HomeMy WebLinkAboutDDW-2024-011467System Number 17007
1.1 Indoor Water Use
Number of residential connections - - - - - - - - - - -- - - - - - - - - - - - - - - - - - -- - - - - - - - -38
Number of other connections - - - 0 ERCs of other connections 0.0
Total Equivalent Residential Connections (ERCs)38.0
gpd/ERC Total (gpm) Gallons/ERC Total (gallons)
800 21.1 400 15,200
1.2 Outdoor Water Use
Is the drinking water used for outdoor irrigation?
Residential ERCs using drinking water for irrigation - - - - - - - - - - - - > > >38
Percentage of Residential ERCs using DW for irrigation - - - - - - - - - - - - > > >100%Map Zones
Average irrigated acreage per residential connection - - - - - - - - - - - - > > >0.05 1
Total irrigated acreage of other connections (park, school, etc.)- - - - - - - - - - - - > > >0.00 2
Irrigation zone 2 3
4
5
6
gpd/ERC Total (gpm) Gallons/ERC Total (gallons)
202 5.3 94 3,559
1.3 Fire Flow Water Use
Does the water system provide fire protection?
Maximum fire flow demand (in gpm) for water system or pressure zone 0
Maximum fire suppression duration (in hours) for water system or pressure zone 0
Required Fire Suppression Storage (in gallons) - - - - - - - - - - - - - - - - - - - - > > >0
2. Summary of Water System Capacity Requirements
gpd/ERC Total (gpm) Gallons/ERC Total (gallons)
1,002 26.4 494 18,759
2.1 Does this system have adequate source capacity (per R309-510-7)?
Required Source Capacity 26.4 gpm
Existing Source Capacity 60.0 gpm
Source Capacity Deficit None gpm
Existing % of Total Req'd 227.0%
MIN. REQUIREMENTS FOR INDOOR WATER USE
MINIMUM REQUIREMENTS FOR WATER SYSTEM
Division of Drinking Water — Water System Capacity Calculation Sheet (Last Update 3/30/2017)
*Enter the green cells only*
(Example: water use of 2 factories
equals to water use of 55 homes.)
Source
MIN. REQUIREMENTS FOR IRRIGATION USE
System Name
Source
South Bear Lake
Storage
Fire flow provided by others.
(Enter notes here regarding whether and what %
of irrigation water is supplied by PWS.)
Source (indoor + outdoor)
Storage
Storage (indoor + outdoor + fire)
This source capacity assessment is a general overall system calculation. It may not reflect the variations in individual areas or pressure zones.
Yes No
Yes No
Enter number of non-residential connections, e.g., 2 industrial connections.
Convert "Number of other connections" (Cell E9) to ERCs here. [ERCs of other
connections = peak day demand of other connections in gal per day / 800 gpd]
Enter estimated irrigated acre
Enter total irrigated acres of other connections here.
Enter fire flow in gpm.
Enter duration in hours.
Autolink to 4.2 "Total Existing Source Capacity" cell below.
Select Irrigated Zone # from the pick list. See "Irrigation Demands & Map" tab on the bottom of the screen or WaterLink.
Less than 100% indicates: (1) additional source capacity is needed, and
(2) source deficiency should be assessed.
Autolink to 2 "Total Source" cell above.
Source deficit indicates that: (1) additional source capacity is needed, and (2) source deficiency should be assessed.
2021Capacity_17007 Page 1 of 2 8/17/2021
2.2 Does this system have adequate storage capacity (per R309-510-8)?
Total Required Storage 18,759 gal
Existing Storage Capacity 12,000 gal
Storage Capacity Deficit 6,759 gal
Required Fire Storage 0 gal
NO
Existing % of Total Req'd 64.0%
3. Transient PWS Indoor Water Use — ERC Calcuation (See R309-510, Tables 510-1, 2, & 4 for other facility types.)
GPD/person* GPD/site or pad Gallons/person
Gallon/site
or pad ERC/site or pad Total # of
sites/pads ERCs
35 0 17.5 0 0.04 0 0.0
20 0 10 0 0.00 0 0.0
5 0 2.5 0 0.00 0 0.0
N/A 100 N/A 50 0.13 0 0.0
Number of people per camp site 0
Source
(GPD/vehicle)
Storage
(Gal./vehicle)
ERC/1000
vehicles served
Vehicles
served/day ERCs
7 3.5 8.8 0 0.0
4. Data Input for Calculating ERCs, Source and Storage 4.2 Summary - Existing Sources (enter in green cells below)
Total Existing Source Capacity (in gpm)60
4.1 Projected ERCs Calculation (optional)WS001 SBL Well 1 60
Total Projected ERCs 38
Existing Residential Connections 38
Obligated Future ERCs (enter below)
Maximum ERCs (assuming indoor use only) 108
4.3 Summary - Existing Storage Tanks (enter below)
Total Existing Storage Cap. (in gallons)12,000
ST001 Tank 1 12,000
RV Park
Facility Type
Source
MINIMUM REQUIREMENTS FOR INDOOR USE
Restaurants
Storage
Semi-Developed Camp w/ flush toilets
South Bear Lake
Roadway Rest Stop w/ flushometer valves
Semi-Developed Camp w/o flush toilets
This storage capacity assessment is a general overall system calculation. It may not reflect the variations in individual areas or pressure zones.
Is storage deficiency solely due
to fire storage?
Autolink to 4.3 "Total Existing Storage Capcity" cell below.
If applicable, enter number of people per camp site here.
Storage deficit indicates that: (1) additional storage volume is needed,
and (2) storage deficiency should be assessed.
Use this number in Cell I8 ("Number of residential connections") on Page 1 to calculate PROJECTED demand & req'ts (including both existing & future connections).
Diaphragm or air pressure tanks shall NOT be considered effective storage volume for (1) community systems, or (2) NTNC with significant demand UNLESS an exception has been granted.
Autolink to 2 "Total Storage" cell above.
If applicable, use this number in cell I8 or cell I9 on Page 1.
If NO, answer one of question set 2.01 to 2.05 in ESS.
If YES, answer one of question set 2.06 to 2.10 in ESS.
Less than 100% indicates: (1) additional storage capacity is needed, and (2) storage deficiency should be assessed.
2021Capacity_17007 Page 2 of 2 8/17/2021