Loading...
HomeMy WebLinkAboutDDW-2024-011365Sanitary Survey - Deficiency Report PWS Number:UTAH08008 Deficiency Points:40 Survey Date:09/23/2024 Survey Name:ORANGEVILLE Surveyor:Danielle Zebelean Sanitary Survey Category: FW SDWIS Severity Code: Significant Deficiency Storage Tanks | ST002 | ORANGEVILLE TANK ST002 73C. Access opening lid properly gasketed Rule: R309-545-14(2)Rule requires the access opening to a tank to be furnished with a gasket between the lid and frame. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:Could not unlock the lid to check the gasket Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: V009 STORAGE TANK LID LACKS A FUNCTIONING GASKET BETWEEN THE LID AND FRAME Sanitary Survey Category: TR SDWIS Severity Code: Minor Deficiency Treatment - General | TP001 | STRAIGHT CANYON MEMBRANE WTP 93B. There are adequate spill containment provisions for acid and caustic liquids. Rule: R309-525-11(6)(a)(iv)(B), R309-525- 11(8)(b)(viii) Rule requires liquid chemical storage tanks to have an overflow and receiving basin or drain capable of receiving accidental spills or overflows, and meeting all the requirements of R309-525-23. Notes:Lacks secondary containment for chemicals used for CIP on membranes Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: TG59 LACKS CONTAINMENT PROVISIONS TO HANDLE SOLUTION TANK SPILLS OR OVERFLOWS