Loading...
HomeMy WebLinkAboutDERR-2024-011085Testing and Inspection Certificate Tanknology Inc. 11000 North MoPac Expressway, Suite 500, Austin, TX 78759 800-800-4633 www.tanknology.com Page 1 of 1 Test Date 8/20/2024 Tanknology WO#NW1-2366803 Test Purpose COMPLIANCE Customer PO#69825850 Customer Location MURPHY OIL USA P.O. BOX 7300 EL DORADO, AR 71731 Murphy #8784 13443 South Hamilton View Rd Riverton, UT 84065 Attn: BRAD WEINISCHKE Attn: (870) 875-7610 () Test / Inspection Description Item Tested Date Tested Result Precision Line Tightness (.1 GPH) Tank 1 Line 1 RUL 8/20/2024 Pass Precision Line Tightness (.1 GPH) Tank 1 Line 2 RUL 8/20/2024 Pass Precision Line Tightness (.1 GPH) Tank 2 Line 1 PREMIUM 8/20/2024 Pass Precision Line Tightness (.1 GPH) Tank 3 Line 1 Low Sulfur Diesel 8/20/2024 Pass Precision Line Tightness (.1 GPH) Tank 4 Line 1 REG - CONV(E0) 8/20/2024 Pass PEI RP 1200 Leak Detector See test report for details 8/20/2024 Pass Impact Valve Inspection See test report for details 8/20/2024 Pass RP 1200 ATG See test report for details 8/20/2024 Pass RP 1200 Sensors See test report for details 8/20/2024 Pass Stage I Pressure Decay 1 RUL 8/20/2024 Pass Stage I Pressure Decay 2 PREMIUM 8/20/2024 Pass Stage I Pressure Decay 4 REG - CONV(E0) 8/20/2024 Pass Pressure Vacuum Vent Cap See test report for details 8/20/2024 Pass Overfill Protection Tank 1 Overfill 1 RUL 8/20/2024 Pass Overfill Protection Tank 2 Overfill 1 PREMIUM 8/20/2024 NA-seized Overfill Protection Tank 3 Overfill 1 Low Sulfur Diesel 8/20/2024 Fail Overfill Protection Tank 4 Overfill 1 REG - CONV(E0) 8/20/2024 Pass RP 1200 Overfill See test report for details 8/20/2024 P/F E-Stop Inspection See test report for details 8/20/2024 Pass Tanknology Representative: Antonette Shockley Technician: David Mathie Telephone: ()Technician Certification: (See forms) Product Line Tightness Test Page 1 of 1 Work Order: 2366803 Date: 8/20/2024 Site Name/ID: Murphy #8784 / 8784 Address: 13443 South Hamilton View Rd City: Riverton State: UT Zip: 84065 Tank Information Test Method Customer Tank ID Product Name Delivery Type Test Pressure (psi) Test Start Time Test End Time Final Leak Rate (gph) Test Result(P/F/I) Test was performed per 3rd party certifications as specified in 40 CFR parts 280 and 281 Tank # 1 Line # 1 TLD-1 1 RUL Pressure 60 10:08 10:38 0.00 Pass Yes Tank # 1 Line # 2 TLD-1 1 RUL Pressure 60 10:08 10:38 0.00 Pass Yes Tank # 2 Line # 1 TLD-1 2 PREMIUM Pressure 60 10:08 10:38 0.00 Pass Yes Tank # 3 Line # 1 TLD-1 3 Low Sulfur Diesel Pressure 60 10:09 10:39 0.00 Pass Yes Tank # 4 Line # 1 TLD-1 4 REG - CONV(E0) Pressure 60 10:09 10:39 0.00 Pass Yes Tank # Line # Technician Comments: UT151 Technician Name:David Mathie Certification #:41442 exp: 10/20/2025 Technician Signature: Environmental Compliance for Petroleum Systems ©2024 Tanknology Inc., Austin, TX. All rights reserved. tanknology.com Murphy #8784 13443 South Hamilton View Rd Riverton UT 84065 8784 Tanknology, Inc. MURPHY OIL USA P.O. BOX 7300 EL DORADO AR 71731 870-875-7610 08/20/2024 RUL RUL Low Sulfur Diesel REG - CONV(E0)FE Petro MLD+GFE Petro MLD+GFE Petro MLD+GFE Petro MLD+D FE Petro MLD+G 30 30 140 2 12 3 30 30 140 2 12 3 30 30 275 2 12 3 30 30 275 2 12 3 30 30 275 2 12 3 UT151 David Mathie NW1-2366803 PREMIUM T1:1 T1:2 T2:1 T3:1 T4:1 Impact Valve Inspection Impact Valve Operational Inspection Work Order:2366803 Date:8/20/2024 Site Name/ID:Murphy #8784 Address:13443 South Hamilton View Rd City:Riverton State:UT Zip:84065 How Inspected: Line Test NFPA 30A PEI RP1200 Other Dispenser Number Grade Secure Mount? Valve Lock?Pass/ Fail Comments 1/2 40 Pass Fail Not Tested 1/2 85 Pass Fail Not Tested 1/2 88 Pass Fail Not Tested 1/2 91 Pass Fail Not Tested 3/4 40 Pass Fail Not Tested 3/4 85 Pass Fail Not Tested 3/4 88 Pass Fail Not Tested 3/4 91 Pass Fail Not Tested 5/6 40 Pass Fail Not Tested 5/6 85 Pass Fail Not Tested 5/6 88 Pass Fail Not Tested 5/6 91 Pass Fail Not Tested 7/8 40 Pass Fail Not Tested 7/8 85 Pass Fail Not Tested 7/8 88 Pass Fail Not Tested 7/8 91 Pass Fail Not Tested 9/10 40 Pass Fail Not Tested 9/10 85 Pass Fail Not Tested 9/10 88 Pass Fail Not Tested 9/10 91 Pass Fail Not Tested Technician Comments: Technician Name:David Mathie Signature: Environmental Compliance for Petroleum Systems ©2024 Tanknology Inc., Austin, TX. All rights reserved. tanknology.com Impact Valve Inspection Impact Valve Operational Inspection Work Order:2366803 Date:8/20/2024 Site Name/ID:Murphy #8784 Address:13443 South Hamilton View Rd City:Riverton State:UT Zip:84065 Dispenser Number Grade Secure Mount? Valve Lock?Pass/ Fail Comments 11/12 40 Pass Fail Not Tested 11/12 85 Pass Fail Not Tested 11/12 88 Pass Fail Not