HomeMy WebLinkAboutDDW-2024-011546Sanitary Survey - Deficiency Report
PWS Number:UTAH27089 Deficiency Points:50 Survey Date:09/25/2024
Survey Name:BIG PLAINS WATER SSD -
CEDAR POINT
Surveyor:J. Paul Wright
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Wells | WS003 | WELL 59
89B. Pump to waste line equipped with #4 non-corrodible mesh screen
Rule: R309-515-6(12)(d)(ix)The discharge end of the pump-to-waste line shall be covered with a No. 4 mesh
corrosion-resistant screen. This significant deficiency must be corrected within 120
days of notification or have a corrective action plan approved by DDW.
Notes:#4 screen missing at time of survey.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: S010 END OF WELL PUMP-TO-WASTE LINE LACKS NO. 4 SCREEN
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST003 | 1M GAL STORAGE TANK
129A. Vent is either down-turned or shielded from contaminants (at least 2 inches below the bottom of the opening)
Rule: R309-545-15(1)Rule requires inverted vents on water storage tanks to be down-turned a minimum of 2
inches below any opening and shielded to prevent the entrance of contaminants. This
significant deficiency must be corrected within 120 days of notification or have a
corrective action plan approved by DDW.
Notes:The shroud around the air vent opening only comes down to the bottom (and not 2 inches
below) of the air vent opening. We discussed a simple fix on site to extend the shroud an
additional 2+ inches.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V005 STORAGE FACILITY VENT NOT DOWNTURNED AT LEAST 2 INCHES BELOW
ANY OPENING