Loading...
HomeMy WebLinkAboutDDW-2024-011546Sanitary Survey - Deficiency Report PWS Number:UTAH27089 Deficiency Points:50 Survey Date:09/25/2024 Survey Name:BIG PLAINS WATER SSD - CEDAR POINT Surveyor:J. Paul Wright Sanitary Survey Category: SO SDWIS Severity Code: Significant Deficiency Wells | WS003 | WELL 59 89B. Pump to waste line equipped with #4 non-corrodible mesh screen Rule: R309-515-6(12)(d)(ix)The discharge end of the pump-to-waste line shall be covered with a No. 4 mesh corrosion-resistant screen. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:#4 screen missing at time of survey. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: S010 END OF WELL PUMP-TO-WASTE LINE LACKS NO. 4 SCREEN Sanitary Survey Category: FW SDWIS Severity Code: Significant Deficiency Storage Tanks | ST003 | 1M GAL STORAGE TANK 129A. Vent is either down-turned or shielded from contaminants (at least 2 inches below the bottom of the opening) Rule: R309-545-15(1)Rule requires inverted vents on water storage tanks to be down-turned a minimum of 2 inches below any opening and shielded to prevent the entrance of contaminants. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:The shroud around the air vent opening only comes down to the bottom (and not 2 inches below) of the air vent opening. We discussed a simple fix on site to extend the shroud an additional 2+ inches. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: V005 STORAGE FACILITY VENT NOT DOWNTURNED AT LEAST 2 INCHES BELOW ANY OPENING