Tested 11/12 91 Pass Fail Not Tested 13/14 40 Pass Fail Not Tested 13/14 85 Pass Fail Not Tested 13/14 88 Pass Fail Not Tested 13/14 91 Pass Fail Not Tested 15/16 40 Pass Fail Not Tested 15/16 85 Pass Fail Not Tested 15/16 88 Pass Fail Not Tested 15/16 91 Pass Fail Not Tested Technician Comments: Technician Name:David Mathie Signature: Environmental Compliance for Petroleum Systems ©2024 Tanknology Inc., Austin, TX. All rights reserved. tanknology.com Murphy #8784 MURPHY OIL USA 13443 South Hamilton View Rd Riverton UT 84065 8784 Tanknology, Inc. P.O. BOX 7300 EL DORADO AR 71731 870-875-7610 800-964-1250 08/20/2024 1 2 3 4 RUL PREM DSL EO FREE VR450PLUS VR450PLUS VR450PLUS VR450PLUS 25431 7901 10420 7901 118.4 118.4 118.4 118.4 UT151 David Mathie 13443 South Hamilton View Rd Murphy #8784 13443 South Hamilton View Rd, Riverton, UT 84065 8784 Tanknology, Inc. MURPHY OIL USA P.O. BOX 7300 EL DORADO, AR 71731 870-875-7610 08/20/2024 ANNULAR ANNULAR STP STP STP STP UDC RUL PREM/DSL/EO RUL PREM DSL EO FREE 1/2 UT151 David Mathie 13443 South Hamilton View Rd Murphy #8784 13443 South Hamilton View Rd, Riverton, UT 84065 8784 Tanknology, Inc. MURPHY OIL USA P.O. BOX 7300 EL DORADO, AR 71731 870-875-7610 08/20/2024 UDC UDC UDC UDC UDC UDC UDC 3/4 5//6 7/8 9/10 11/12 13/14 15/16 David Mathie 2 inch Pressure Decay Test TP201.3 Store Information Testing Company Site Name :Murphy #8784 Name :TANKNOLOGY INC. Address :13443 South Hamilton View Rd Riverton, UT 84065 Address :11000 N. MoPac Expressway Suite 500 Austin, TX 78759 Phone :-Phone :(800) 800-4633 Stage I System?DUAL Stage II System?NONE Total # of Nozzles :16 Products per Nozzle :3 Tanks Manifolded ?No Drop-Out tank present?NO Total # of Tanks Tested :3 Tank Information : Product Grade : Tank Capacity, gallons : Gasoline, gallons : Ullage, gallons : Testing Information : Start Time : Initial Pressure, wcg : Pressure @ 1 minute(s) : Pressure @ 2 minutes : Pressure @ 3 minutes : Pressure @ 4 minutes : Pressure @ 5 minutes : Allowable Final Pressure : Pass/Fail (Enter "GF" Gross Failure) 1 RUL 25431 17341 8090 10:52 2.00 1.99 1.98 1.97 1.96 1.95 1.89 Pass 2 PREMIUM 7901 5489 2412 11:01 2.00 1.98 1.96 1.94 1.92 1.90 1.64 Pass 4 REG - CONV(E0) 7901 2716 5185 11:10 2.00 1.98 1.96 1.94 1.93 1.92 1.82 Pass Total 41233 25546 15687 All Comments: Tester :David Mathie Test Date :8/20/2024 Signature :Work Order :2366803 WO: 2366803 PVVC tested ==>RUL Manifolded Final Test Result (Pass / Fail) ==>Fail PVVC Manuf. ==>OPW Model Number ==>623V-2203 Is this Original or Replacement? Original If this cap is being replaced, check here: Manf Spec (CFH) Measured Leak Rate in ml/Min; Cracking (in H2O) Calc CFH (ml/min x .00212) Result (Pass /Fail) Pos Leak Rate(CFH)0.05 20 0.0424 Pass Low High Measured Pos Cracking (in H2O)2.50 6.00 2.08 Fail Neg Leak Rate (CFH)0.21 100 0.2120 Fail Low High Measured Neg Cracking (in H2O)-10.00 -6.00 -3.50 Fail PVVC tested ==>RUL Manifolded Final Test Result (Pass / Fail) ==>Pass PVVC Manuf. ==>OPW Model Number ==>723V Is this Original or Replacement? Replacement Manf Spec (CFH) Measured Leak Rate in ml/Min; Cracking (in H2O) Calc CFH (ml/min x .00212) Result (Pass /Fail) Pos Leak Rate(CFH)0.05 4 0.0085 Pass Low High Measured Pos Cracking (in H2O)2.50 6.00 3.66 Pass Neg Leak Rate (CFH)0.21 16 0.0339 Pass Low High Measured Neg Cracking (in H2O)-10.00 -6.00 -7.89 Pass PVVC tested ==>PREM Manifolded Final Test Result (Pass / Fail) ==>Fail PVVC Manuf. ==>OPW Model Number ==>623V-2203 Is this Original or Replacement? Original If this cap is being replaced, check here: Manf Spec (CFH) Measured Leak Rate in ml/Min; Cracking (in H2O) Calc CFH (ml/min x .00212) Result (Pass /Fail) Pos Leak Rate(CFH)0.05 25 0.0530 Fail Low High Measured Pos Cracking (in H2O)2.50 6.00 0.32 Fail Neg Leak Rate (CFH)0.21 100 0.2120 Fail Low High Measured Neg Cracking (in H2O)-10.00 -6.00 -1.02 Fail PVVC tested ==>PREM Manifolded Final Test Result (Pass / Fail) ==>Pass PVVC Manuf. ==>OPW Model Number ==>723V Is this Original or Replacement? Replacement Manf Spec (CFH) Measured Leak Rate in ml/Min; Cracking (in H2O) Calc CFH (ml/min x .00212) Result (Pass /Fail) Pos Leak Rate(CFH)0.05 6 0.0127 Pass Low High Measured Pos Cracking (in H2O)2.50 6.00 3.52 Pass Neg Leak Rate (CFH)0.21 18 0.0382 Pass Low High Measured Neg Cracking (in H2O)-10.00 -6.00 -7.84 Pass PVVC tested ==>EO Manifolded Final Test Result (Pass / Fail) ==>Pass PVVC Manuf. ==>OPW Model Number ==>623V-2203 Is this Original or Replacement? Original If this cap is being replaced, check here: Manf Spec (CFH) Measured Leak Rate in ml/Min; Cracking (in H2O) Calc CFH (ml/min x .00212) Result (Pass /Fail) Pos Leak Rate(CFH)0.05 20 0.0424 Pass Low High Measured