HomeMy WebLinkAboutDDW-2024-011235Sanitary Survey - Deficiency Report
PWS Number:UTAH13015 Deficiency Points:70 Survey Date:09/04/2024
Survey Name:CORAL PINK SAND DUNES Surveyor:Luke Treutel
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Wells | WS002 | SAND DUNES WELL 2
62. Provisions available to periodically measure water levels
Rule: R309-515-6(12)(e ), R309-515-6(12)(c)(vi)Rule requires provisions be made to permit periodic measurement of water levels in the
completed well.
Notes:System lacks provisions to periodically check water level in the well
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: S015 WELL LACKS A MEANS TO MEASURE WATER LEVELS PERIODICALLY
Sanitary Survey Category: FW
SDWIS Severity Code: Minor Deficiency
Storage Tanks | ST001 | OLD TANK
86A. Mild deterioration or spalling?
Rule: R309-545-6(1) and 545-9(1)Rule requires all water storage tanks to have suitable watertight roofs and sidewalls
that shall also exclude birds, animals, insects, and excessive dust.
Notes:Cracks on tank wall
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: V021 STORAGE TANK ROOF OR SIDEWALLS SHOW SIGNS OF MILD OR MODERATE
DETERIORATION
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST001 | OLD TANK
86B. Severe deterioration or spalling?
Rule: R309-545-6(1) and 545-9(1)Rule requires all water storage tanks to have suitable watertight roofs and sidewalls
that shall also exclude birds, animals, insects, and excessive dust. This significant
deficiency must be corrected within 120 days of notification or have a corrective action
plan approved by DDW.
Notes:Cracks on tank wall
Deficiency Points: 50
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V022 STORAGE TANK ROOF OR SIDEWALLS SHOW SIGNS OF SEVERE
DETERIORATION