HomeMy WebLinkAboutDERR-2024-010965Utah Department of Environmental Quality - UST Release Detection
TANK OWNERSHIP
Name PETROLEUM WHOLESALE
Address PO BOX 4456
HOUSTON, TX 77210
Contact PETROLEUM WHOLESALE
Phone
Email csmith@petroleumwholesale.com
TANK LOCATION
Name SUNMART #807
Address 885 S PARK AVE
FILLMORE, UT 84631
A Operator KEVIN COLEMAN
Phone (435) 714-0045
B Operator SAME
Phone SAME
Facility ID: 2000693 Inspection Date: 09/23/2024
DISPENSER DETAILS
DISP
ID/ALT
ID
SUBSTANCE UDC PIPE FLEX LOC
INSTALL
DATE
UDC
INSTALL
DATE
FIRE
VALVE
SAT
PRESENT
UDC
TEST
DISP
FLEX
CP
TEST
1 - 1/2 Gasoline Yes Steel Flex in Sump March
16,
1998
March
16,
1998
Yes No None None
2 - 3/4 Gasoline Yes Steel Flex in Sump March
16,
1998
March
16,
1998
Yes No None None
3 - 5/6 Gasoline Yes Steel Flex in Sump March
16,
1998
March
16,
1998
Yes No None None
4 - 7/8 Gasoline Yes Steel Flex in Sump March
16,
1998
March
16,
1998
Yes No None None
5 - 9/10 Gasoline Yes Steel Flex in Sump March
16,
1998
March
16,
1998
Yes No None None
6 -
11/12
Gasoline Yes Steel Flex in Sump March
16,
1998
March
16,
1998
Yes No None None
7 - D
1/2
Diesel Yes Steel Flex in Sump March
16,
1998
March
16,
1998
Yes Yes None None
8 - D
3/2S
Diesel Yes Steel Flex in Sump March
16,
1998
March
16,
1998
Yes No None None
9 - D
4/3S
Diesel Yes Steel Flex in Sump March
16,
1998
March
16,
1998
Yes Yes None None
10 - D
5/4S
Diesel Yes Steel Flex in Sump March
16,
1998
March
16,
1998
Yes Yes None None
11 - D
6/5S
Diesel Yes Steel Flex in Sump March
16,
1998
March
16,
1998
Yes Yes None None
12 - D
7/6S
Diesel Yes Steel Flex in Sump March
16,
1998
March
16,
1998
Yes Yes None None
13 - D
7S
Diesel Yes Steel Flex in Sump March
16,
1998
March
16,
1998
Yes No None None
TANK DETAILS
2024-09-23 Page 1 of 10
Tank ID/Alt ID 1 / 1
E-Gen/AST No / No
Siphon/Compart No / No
Tank Status Currently In Use
Installed/Cap/Loc March 16, 1998 / 12000 / West
Substance Stored Gasoline / Premium
Tank Material-
Mod
Fiberglass Reinforced Plastic-
None
ATG Franklin / TS-550
LTT Test Jan. 23, 2024
LLD Test Jan. 23, 2024
Pipe Material-
Mod Flexible Plastic / Double-Walled
Pipe type/STP
Cont Pressurized / Yes
STP Flex
Connectors Steel Flex in Sump
LLD Model Red Jacket / VR FX1V
Spill/Overfill/Sm
Delivery
5 gal. Spill Bucket / Automatic
shutoff / No
PST Fund/Other
Type Yes / None
Tank/Pipe Rel
Det
TankSIR
PipeAutoLineLeakDetection /
PipeLineTightness
CP Tank Test None
CP Pipe Test None
Tank ID/Alt ID 2 / 2
E-Gen/AST No / No
Siphon/Compart Yes / No
Tank Status Currently In Use
Installed/Cap/Loc March 16, 1998 / 12000 / Center
Substance Stored Gasoline / Regular
Tank Material-
Mod
Fiberglass Reinforced Plastic-
None
ATG Franklin / TS-550
LTT Test Jan. 23, 2024
LLD Test Jan. 23, 2024
Pipe Material-
Mod Flexible Plastic / Double-Walled
Pipe type/STP
Cont Pressurized / Yes
STP Flex
Connectors Steel Flex in Sump
LLD Model Red Jacket / VR FX1V
