HomeMy WebLinkAboutDDW-2024-011513Sanitary Survey - Deficiency Report
PWS Number:UTAH22080 Deficiency Points:40 Survey Date:09/24/2024
Survey Name:PINES RANCH Surveyor:Tom McOmie
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Springs | WS001 | PINES RANCH SPRING
63. No deep-rooted vegetation is within the 50 ft collection area.
Rule: R309-515-7(7)(f)All deep-rooted vegetation within the fenced collection area shall be removed by a
means not negatively affecting water quality. This significant deficiency must be
corrected within 120 days of notification or have a corrective action plan approved by
DDW.
Notes:Needs to clear out the willows.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: SS07 DEEP ROOTED VEGETATION IN SPRING COLLECTION AREA
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Springs | WS001 | PINES RANCH SPRING
65. Is a spring collection box present? ... if yes, answer the following question(s)
Rule: R309-515-7(7)(c)Rule requires each spring collection area to be provided with at least one collection box
to permit spring inspection and testing.
Notes:Its not that kind of a system.
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: L014 SPRING COLLECTION BOX NOT PRESENT
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Springs | WS001 | PINES RANCH SPRING
66. Is a spring box vent present? ... if yes, answer the following question(s)
Rule: R309-515-7(7)(d), R309-545-15 Rule requires junction boxes and collection boxes to comply with R309-545 with respect
to venting. Therefore, a junction or collection box requires a vent to be fitted with #14
mesh or finer non-corrodible screen, be fitted with a protective heavy-gauge screen or
covering if 6 inches in diameter or greater, be down-turned and shielded to prevent the
entrance of contaminants, be located and sized to avoid blockage during winter, and
have the end of the vent discharge a minimum of 24 inches above the earth on buried
structures.
Notes:Issued 2007 / There is no spring box.
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: SS11 SPRING BOX LACKS A MEANS OF VENTING
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Springs | WS001 | PINES RANCH SPRING
67. Spring has a permanent flow-measuring device.
Rule: R309-515-7(7)(h)Rule requires a spring to have a permanent flow measuring device.
Notes:Issued 2021 / This is a sealed system and you don't see the water until it enters the tank.
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: SS01 LACKS A PERMANENT DEVICE FOR MEASURING SPRING FLOW