Pos Cracking (in H2O)2.50 6.00 2.58 Pass Neg Leak Rate (CFH)0.21 60 0.1272 Pass Low High Measured Neg Cracking (in H2O)-10.00 -6.00 -6.09 Pass PVVC tested ==> Manifolded Final Test Result (Pass / Fail) ==> PVVC Manuf. ==>Model Number ==> Is this Original or Replacement? Manf Spec (CFH) Measured Leak Rate in ml/Min; Cracking (in H2O) Calc CFH (ml/min x .00212) Result (Pass /Fail) Pos Leak Rate(CFH) Low High Measured Pos Cracking (in H2O) Neg Leak Rate (CFH) Low High Measured Neg Cracking (in H2O) 11000 N. MOPAC EXPRESSWAY, SUITE 500, AUSTIN, TX 78759 (800) 800-4633 QP-08-03-FF-02 Pressure Vacuum Vent Cap TP-201.1E Field Form Rev C 1/27/2011 Site Overall Test Results: Pass Total +ve LR: 0.0636 Total -ve LR: 0.1993 Test Date 8/20/2024 Technician Name David Mathie WO #2366803 Facility Name / Loc #Murphy #8784 8784 Street 13443 South Hamilton View Rd City, St, Zip Riverton, UT 84065 Pressure Vacuum Vent Cap Test Form TP-201.1E Wilson, North Carolina 27893 Telephone: 252.243.0150 Web: www.emcoretail.com A1100 Overfill Prevention Valve Calculation Sheet This calculation sheet is to document the dimensions needed for proper installation and should be used only with the instructions. This sheet assumes 95% maximum fill based on NFPA30 guidelines. Length measurements are in inches. Contact the local Authority Having Jurisdiction (AHJ) to determine all regulatory requirements regarding fill capacity. TANK: Tank 1 - Overfill 1 RUL Flapper Valve PRIMARY Test Date: 8/20/2024 Testing Company: Tanknology, Inc. Company:MURPHY OIL CO Site: 8784 Address:13443 South Hamilton View Rd ,Riverton ,UT Overfill Valve Height Inspection 1. Tank Diameter is TD 118.38 2. Tank Capacity is TC 25431.00 3. Desired Shutoff Percentage (Note NFPA Guidelines)0.95 4. Shutoff Tank CapacityTC@ shutoff % = TC x 0.95 24159.45 5. Tank Level from Stick Chart for Shutoff Capacity (95%)106.38 6. Tank B DimensionB = TD - TL @ 95%12.00 7. Distance from top seal surface (1) to the top (inside) of the tank (2) is A 32.50 CAUTION: If tank has a manway make sure to account for the manway height. 8. Calculated Minimum Length of OPV top tube to (95% mark) on the A1100 is C See Picture. Measure C distance from the 95% line on valve and cut top tube 44.50 9. Actual Measured Length of OPV top tube to (95% mark) on the A1100 (measure)44.50 10. Result of Valve height Inspection (if Actual is >= Calculated PASS)Pass 11. Inspect the device for corrosion, damage, and confirm proper operation? P/F Pass comments: Drop Tube Tank Bottom Clearance Inspection 1. Distance from the top seal surface to the tank bottom 2. Distance from the top of drop tube to the highest point of bottom tube cut 3. Actual Maximum tube distance from tank bottom 0.00 comments: "C" 1. The sealing surface refers to the location of the OPV collar sealing point. It may be the riser pipe or the seal surface built in to some spill buckets. 2. If the tank uses a manway, be sure to use the tank top for measurement and not the top of the manway as shown in the diagram. Riser Pipe with Spill Containment Manhole Manway Style Tank WO: 2366803 Wilson, North Carolina 27893 Telephone: 252.243.0150 Web: www.emcoretail.com A1100 Overfill Prevention Valve Calculation Sheet This calculation sheet is to document the dimensions needed for proper installation and should be used only with the instructions. This sheet assumes 95% maximum fill based on NFPA30 guidelines. Length measurements are in inches. Contact the local Authority Having Jurisdiction (AHJ) to determine all regulatory requirements regarding fill capacity. TANK: Tank 2 - Overfill 2 PREMIUM Flapper Valve PRIMARY Test Date: 8/20/2024 Testing Company: Tanknology, Inc. Company:MURPHY OIL CO Site: 8784 Address:13443 South Hamilton View Rd ,Riverton ,UT Overfill Valve Height Inspection 1. Tank Diameter is TD 118.38 2. Tank Capacity is TC 7901.00 3. Desired Shutoff Percentage (Note NFPA Guidelines)0.95 4. Shutoff Tank CapacityTC@ shutoff % = TC x 0.95 7505.95 5. Tank Level from Stick Chart for Shutoff Capacity (95%)106.88 6. Tank B DimensionB = TD - TL @ 95%11.50 7. Distance from top seal surface (1) to the top (inside) of the tank (2) is A CAUTION: If tank has a manway make sure to account for the manway height. 8. Calculated Minimum Length of OPV top tube to (95% mark) on the A1100 is C See Picture. Measure C distance from the 95% line on valve and cut top tube 11.50 9. Actual Measured Length of OPV top tube to (95% mark) on the A1100 (measure) 10. Result of Valve height Inspection (if Actual is >= Calculated PASS)NA-seized 11. Inspect the device for corrosion, damage, and confirm proper operation? P/F comments: Drop Tube Tank Bottom Clearance Inspection 1. Distance from the top seal surface to the tank bottom 2. Distance from the top of drop tube to the highest point of bottom tube cut 3. Actual Maximum tube distance from tank bottom 0.00 comments: "C" 1. The sealing surface refers to the location of the OPV collar sealing point. It may be the riser pipe or the seal surface built in to some spill buckets. 