HomeMy WebLinkAboutDDW-2024-011288Sanitary Survey - Deficiency Report
PWS Number:UTAH24050 Deficiency Points:25 Survey Date:09/05/2024
Survey Name:JONES HOLE NATIONAL
FISH HATCHERY
Surveyor:Brian Pattee
Sanitary Survey Category: DS
SDWIS Severity Code: Significant Deficiency
Distribution | DS001 | UTAH24050 DISTRIBUTION SYSTEM
44A. Open end of vent line covered with #14 mesh screen
Rule: R309-550-6(6)(b)Rule states the open end of the air relief vent pipe from automatic valves shall be
provided with a #14 mesh, non-corrodible screen and a downward elbow, and where
possible, be extended to at least one foot above grade. This significant deficiency must
be corrected within 120 days of notification or have a corrective action plan approved
by DDW.
Notes:No screen on air vac on line from tank , Air vac was turned off at time of survey .
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: D004 AIR RELIEF VALVE PIPE LACKS NO. 14 SCREEN