PWS Number:UTAH19018 Deficiency Points:180 Survey Date:09/13/2024
Survey Name:DEVILS CANYON
CAMPGROUND
Surveyor:David Kruse
Sanitary Survey Category: SM
SDWIS Severity Code: Significant Deficiency
General Maintenance and Environment | DS001 | UTAH19018 DISTRIBUTION SYSTEM
39. Are there any visual indications of unsanitary conditions?
Rule: R309-200-6, R309-105-18, R309-215-4(3)R309-200-6 The Secondary Maximum Contaminant Levels for public water systems
deals with substances which affect the aesthetic quality of drinking water. They are
presented here as recommended limits or ranges and are not grounds for rejection. The
taste of water may be unpleasant and the usefulness of the water may be impaired if
these standards are significantly exceeded.
R309-105-18 The Director or the local health department shall be informed by
telephone by a water supplier of any "emergency situation". The term "emergency
situation...
R309-215-4(3) If the water fails to meet minimum standards, then certain public
notification procedures shall be carried out, as outlined in R309-220. Water suppliers
shall also keep analytical records in their possession, for a required length of time, as
outlined in R309-105-17.
Notes:A dead mouse was observed floating in what is considered the spring collection box. At that
point in time, the system was already drained of all water due to a pump failure. System was
directed to remove the mouse and drain the spring. Complete disinfection will be required
prior to placing the system back online.
Deficiency Points: 50
Days until points become effective on IPS: 120
SDWIS Deficiency Description: M017 WATER STAGNATION, BIOFILM OR SEDIMENTS CONTRIBUTES TO DRINKING
WATER CONTAMINATION
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Springs | WS001 | SPRING
62B. Spring box lid is gasketed
Rule: R309-515-7(7)(d), R309-545-14 (2)Access openings shall comply with R309-545 and be provided with a cover furnished
with a gasket between the lid and frame. This significant deficiency must be corrected
within 120 days of notification or have a corrective action plan approved by DDW.
Notes:A gasket was not observed during the inspection. Please ensure that the second door
containing the spring collection basin is adequately sealed.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: SS10 SPRING BOX LID LACKS A GASKET
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Springs | WS001 | SPRING
62F. All openings/penetrations in the spring collection box are sealed.
Rule: R309-515-7(7)(d), R309-545-9(1) and (2)All junction and collection boxes shall comply with R309-545 and shall have suitable
watertight roofs and sidewalls that exclude birds, animals, insects, and excessive dust.
All openings shall be kept to a minimum and be watertight. Pipes that may contain
water of lesser quality than drinking water shall not penetrate the spring box. This
significant deficiency must be corrected within 120 days of notification or have a
corrective action plan approved by DDW.
Notes:The two doors which contain the spring are not sealed. Please work to completely seal the
openings around both doors to ensure that critters cannot access the spring collection basin.
Deficiency Points: 50
Days until points become effective on IPS: 120
SDWIS Deficiency Description: SS20 UNSEALED OPENINGS IN SPRING COLLECTION BOX
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Springs | WS001 | SPRING
64. Spring has a permanent flow-measuring device.
Rule: R309-515-7(7)(h)Rule requires a spring to have a permanent flow measuring device.
Notes:No permanent flow measuring device.
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: SS01 LACKS A PERMANENT DEVICE FOR MEASURING SPRING FLOW
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST001 | LOWER TANK
77B. Overflow line covered with #4 mesh non-corrodible screen
Rule: R309-545-13(3)Rule requires overflow pipes to be screened with #4 mesh non-corrodible screens
installed at a location least susceptible to damage by vandalism. This significant
deficiency must be corrected within 120 days of notification or have a corrective action
plan approved by DDW.
Notes:Overflow line screen has degraded and is no longer sealed. Please replace overflow line
screen.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V012 END OF STORAGE TANK OVERFLOW PIPE LACKS NO. 4 SCREEN
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST002 | UPPER TANK
85C. Access opening lid properly gasketed
Rule: R309-545-14(2)Rule requires the access opening to a tank to be furnished with a gasket between the lid
and frame. This significant deficiency must be corrected within 120 days of notification
or have a corrective action plan approved by DDW.
Notes:Gasket has degraded and is no longer in place. Please replace gasket.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V009 STORAGE TANK LID LACKS A FUNCTIONING GASKET BETWEEN THE LID AND
FRAME