SS 3-5 MBTEXN and TPH-GRO 8260
USC-2 gasoline USC 3-5 USC ASTM-D2487
gasoline MBTEXN and TPH-GRO 8260
USC-3 USC 3-5 USC ASTM-D2487gasoline
GW-2 GW 4-6
GW-1 GW 4-6
5
Facility Site Plat (Closure Plan)
The site plat must be drawn to an appropriate identified scale. It must show planned sampling locations, substances stored in tanks, and
other relevant information. Tank and sample identification numbers must be consistent with the information given on pages 1 and 4 of the
Closure Plan.
Facility ID: Drawn By:Date:
X = Sample locations (SS-#, WS-#, USC-#) Site Plat Must Indicate Approximate Locations of:
●= Monitoring Wells (MW-#)-Current & former tanks, piping & dispensers
○= Soil boring (SB-#), or Geoprobe Boring (GP-#)-Location of all samples to be taken
◘= Water Wells (domestic, livestock, etc.)-Buildings, fences, & property boundaries
Slope of Surface Topography: (N,NW,W,SW,S,SE,E,NE)-Utility conduits (sewers, gas, water, storm drains, electrical, etc.)
Land Use At Site: Residential Commercial Industrial
Surrounding Land: _ Residential Commercial Industrial
North Scale: 1”= Feet
PLEASE SEE ATTACHED SITE PLAN
6
Regional groundwater flow direction:
State Certified Laboratory to be used:
Address City State Zip
Contact Person Phone
I certify under penalty of law that I am the owner/operator of the tank(s) referenced above and that I am familiar with
the information on this form and that it is true, accurate and complete, and further, that the procedures described herein
will be followed during tank closure.
Signature of tank owner
Full Name of tank owner Date
Please explain any unusual or extenuating circumstances expected regarding the site assessment or closure:
Approximate depth to groundwater in the vicinity of the tanks: feet.
northwest
Pace National Analytical
12065 Lebanon Road Mt. Juliet TN 37122
Marty Edwards (615) 758-5858
Marc Westfall
The proposed closure date is October 15, 2024.
9/25/24
Release Sites MEY, MPS, and MZF are associated with this Facility. All received closure by NFA.
5
UE UE
UE
UE
UE UE UE UE UE UE
CONCRETE
GRASS SIGN
CONCRETE
GRASS
LIGHT
POLE
SIDEWALK
CONCRETE
SIDEWALK
SEWERTRAFFIC
POLE
PP
PP
PP
PP
PP PP PP
PPPPPP
PP
PP
PP
C
O
N
C
R
E
T
E
ELEVEN
7-ELEVEN STORE
No.25117
CONCRETE
PARKING
SIDEWALK
PHONES
GR
A
S
S
SI
D
E
W
A
L
K
SI
G
N
CANOPY
LIGHT
POLE
FIRE HYDRANT
30
0
W
E
S
T
330 SOUTH
WATER METER
WATER METER
ELECTRICAL BOX
SI
D
E
W
A
L
K
GAS
METER
LIGHT
ELECTRICAL
PANELS
DUMPSTER
VIC'S
PERFORMANCE
AUTOMOTIVE
LIGHT
POLE
INDUSTRIAL PRODUCTS MFG.
ELECTRIC
POLE
CONCRETE
ASPHALT
USTs
AIR
MW-1
MW-2
MW-3
PH-5
PH-8
PH-7
PH-4
PH-6
PH-3
PH-2
PH-1
SS-7
SS-5
SS-4/USC-3
SS-3/USC-2
GW-1 SS-2
SS-1/USC-1 GW-2
FOR:
FILEPATH:C:\Users\SAguinaldo\Desktop\2024\SLC\203724057\FIG 1_7-11_25117_SITE PLAN_08-28_2024.dwg | Layout Tab: 1 | Drafter: SAguinaldo | Sep 05, 2024 at 4:42
No warranty is made by Stantec Consulting Services Inc. as to the accuracy, reliability, or completeness of these data. Original data were
compiled from various sources. This information may not meet National Map Accuracy Standards. This product was developed
electronically, and may be updated without notification. Any reproduction may result in a loss of scale and or information.
STA AMS JPW 08/28/24
1SITE PLAN
JOB NUMBER:DRAWN BY:CHECKED BY:APPROVED BY:DATE:
FIGURE:
203724057
ELEVEN
PHONE:
2890 E COTTONWOOD PKWY, STE 300
SALT LAKE CITY, UTAH
(801) 261-0090
7-ELEVEN STORE No.25117
287 WEST 3300 SOUTH
SALT LAKE CITY, UTAH
MW-1 ABANDONED MONITORING WELL LOCATION
PH-4 PROBEHOLE LOCATION
LEGEND
N
0 30 60
APPROXIMATE SCALE IN FEET
SS = CLOSURE SOIL SAMPLE LOCATION
GW = CLOSURE GROUNDWATER SAMPLE LOCATION
USC = UNIFIED SOIL CLASSIFICATION SYSTEM SAMPLE LOCATION
OVERHEAD ELECTRIC LINE
ELECTRIC LINE
GAS LINE
STORM DRAIN
WATER LINE
UNKNOWN UTILITY LINE
PRODUCT RETURN LINEPP
SS-6