2. If the tank uses a manway, be sure to use the tank top for measurement and not the top of the manway as shown in the diagram. Riser Pipe with Spill Containment Manhole Manway Style Tank WO: 2366803 Wilson, North Carolina 27893 Telephone: 252.243.0150 Web: www.emcoretail.com A1100 Overfill Prevention Valve Calculation Sheet This calculation sheet is to document the dimensions needed for proper installation and should be used only with the instructions. This sheet assumes 95% maximum fill based on NFPA30 guidelines. Length measurements are in inches. Contact the local Authority Having Jurisdiction (AHJ) to determine all regulatory requirements regarding fill capacity. TANK: Tank 3 - Overfill 3 Low Sulfur Diesel Flapper Valve PRIMARY Test Date: 8/20/2024 Testing Company: Tanknology, Inc. Company:MURPHY OIL CO Site: 8784 Address:13443 South Hamilton View Rd ,Riverton ,UT Overfill Valve Height Inspection 1. Tank Diameter is TD 118.38 2. Tank Capacity is TC 10420.00 3. Desired Shutoff Percentage (Note NFPA Guidelines)0.95 4. Shutoff Tank CapacityTC@ shutoff % = TC x 0.95 9899.00 5. Tank Level from Stick Chart for Shutoff Capacity (95%)105.63 6. Tank B DimensionB = TD - TL @ 95%12.75 7. Distance from top seal surface (1) to the top (inside) of the tank (2) is A 34.75 CAUTION: If tank has a manway make sure to account for the manway height. 8. Calculated Minimum Length of OPV top tube to (95% mark) on the A1100 is C See Picture. Measure C distance from the 95% line on valve and cut top tube 47.50 9. Actual Measured Length of OPV top tube to (95% mark) on the A1100 (measure)46.50 10. Result of Valve height Inspection (if Actual is >= Calculated PASS)Fail 11. Inspect the device for corrosion, damage, and confirm proper operation? P/F comments: Drop Tube Tank Bottom Clearance Inspection 1. Distance from the top seal surface to the tank bottom 2. Distance from the top of drop tube to the highest point of bottom tube cut 3. Actual Maximum tube distance from tank bottom 0.00 comments: "C" 1. The sealing surface refers to the location of the OPV collar sealing point. It may be the riser pipe or the seal surface built in to some spill buckets. 2. If the tank uses a manway, be sure to use the tank top for measurement and not the top of the manway as shown in the diagram. Riser Pipe with Spill Containment Manhole Manway Style Tank WO: 2366803 Wilson, North Carolina 27893 Telephone: 252.243.0150 Web: www.emcoretail.com A1100 Overfill Prevention Valve Calculation Sheet This calculation sheet is to document the dimensions needed for proper installation and should be used only with the instructions. This sheet assumes 95% maximum fill based on NFPA30 guidelines. Length measurements are in inches. Contact the local Authority Having Jurisdiction (AHJ) to determine all regulatory requirements regarding fill capacity. TANK: Tank 4 - Overfill 4 REG - CONV(E0) Flapper Valve PRIMARY Test Date: 8/20/2024 Testing Company: Tanknology, Inc. Company:MURPHY OIL CO Site: 8784 Address:13443 South Hamilton View Rd ,Riverton ,UT Overfill Valve Height Inspection 1. Tank Diameter is TD 118.38 2. Tank Capacity is TC 7901.00 3. Desired Shutoff Percentage (Note NFPA Guidelines)0.95 4. Shutoff Tank CapacityTC@ shutoff % = TC x 0.95 7505.95 5. Tank Level from Stick Chart for Shutoff Capacity (95%)106.88 6. Tank B DimensionB = TD - TL @ 95%11.50 7. Distance from top seal surface (1) to the top (inside) of the tank (2) is A 42.25 CAUTION: If tank has a manway make sure to account for the manway height. 8. Calculated Minimum Length of OPV top tube to (95% mark) on the A1100 is C See Picture. Measure C distance from the 95% line on valve and cut top tube 53.75 9. Actual Measured Length of OPV top tube to (95% mark) on the A1100 (measure)54.25 10. Result of Valve height Inspection (if Actual is >= Calculated PASS)Pass 11. Inspect the device for corrosion, damage, and confirm proper operation? P/F Pass comments: Drop Tube Tank Bottom Clearance Inspection 1. Distance from the top seal surface to the tank bottom 2. Distance from the top of drop tube to the highest point of bottom tube cut 3. Actual Maximum tube distance from tank bottom 0.00 comments: "C" 1. The sealing surface refers to the location of the OPV collar sealing point. It may be the riser pipe or the seal surface built in to some spill buckets. 