HomeMy WebLinkAboutDDW-2024-011396Sanitary Survey - Deficiency Report PWS Number:UTAH27069 Deficiency Points:80 Survey Date:09/25/2024 Survey Name:BIG PLAINS WATER SSD - APPLE VALLEY Surveyor:J. Paul Wright Sanitary Survey Category: SO SDWIS Severity Code: Significant Deficiency Wells | WS003 | GREGERSON WELL 80. Wellhead is sealed to prevent contamination. Rule: R309-515-6(6)(i)R309-515-6(6)(i) and R309-515-6(12)(b,c,d)require a sanitary seal be installed and maintained at the wellhead and discharge piping. This significant deficiency should be corrected within 120 days of notification or have a corrective action plan approved by Notes:A new sounding tube had been installed and needed caulk. It was deficient at time of visit, but they fixed it on site. A photo will be sent with the sanitary survey to show the fix and to resolve the deficiency. Deficiency Points: 50 Days until points become effective on IPS: 120 SDWIS Deficiency Description: S013 WELL LACKS THE REQUIRED WELL SEAL Sanitary Survey Category: FW SDWIS Severity Code: Minor Deficiency Storage Tanks | ST001 | STORAGE FACILITY ST001 107A. Mild deterioration or spalling? Rule: R309-545-6(1) and 545-9(1)Rule requires all water storage tanks to have suitable watertight roofs and sidewalls that shall also exclude birds, animals, insects, and excessive dust. Notes:Existing on IPS Report, they are looking to replace these tanks. Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: V021 STORAGE TANK ROOF OR SIDEWALLS SHOW SIGNS OF MILD OR MODERATE DETERIORATION Sanitary Survey Category: FW SDWIS Severity Code: Minor Deficiency Storage Tanks | ST002 | STORAGE FACILITY ST002 121A. Mild deterioration or spalling? Rule: R309-545-6(1) and 545-9(1)Rule requires all water storage tanks to have suitable watertight roofs and sidewalls that shall also exclude birds, animals, insects, and excessive dust. Notes:Existing on IPS Report, they are looking to replace these tanks. Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: V021 STORAGE TANK ROOF OR SIDEWALLS SHOW SIGNS OF MILD OR MODERATE DETERIORATION