September 19, 2024
Todd R Poulsen
Skyline Mine
9815 S Monroe St, Ste 203
Sandy, Utah 84070
Subject: Increased Monitoring Requirements – Source Sampling of Well #1 (WS001); Skyline Mine,
UTAH04040
Dear Todd Poulsen:
Skyline Mine is required to conduct increased sampling at Well #1 (WS001) to investigate the quality of that
source.
1. With system name here request to uninstall treatment, this source water quality evaluation has added the
following monitoring requirement for your system:
Facility with
new
requirements
Facility
ID
Sample
Point ID
Analyte(s)
Required
# of
samples
Sampling
Frequency
Next Due
Date
Rule Reference
Well #1
(WS001)
WS001 WS001 Total Coliform;
E. coli
1 Each Monthly 09/01/2024-
09/30/2024
R309-215-16(b)
Well #1
(WS001)
WS001
WS001
Iron 1 Quarterly 10/01/2024-
12/31/2024
R309-215-6(2)
Manganese 1 Quarterly 10/01/2024-
12/31/2024
R309-215-6(2)
TDS 1 Quarterly 10/01/2024-
12/31/2024
R309-215-6(2)
Turbidity 1 Quarterly 10/01/2024-
12/31/2024
R309-215-6(2)
WTP & CL2
(TP001)
TP001
TP001
Iron 1 Quarterly 10/01/2024-
12/31/2024
R309-215-6(2)
Manganese 1 Quarterly 10/01/2024-
12/31/2024
R309-215-6(2)
TDS 1 Quarterly 10/01/2024-
12/31/2024
R309-215-6(2)
Turbidity 1 Quarterly 10/01/2024-
12/31/2024
R309-215-6(2)
2. Treatment cannot be uninstalled until this sampling has been completed. The sampling requirements
presented above will remain in place for a minimum of four quarters.
3. All bacteriological source samples shall be collected prior to any treatment and/or at a location that
represents the source water quality.
4. The intent of the iron, manganese, turbidity and TDS samples is to determine how filtration may impact
the concentration of these parameters. Please collect the samples listed above.
a. Well #1 (WS001) samples shall be collected directly from the well head, upstream of any
treatment.
b. WQTP & CL2 (TP001) samples shall be collected immediately downstream of the filter at a
location that represented the water after it has undergone treatment, and before it has entered the
distribution system,
5. Label all source samples with the facility name and code listed above as the sampling location and
facility code.
Please note that this bacteriological source sampling requirement is in addition to the distribution system
bacteriological sampling requirement already in place. All distribution samples must be labeled with sample
location/sample address and DS001 for the facility code.
You can find the current monitoring schedule for your water system at waterlink.utah.gov by selecting your system
and then selecting Water Monitoring under Water System Reports.
Thank you for your efforts in protecting the drinking water quality in your water system and protecting public
health. If you have any questions regarding these increased bacteriological monitoring requirements for, please
contact Sitara Federico of the Division at (385)-515-1459 or sfederico@utah.gov. Please contact David Kruse at
(385)-566-7789 or dbkruse@utah.gov with any questions related to source monitoring requirements.
Sincerely,
Mark Berger
Monitoring and Standards Section Manager
cc: Todd R Poulsen, tpoulsen@wolverinefuels.com
Orion Rogers, Southeastern Utah District Health Department
Curtis Page, District Engineer, cmpage@utah.gov
Sitara Federico, Division of Drinking Water, sfederico@utah.gov
David Kruse, Division of Drinking Water, dbkruse@utah.gov
VSA Team, Division of Drinking Water, EQDWVSA@utah.gov