HomeMy WebLinkAboutDDW-2024-011443Sanitary Survey - Deficiency Report
PWS Number:UTAH19067 Deficiency Points:105 Survey Date:09/13/2024
Survey Name:NIZHONI CAMPGROUND Surveyor:David Kruse
Sanitary Survey Category: DS
SDWIS Severity Code: Significant Deficiency
Distribution | DS001 | UTAH19067 DISTRIBUTION SYSTEM
44. Blow offs or air release valves do not discharge below flood level in ditches or streams.
Rule: R309-550-9(1) and (2), R309-550-13(2)R309-550-9(1 & 3)
Notes:Blow off (end of the line drain valve) near the large group campsites discharges to below
grade.
Deficiency Points: 50
Days until points become effective on IPS: 120
SDWIS Deficiency Description: D016 DIST SYS LINE CONNECTED TO OR SUBJECT TO CONTAMINATION
Sanitary Survey Category: TR
SDWIS Severity Code: Minor Deficiency
Wells | WS001 | NIZHONI WELL 1
62. No toxic chemicals, hazardous or flammable materials, or lubricants inside the well house or near well head?
Rule: R309-105-7, 8 & 18, R309-100 through
605
Trigger for regulatory followup to address concerns.
Notes:Well discharge line is raised within building which primary purpose is to house generator
supplies. Well discharge line has a sample tap outside of the building.
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: TGR9 TRIGGER FOR REGULATORY FOLLOWUP TO ADDRESS CONCERNS
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Wells | WS001 | NIZHONI WELL 1
64. Well discharge line has a check valve.
Rule: R309-515-6(12)(d)(iv)Rule requires the discharge piping to be equipped with (in order of placement from the
wellhead) a smooth nosed sampling tap, a check valve, a pressure gauge, a means of
measuring flow, and a shutoff valve.
Notes:No check valve on discharge line.
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: S024 NO CHECK VALVE ON WELL DISCHARGE PIPING
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Wells | WS001 | NIZHONI WELL 1
65. Well discharge line has a pressure gauge.
Rule: R309-515-6(12)(d)(iv)Rule requires the discharge piping to be equipped with (in order of placement from the
wellhead) a smooth nosed sampling tap, a check valve, a pressure gauge, a means of
measuring flow, and a shutoff valve.
Notes:No pressure gauge on discharge line.
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: S025 NO PRESSURE GAUGE ON WELL DISCHARGE PIPING
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Wells | WS001 | NIZHONI WELL 1
66. Well discharge line has a means to measure flow.
Rule: R309-515-6(12)(d)(iv)Rule requires the discharge piping to be equipped with (in order of placement from the
wellhead) a smooth nosed sampling tap, a check valve, a pressure gauge, a means of
measuring flow, and a shutoff valve.
Notes:No means to measure flow on discharge line.
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: S026 NO FLOW METER ON WELL DISCHARGE PIPING
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST001 | STORAGE FACILITY ST001
83B. Overflow line covered with #4 mesh non-corrodible screen
Rule: R309-545-13(3)Rule requires overflow pipes to be screened with #4 mesh non-corrodible screens
installed at a location least susceptible to damage by vandalism. This significant
deficiency must be corrected within 120 days of notification or have a corrective action
plan approved by DDW.
Notes:Screen needs replacement.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V012 END OF STORAGE TANK OVERFLOW PIPE LACKS NO. 4 SCREEN