2. If the tank uses a manway, be sure to use the tank top for measurement and not the top of the manway as shown in the diagram. Riser Pipe with Spill Containment Manhole Manway Style Tank WO: 2366803 Murphy #8784 13443 South Hamilton View Rd Riverton, UT 84065 8784 Tanknology, Inc. MURPHY OIL USA 870-875-7610 800-800-4633 08/20/2024 RUL 1 25431 118.375 E/W PREM 2 7901 118.375 E/W DSL 3 10420 118.375 E/W EO FREE 4 7901 118.375 E/W UT151 PREM COULD NOT REMOVE DROP TUBE ADP SEIZED David Mathie P.O. BOX 7300 EL DORADO, AR 71731 Emergency Stop (E-Stop / ESO) Periodic Inspection Facility Information Technician Information Site #: Murphy #8784 8784 Date: 8/20/2024 Address: 13443 South Hamilton View Rd Name: David Mathie City / State: Riverton UT Technician Signature: The objective of this test is to provide assurance that the when the E-Stop switch is activated, all the fueling system circuits (turbines, and dispensers) are de-energized, and remain de-energized until they are re-set manually). The test procedures and guidelines shall be in accordance with the E-Stop Testing Process. SITE DATA 1 Number of E-Stop switches INSIDE of the building: 1 2 Number of E-Stop switches OUTSIDE of the building: 2 PERFORMANCE DATA Yes No NA 3 You have added or confirmed that all E-Stop locations are on the Site Diagram 4 Do all E-Stops shutdown power to ALL DISPENSERS 5 Do all E-Stops shutdown power to ALL STP's 6 Are ALL E-Stops clearly Labeled 7 Are the TURBINE BREAKERS clearly identified / labeled POST TEST 8 All equipment secured and any access ports, lids, enclosures are closed. 9 All safety barricades and test equipment has been properly removed 10 E-Stop was reset and all dispensing functions are normal E-Stop Inspection Results 11 PASS FAIL INCONCLUSIVE Comments (Clearly describe any deficiencies found) WO: 2366803 Murphy Oil USA Site Checklist Murphy # :8784 City, State :Riverton, UT Work Order :2366803 Tank Monitor Please Record All Sensor Alarms, Investigate, and Identify the Cause. Alarm 1:NA Cause: (Is there any free product?) Alarm 2: Cause: (Is there any free product?) Alarm 3: Cause: (Is there any free product?) Alarm 4: Cause: (Is there any free product?) Alarm 5: Cause: (Is there any free product?) Alarm 6: Cause: (Is there any free product?) Please check box for any issues found on tank farm and include comments below Riser Caps – (Tight) Spill Buckets – (Bad gaskets, drains, bucket liners, lids) Vapor Recovery Buckets – (Bad lids, gaskets, popetes, bucket liners) Manhole Covers STP Sump Lids Dispenser Hanging Hardware – (hoses, swivels, break-away, nozzles) Overfill Protection Stage I Vapor Recovery – (swivel dry breaks, tight fit, dual point VR) Stage II Vapor Recovery – (Vapor Saver, ?) Cathodic Protection – (Sacrificial Anodes or Impressed Current?) Are tank guage sticks or GW bailers operable and serviceable? Y Comments: OVERFILL ON PREM ADPT SEIZED LOWER COULD NOT REMOVE DROP TUBE DSL OVERFILL NEED 12.75 PLUS RISER HAVE 11.5 NOT 95% WO: 2366803 Site Diagram (This site diagram is for reference only and is not drawn to scale) Work Order:2366803 Site ID / Name:8784 / Murphy #8784 Address:13443 South Hamilton View Rd City:Riverton State:UT Zip:84065 W.O.# NW1-2366803 Cust Ref#: 69825850 +AAE- I10100 08/20/24 11:51 AM MURPHY USA +ACM-8784 13443 S. HAMILTON Dr RIVERTON,UT 84065 SYSTEM STATUS REPORT ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME ALL FUNCTIONS NORMAL +AAMAAQ- I90200 08/20/24 11:51 AM SOFTWARE REVISION LEVEL VERSION 30.79. SOFTWARE+ACM- 342005-006-K- CREATED - 16.06.21.14.32 +AAMAAQ- I20100 08/20/24 11:51 AM MURPHY USA +ACM-8784 13443 S. HAMILTON Dr RIVERTON,UT 84065 IN-TANK INVENTORY TANK PRODUCT VOLUME TC-VOLUME ULLAGE HEIGHT WATER TEMP 1 REG-25K 17252 0 8179 75.56 0.00 76.72 2 PREMIUM-8K 5473 0 2428 77.28 0.00 74.18 3 DIESEL-10K 3163 0 7257 41.71 0.00 74.84 4 E0-8K 2715 0 5186 44.32 0.00 73.39 +AAMAAQ- I30100 08/20/24 11:51 AM MURPHY USA +ACM-8784 13443 S. HAMILTON Dr RIVERTON,UT 84065 LIQUID STATUS REPORT SENSOR LOCATION STATUS 1 Unleaded Interstitia Normal 2 Premium Interstitial Normal 3 Unleaded STP Sump Normal 4 E0-STP Sump Normal 5 Diesel STP Sump Normal 6 Premium STP Sump Normal 7 Dissp.1+ACY-2 Normal 8 Disp.3+ACY-4 Normal 9 Disp.5+ACY-6 Normal 10 Disp.7+ACY-8 Normal 12 Disp.9+ACY-10 Normal 13 Disp.11+ACY-12 Normal 14 Disp.13+ACY-14 Normal 15 Disp.15+ACY-16 Normal +AAMAAQ- I30200 08/20/24 11:51 AM MURPHY USA +ACM-8784 13443 S. HAMILTON Dr RIVERTON,UT 84065 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 Unleaded Interstitia 08/20/24 10:39 AM FUEL ALARM 08/03/23 10:08 AM SENSOR OUT ALARM 08/03/23 9:53 AM SENSOR OUT ALARM 08/03/23 9:50 AM FUEL ALARM 07/24/23 11:29 AM SENSOR OUT ALARM 07/24/23 11:15 AM FUEL ALARM 07/24/23 10:26 AM FUEL ALARM 08/04/22 