HomeMy WebLinkAboutDDW-2024-011337Sanitary Survey - Deficiency Report PWS Number:UTAH24010 Deficiency Points:75 Survey Date:09/17/2024 Survey Name:JENSEN WID Surveyor:Joe Hadlock Sanitary Survey Category: FW SDWIS Severity Code: Significant Deficiency Storage Tanks | ST001 | NAPLES TANK 59C. Access opening lid properly gasketed Rule: R309-545-14(2)Rule requires the access opening to a tank to be furnished with a gasket between the lid and frame. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:Gasket needs repaired. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: V009 STORAGE TANK LID LACKS A FUNCTIONING GASKET BETWEEN THE LID AND FRAME Sanitary Survey Category: FW SDWIS Severity Code: Significant Deficiency Storage Tanks | ST001 | NAPLES TANK 65B. Overflow line covered with #4 mesh non-corrodible screen Rule: R309-545-13(3)Rule requires overflow pipes to be screened with #4 mesh non-corrodible screens installed at a location least susceptible to damage by vandalism. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:There is a hole in the screen. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: V012 END OF STORAGE TANK OVERFLOW PIPE LACKS NO. 4 SCREEN Sanitary Survey Category: FW SDWIS Severity Code: Significant Deficiency Storage Tanks | ST002 | SUNSHINE BENCH TANK 79. Is a tank overflow present? ... if yes, answer the following question(s) Rule: R309-545-13 Rule requires all storage tanks to be provided with an overflow that discharges at an an elevation between 12 and 24 inches above the ground surface or the rim of the receiving basin. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes: Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: VL01 STORAGE TANK LACKS AN OVERFLOW