HomeMy WebLinkAboutDDW-2024-011365Sanitary Survey - Deficiency Report
PWS Number:UTAH08008 Deficiency Points:40 Survey Date:09/23/2024
Survey Name:ORANGEVILLE Surveyor:Danielle Zebelean
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST002 | ORANGEVILLE TANK ST002
73C. Access opening lid properly gasketed
Rule: R309-545-14(2)Rule requires the access opening to a tank to be furnished with a gasket between the lid
and frame. This significant deficiency must be corrected within 120 days of notification
or have a corrective action plan approved by DDW.
Notes:Could not unlock the lid to check the gasket
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V009 STORAGE TANK LID LACKS A FUNCTIONING GASKET BETWEEN THE LID AND
FRAME
Sanitary Survey Category: TR
SDWIS Severity Code: Minor Deficiency
Treatment - General | TP001 | STRAIGHT CANYON MEMBRANE WTP
93B. There are adequate spill containment provisions for acid and caustic liquids.
Rule: R309-525-11(6)(a)(iv)(B), R309-525-
11(8)(b)(viii)
Rule requires liquid chemical storage tanks to have an overflow and receiving basin or
drain capable of receiving accidental spills or overflows, and meeting all the
requirements of R309-525-23.
Notes:Lacks secondary containment for chemicals used for CIP on membranes
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: TG59 LACKS CONTAINMENT PROVISIONS TO HANDLE SOLUTION TANK SPILLS OR
OVERFLOWS