2:28 PM FUEL ALARM 09/29/21 9:57 AM FUEL ALARM 2 Premium Interstitial 08/20/24 10:40 AM FUEL ALARM 07/24/23 10:19 AM FUEL ALARM 08/04/22 2:25 PM FUEL ALARM 09/29/21 10:08 AM FUEL ALARM 3 Unleaded STP Sump 08/20/24 10:09 AM FUEL ALARM 07/24/23 10:23 AM FUEL ALARM 08/04/22 2:22 PM FUEL ALARM 09/29/21 9:46 AM FUEL ALARM 4 E0-STP Sump 08/20/24 10:09 AM FUEL ALARM 07/24/23 10:17 AM FUEL ALARM 08/04/22 2:24 PM FUEL ALARM 09/29/21 9:45 AM FUEL ALARM 5 Diesel STP Sump 08/20/24 10:08 AM FUEL ALARM 07/24/23 10:20 AM FUEL ALARM 08/04/22 2:22 PM FUEL ALARM 09/29/21 9:46 AM FUEL ALARM 6 Premium STP Sump 08/20/24 10:08 AM FUEL ALARM 07/24/23 10:22 AM FUEL ALARM 08/04/22 2:23 PM FUEL ALARM 09/29/21 9:48 AM FUEL ALARM 7 Dissp.1+ACY-2 08/20/24 9:27 AM FUEL ALARM 07/24/23 10:21 AM FUEL ALARM 08/04/22 2:29 PM FUEL ALARM 09/29/21 9:25 AM FUEL ALARM 8 Disp.3+ACY-4 08/20/24 9:27 AM FUEL ALARM 07/24/23 10:21 AM FUEL ALARM 08/04/22 2:29 PM FUEL ALARM 09/29/21 9:26 AM FUEL ALARM 9 Disp.5+ACY-6 08/20/24 9:30 AM FUEL ALARM 07/24/23 10:20 AM FUEL ALARM 08/04/22 2:29 PM FUEL ALARM 09/29/21 9:25 AM FUEL ALARM 10 Disp.7+ACY-8 08/20/24 9:28 AM FUEL ALARM 07/24/23 10:21 AM FUEL ALARM 08/04/22 2:30 PM FUEL ALARM 09/29/21 9:26 AM FUEL ALARM 12 Disp.9+ACY-10 08/20/24 9:26 AM FUEL ALARM 07/24/23 10:23 AM FUEL ALARM 08/04/22 2:30 PM FUEL ALARM 09/29/21 9:37 AM FUEL ALARM 13 Disp.11+ACY-12 08/20/24 9:26 AM FUEL ALARM 07/24/23 10:23 AM FUEL ALARM 08/04/22 2:31 PM FUEL ALARM 09/29/21 9:36 AM FUEL ALARM 14 Disp.13+ACY-14 08/20/24 9:27 AM FUEL ALARM 07/24/23 10:22 AM FUEL ALARM 08/04/22 2:30 PM FUEL ALARM 09/29/21 9:33 AM FUEL ALARM 15 Disp.15+ACY-16 08/20/24 9:28 AM FUEL ALARM 07/24/23 10:23 AM FUEL ALARM 08/04/22 2:31 PM FUEL ALARM 09/29/21 9:35 AM FUEL ALARM +AAMAAQ- I6SU00 08/20/24 11:51 AM MURPHY USA +ACM-8784 13443 S. HAMILTON Dr RIVERTON,UT 84065 +AD0APQA9AD0APQA9AD0APQA9AD0APQA9AD0APQ- SETUP FOR ALL TANKS +AD0APQA9AD0APQA9AD0APQA9AD0APQA9AD0APQ- USER ULLAGE: DISABLED PRINT TC VOLUMES: DISABLED TC REFERENCE TEMPERATURE: 60.00 DEG F PERIODIC TEST NEEDED WARNINGS: DISABLED DAYS BEFORE PERIODIC WARNING: 25 DAYS BEFORE PERIODIC ALARM: 30 ANNUAL TEST NEEDED WARNINGS: DISABLED DAYS BEFORE ANNUAL WARNING: 355 DAYS BEFORE ANNUAL ALARM: 365 TC DENSITY: DISABLED STICK HEIGHT: DISABLED - - - - - - - - - - - - - - - - - - - - - - - - - F+ACM- PRODUCT LABEL T+ACM- TANK LABEL -- -------------------- -- -------------------- - - - - - - - - - - - - - - - - - - - - - - - - - +AD0APQA9AD0APQA9AD0APQA9AD0APQA9AD0APQA9- SETUP FOR TANK 1 +AD0APQA9AD0APQA9AD0APQA9AD0APQA9AD0APQA9AD0- CONFIGURED: YES LABEL: REG-25K PRODUCT CODE: 1 PROBE NUMBER: 1 PROBE OFFSET: 0.00 INCHES FULL VOLUME: 25431 GALLONS DIAMETER: 118.4 INCHES TILT: 0.00 INCHES THERMAL COEFFICIENT: 0.000700 METER DATA PRESENT: NO PUMP THRESHOLD: 10 GALLONS DELIVERY DELAY: 5 MINUTES GROSS TEST FAIL: ALARMS DISABLED PERIODIC TEST FAIL: ALARMS DISABLED ANNUAL TEST FAIL: ALARMS DISABLED GOST VOLUME CORRECTION: DISABLED - - - - - - - - - - - - - - - - - - - - - - - - - MAX VOLUME: 25431 GALLONS HIGH PRODUCT: 95+ACU- DELIVERY OVERFILL: 90+ACU- DELIVERY LIMIT: 0+ACU- LOW PRODUCT: 0 GALLONS HIGH WATER WARNING: -0.25 INCHES HIGH WATER ALARM: 1.00 INCHES WATER ALARM FILTER LEVEL: LOW WATER ALARM FILTER DELAY: 180 S LEAK ALARM LIMIT: 10 GALLONS SUDDEN LOSS LIMIT: 25 GALLONS FUEL HIGH TEMP LIMIT: 140.000 DEG F FUEL LOW TEMP LIMIT: -58.000 DEG F - - - - - - - - - - - - - - - - - - - - - - - - - TANK TEST METHOD: SLD LEAK TEST RATE: 0.200 GPH PERIODIC TEST TYPE: STANDARD TEST FREQUENCY: On Date 01/01/2017 01:28 GROSS TEST AUTO CONFIRM: DISABLED TANK TEST SIPHON BREAK: OFF DURATION: 2 HOURS MINIMUM PERIODIC VOLUME: 0.0 +ACU- MINIMUM ANNUAL VOLUME: 0.0 +ACU- EARLY STOP: DISABLED TANK TEST NOTIFY: DISABLED - - - - - - - - - - - - - - - - - - - - - - - - - TANK PROFILE: Four Point +ACM- HEIGHT VOLUME +ACM- HEIGHT VOLUME -- ------- -------- -- ------- -------- 04 118.4 25431 02 59.2 12732 03 88.8 20608 01 29.6 4856 - - - - - - - - - - - - - - - - - - - - - - - - - TANK ID: 1 CHART ID: 1 LABEL: +ACoAKgAqACoAKg- TYPE: Four Point SOURCE: User Entered LAST CHANGE: 2016-10-19 STATUS: Active VOLUME ENTRY: Total Volume +ACM- HEIGHT VOLUME +ACM- HEIGHT VOLUME --- ------- -------- --- ------- -------- 001 118.4 25431 003 59.2 12732 002 88.8 20608 004 29.6 4856 - - - - - - - - - - - - - - - - - - - - - - - - - T1 SIPHON MANIFOLDED TO TANKS: NONE T1 LINE MANIFOLDED TO TANKS: NONE - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - HRM WARNING LIMIT: 1 GALLONS ALARM LIMIT: 1 GALLONS MAXIMUM CEILING LIMIT: 132 GALLONS - - - - - - - - - - - - - - - - - - - - - - - - - +AD0APQA9AD0APQA9AD0APQA9AD0APQA9AD0APQA9- SETUP FOR TANK 2 +AD0APQA9AD0APQA9AD0APQA9AD0APQA9AD0APQA9AD0- CONFIGURED: YES LABEL: PREMIUM-8K PRODUCT CODE: 2 PROBE NUMBER: 2 PROBE OFFSET: 0.00 INCHES FULL VOLUME: 7901 GALLONS DIAMETER: 118.4 INCHES TILT: 0.00 INCHES THERMAL COEFFICIENT: 0.000700 METER DATA PRESENT: NO PUMP THRESHOLD: 10 GALLONS DELIVERY DELAY: 5 MINUTES GROSS TEST FAIL: ALARMS DISABLED PERIODIC TEST FAIL: ALARMS DISABLED ANNUAL TEST FAIL: ALARMS DISABLED GOST VOLUME CORRECTION: DISABLED - - - - - - - - - - - - - - - - - - - - - - - - - MAX VOLUME: 7901 GALLONS HIGH PRODUCT: 95+ACU- DELIVERY OVERFILL: 90+ACU- DELIVERY LIMIT: 0+ACU- LOW PRODUCT: 0 GALLONS HIGH WATER WARNING: -0.25 INCHES HIGH WATER ALARM: 1.00 INCHES WATER ALARM FILTER LEVEL: LOW WATER ALARM FILTER DELAY: 180 S LEAK ALARM LIMIT: 10 GALLONS SUDDEN LOSS LIMIT: 25 GALLONS FUEL HIGH TEMP LIMIT: 140.000 DEG F FUEL LOW TEMP LIMIT: -58.000 DEG F - - - - - - - - - - - - - - - - - - - - - - - - - TANK TEST METHOD: SLD LEAK TEST RATE: 0.200 GPH PERIODIC TEST TYPE: STANDARD TEST FREQUENCY: On Date 01/01/2017 01:00 GROSS TEST AUTO CONFIRM: DISABLED TANK TEST SIPHON BREAK: OFF DURATION: 2 HOURS MINIMUM PERIODIC VOLUME: 0.0 +ACU- MINIMUM ANNUAL VOLUME: 0.0 +ACU- EARLY STOP: DISABLED TANK TEST NOTIFY: DISABLED - - - - - - - - - - - - - - - - - - - - - - - - - TANK PROFILE: Four Point +ACM- HEIGHT VOLUME +ACM- HEIGHT VOLUME -- ------- -------- -- ------- -------- 04 118.4 7901 02 59.2 3964 03 88.8 6365 01 29.6 1560 - - - - - - - - - - - - - - - - - - - - - - - - - TANK ID: 2 CHART ID: 1 LABEL: +ACoAKgAqACoAKg- TYPE: Four Point SOURCE: User Entered LAST CHANGE: 2016-10-19 STATUS: Active VOLUME ENTRY: Total Volume +ACM- HEIGHT VOLUME +ACM- HEIGHT VOLUME --- ------- -------- --- ------- -------- 001 118.4 7901 003 59.2 3964 002 88.8 6365 004 29.6 1560 - - - - - - - - - - - - - - - - - - - - - - - - - T2 SIPHON MANIFOLDED TO TANKS: NONE T2 LINE MANIFOLDED TO TANKS: NONE - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - HRM WARNING LIMIT: 1 GALLONS ALARM LIMIT: 1 GALLONS MAXIMUM CEILING LIMIT: 132 GALLONS - - - - - - - - - - - - - - - - - - - - - - - - - +AD0APQA9AD0APQA9AD0APQA9AD0APQA9AD0APQA9- SETUP FOR TANK 3 +AD0APQA9AD0APQA9AD0APQA9AD0APQA9AD0APQA9AD0- CONFIGURED: YES LABEL: DIESEL-10K PRODUCT CODE: 3 PROBE NUMBER: 3 PROBE OFFSET: 0.00 INCHES FULL VOLUME: 10420 GALLONS DIAMETER: 118.4 INCHES TILT: 0.00 INCHES THERMAL COEFFICIENT: 0.000450 METER DATA PRESENT: NO PUMP THRESHOLD: 10 GALLONS DELIVERY DELAY: 5 MINUTES GROSS TEST FAIL: ALARMS DISABLED PERIODIC TEST FAIL: ALARMS DISABLED ANNUAL TEST FAIL: ALARMS DISABLED GOST VOLUME CORRECTION: DISABLED - - - - - - - - - - - - - - - - - - - - - - - - - MAX VOLUME: 10420 GALLONS HIGH PRODUCT: 95+ACU- DELIVERY OVERFILL: 90+ACU- DELIVERY LIMIT: 0+ACU- LOW PRODUCT: 0 GALLONS HIGH WATER WARNING: -0.25 INCHES HIGH WATER ALARM: 1.00 INCHES WATER ALARM FILTER LEVEL: LOW WATER ALARM FILTER DELAY: 180 S LEAK ALARM LIMIT: 10 GALLONS SUDDEN LOSS LIMIT: 25 GALLONS FUEL HIGH TEMP LIMIT: 140.000 DEG F FUEL LOW TEMP LIMIT: -58.000 DEG F - - - - - - - - - - - - - - - - - - - - - - - - - TANK TEST METHOD: SLD LEAK TEST RATE: 0.200 GPH PERIODIC TEST TYPE: STANDARD TEST FREQUENCY: On Date 01/01/2017 01:00 GROSS TEST AUTO CONFIRM: DISABLED TANK TEST SIPHON BREAK: OFF DURATION: 2 HOURS MINIMUM PERIODIC VOLUME: 0.0 +ACU- MINIMUM ANNUAL VOLUME: 0.0 +ACU- EARLY STOP: DISABLED TANK TEST NOTIFY: DISABLED - - - - - - - - - - - - - - - - - - - - - - - - - TANK PROFILE: Four Point +ACM- HEIGHT VOLUME +ACM- HEIGHT VOLUME -- ------- -------- -- ------- -------- 04 118.4 10420 02 59.2 5200 03 88.8 8515 01 29.6 1893 - - - - - - - - - - - - - - - - - - - - - - - - - TANK ID: 3 CHART ID: 1 LABEL: +ACoAKgAqACoAKg- TYPE: Four Point SOURCE: User Entered LAST CHANGE: 2016-10-19 STATUS: Active VOLUME ENTRY: Total Volume +ACM- HEIGHT VOLUME +ACM- HEIGHT VOLUME --- ------- -------- --- ------- -------- 001 118.4 10420 003 59.2 5200 002 88.8 8515 004 29.6 1893 - - - - - - - - - - - - - - - - - - - - - - - - - T3 SIPHON MANIFOLDED TO TANKS: NONE T3 LINE MANIFOLDED TO TANKS: NONE - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - HRM WARNING LIMIT: 1 GALLONS ALARM LIMIT: 1 GALLONS MAXIMUM CEILING LIMIT: 132 GALLONS - - - - - - - - - - - - - - - - - - - - - - - - - +AD0APQA9AD0APQA9AD0APQA9AD0APQA9AD0APQA9- SETUP FOR TANK 4 +AD0APQA9AD0APQA9AD0APQA9AD0APQA9AD0APQA9AD0- CONFIGURED: YES LABEL: E0-8K PRODUCT CODE: 4 PROBE NUMBER: 4 PROBE OFFSET: 0.00 INCHES FULL VOLUME: 7901 GALLONS DIAMETER: 118.4 INCHES TILT: 0.00 INCHES THERMAL COEFFICIENT: 0.000700 METER DATA PRESENT: NO PUMP THRESHOLD: 10 GALLONS DELIVERY DELAY: 5 MINUTES GROSS TEST FAIL: ALARMS DISABLED PERIODIC TEST FAIL: ALARMS DISABLED ANNUAL TEST FAIL: ALARMS DISABLED GOST VOLUME CORRECTION: DISABLED - - - - - - - - - - - - - - - - - - - - - - - - - MAX VOLUME: 7901 GALLONS HIGH PRODUCT: 95+ACU- DELIVERY OVERFILL: 90+ACU- DELIVERY LIMIT: 0+ACU- LOW PRODUCT: 0 GALLONS HIGH WATER WARNING: -0.25 INCHES HIGH WATER ALARM: 1.00 INCHES WATER ALARM FILTER LEVEL: LOW WATER ALARM FILTER DELAY: 180 S LEAK ALARM LIMIT: 10 GALLONS SUDDEN LOSS LIMIT: 25 GALLONS FUEL HIGH TEMP LIMIT: 140.000 DEG F FUEL LOW TEMP LIMIT: -58.000 DEG F - - - - - - - - - - - - - - - - - - - - - - - - - TANK TEST METHOD: SLD LEAK TEST RATE: 0.200 GPH PERIODIC TEST TYPE: STANDARD TEST FREQUENCY: On Date 01/01/2017 01:00 GROSS TEST AUTO CONFIRM: DISABLED TANK TEST SIPHON BREAK: OFF DURATION: 2 HOURS MINIMUM PERIODIC VOLUME: 0.0 +ACU- MINIMUM ANNUAL VOLUME: 0.0 +ACU- EARLY STOP: DISABLED TANK TEST NOTIFY: DISABLED - - - - - - - - - - - - - - - - - - - - - - - - - TANK PROFILE: Four Point +ACM- HEIGHT VOLUME +ACM- HEIGHT VOLUME -- ------- -------- -- ------- -------- 04 118.4 7901 02 59.2 3964 03 88.8 6365 01 29.6 1560 - - - - - - - - - - - - - - - - - - - - - - - - - TANK ID: 4 CHART ID: 1 LABEL: +ACoAKgAqACoAKg- TYPE: Four Point SOURCE: User Entered LAST CHANGE: 2016-10-19 STATUS: Active VOLUME ENTRY: Total Volume +ACM- HEIGHT VOLUME +ACM- HEIGHT VOLUME --- ------- -------- --- ------- -------- 001 118.4 7901 003 59.2 3964 002 88.8 6365 004 29.6 1560 - - - - - - - - - - - - - - - - - - - - - - - - - T4 SIPHON MANIFOLDED TO TANKS: NONE T4 LINE MANIFOLDED TO TANKS: NONE - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - HRM WARNING LIMIT: 1 GALLONS ALARM LIMIT: 1 GALLONS MAXIMUM CEILING LIMIT: 132 GALLONS - - - - - - - - - - - - - - - - - - - - - - - - - +AAMAAQ- I70300 08/20/24 11:52 AM LIQUID MODEL SENSOR LABEL MODEL 1 Unleaded Interstitia Tri-State(Single Float) 2 Premium Interstitial Tri-State(Single Float) 3 Unleaded STP Sump Tri-State(Single Float) 4 E0-STP Sump Tri-State(Single Float) 5 Diesel STP Sump Tri-State(Single Float) 6 Premium STP Sump Tri-State(Single Float) 7 Dissp.1+ACY-2 Tri-State(Single Float) 8 Disp.3+ACY-4 Tri-State(Single Float) 9 Disp.5+ACY-6 Tri-State(Single Float) 10 Disp.7+ACY-8 Tri-State(Single Float) 11 Disp.9+ACY-10 Tri-State(Single Float) 12 Disp.9+ACY-10 Tri-State(Single Float) 13 Disp.11+ACY-12 Tri-State(Single Float) 14 Disp.13+ACY-14 Tri-State(Single Float) 15 Disp.15+ACY-16 Tri-State(Single Float) 16 Tri-State(Single Float) 17 Tri-State(Single Float) 18 Tri-State(Single Float) 19 Tri-State(Single Float) 20 Tri-State(Single Float) 21 Tri-State(Single Float) 22 Tri-State(Single Float) 23 Tri-State(Single Float) 24 Tri-State(Single Float) 25 Tri-State(Single Float) 26 Tri-State(Single Float) 27 Tri-State(Single Float) 28 Tri-State(Single Float) 29 Tri-State(Single Float) 30 Tri-State(Single Float) 31 Tri-State(Single Float) 32 Tri-State(Single Float) 33 Tri-State(Single Float) 34 Tri-State(Single Float) 35 Tri-State(Single Float) 36 Tri-State(Single Float) 37 Tri-State(Single Float) 38 Tri-State(Single Float) 39 Tri-State(Single Float) 40 Tri-State(Single Float) 41 Tri-State(Single Float) 42 Tri-State(Single Float) 43 Tri-State(Single Float) 44 Tri-State(Single Float) 45 Tri-State(Single Float) 46 Tri-State(Single Float) 47 Tri-State(Single Float) 48 Tri-State(Single Float) 49 Tri-State(Single Float) 50 Tri-State(Single Float) 51 Tri-State(Single Float) 52 Tri-State(Single Float) 53 Tri-State(Single Float) 54 Tri-State(Single Float) 55 Tri-State(Single Float) 56 Tri-State(Single Float) 57 Tri-State(Single Float) 58 Tri-State(Single Float) 59 Tri-State(Single Float) 60 Tri-State(Single Float) 61 Tri-State(Single Float) 62 Tri-State(Single Float) 63 Tri-State(Single Float) 64 Tri-State(Single Float) 65 Tri-State(Single Float) 66 Tri-State(Single Float) 67 Tri-State(Single Float) 68 Tri-State(Single Float) 69 Tri-State(Single Float) 70 Tri-State(Single Float) 71 Tri-State(Single Float) 72 Tri-State(Single Float) 73 Tri-State(Single Float) 74 Tri-State(Single Float) 75 Tri-State(Single Float) 76 Tri-State(Single Float) 77 Tri-State(Single Float) 78 Tri-State(Single Float) 79 Tri-State(Single Float) 80 Tri-State(Single Float) 81 Tri-State(Single Float) 82 Tri-State(Single Float) 83 Tri-State(Single Float) 84 Tri-State(Single Float) 85 Tri-State(Single Float) 86 Tri-State(Single Float) 87 Tri-State(Single Float) 88 Tri-State(Single Float) 89 Tri-State(Single Float) 90 Tri-State(Single Float) 91 Tri-State(Single Float) 92 Tri-State(Single Float) 93 Tri-State(Single Float) 94 Tri-State(Single Float) 95 Tri-State(Single Float) 96 Tri-State(Single Float) 97 Tri-State(Single Float) 98 Tri-State(Single Float) 99 Tri-State(Single Float) +AAM- W.O.# NW1-2366803 Cust Ref#: 69825850 OVF W.O.# NW1-2366803 Cust Ref#: 69825850 UDC PIPE PAINTED