Spill/Overfill/Sm
Delivery
5 gal. Spill Bucket / Automatic
shutoff / No
PST Fund/Other
Type Yes / None
Tank/Pipe Rel
Det
TankSIR
PipeAutoLineLeakDetection /
PipeLineTightness
CP Tank Test None
CP Pipe Test None
Tank ID/Alt ID 3 / 3
E-Gen/AST No / No
Siphon/Compart Yes / No
Tank Status Currently In Use
Installed/Cap/Loc March 16, 1998 / 12000 / East
Substance Stored Gasoline / Regular
Tank Material-
Mod
Fiberglass Reinforced Plastic-
None
ATG Franklin / TS-550
LTT Test None
LLD Test None
Pipe Material-
Mod
Fiberglass Reinforced Plastic /
None
Pipe type/STP
Cont Siphon Bar / Yes
STP Flex
Connectors Not Listed
LLD Model
Spill/Overfill/Sm
Delivery
5 gal. Spill Bucket / Automatic
shutoff / No
PST Fund/Other
Type Yes / None
Tank/Pipe Rel
Det
TankSIR PipeLDNotListed /
PipeLineTightness
CP Tank Test None
CP Pipe Test None
2024-09-23 Page 2 of 10
Tank ID/Alt ID 4 / 4
E-Gen/AST No / No
Siphon/Compart Yes / No
Tank Status Currently In Use
Installed/Cap/Loc June 22, 2016 / 22000 / Single -
Separate excavation
Substance
Stored Diesel / Diesel #2 (U.L.S.)
Tank Material-
Mod
Composite (Steel w/ FRP)-
Double-Walled
ATG Franklin / TS-550
LTT Test Jan. 23, 2024
LLD Test Jan. 23, 2024
Pipe Material-
Mod Flexible Plastic / Double-Walled
Pipe type/STP
Cont Pressurized / Yes
STP Flex
Connectors Steel Flex in Sump
LLD Model Red Jacket / VR FX1DV
Spill/Overfill/Sm
Delivery
5 gal. Spill Bucket / Automatic
shutoff / No
PST Fund/Other
Type Yes / None
Tank/Pipe Rel
Det
TankInterstitialDblWalled
PipeAutoLineLeakDetection /
PipeLineTightness
CP Tank Test None
CP Pipe Test None
INSPECTION COMMENTS
None
2024-09-23 Page 3 of 10
FACILITY RESPONSES
Financial Responsibility
Financial responsibility method is ok?Yes
The above accurately represents the
facility's release detection records Yes
Operator Training
A Operator current?Yes
B Operator current?Yes
Monthly checklist available and
complete?Yes
Is the site unmanned?Yes
Is a sign posted in a conspicuous area
giving the name and telephone number
of a person in case of an emergency
and if the station is manned part of the
time, are C operators trained?
Yes
Does the site have emergency shutoff
device?Yes
TANK RESPONSES
Tank 1 Spill/Overfill
Tank has a spill prevention device?Yes
Are you able to visually inspect the spill
containment bucket(s) for functionality?
(i.e. are the buckets clean enough to
see cracks, etc?)
Yes
Is the spill containment bucket intact?Yes
Is the spill containment bucket(s) able
to contain a spill? (i.e. is there water,
product, debris, etc in the spill bucket
to prevent it from containing a spill?)
Yes
Tank has an overfill device?Yes
Tank is exempt from this requirement?Yes
Tank 1 Cathodic Protection
Tanks are protected from corrosion?Yes
Piping is protected from corrosion?Yes
Flex connectors at the tank sub-pumps
are protected from corrosion?Yes
Containment sumps are sealed, free
from water, product, etc?Yes
Tank 1 Pressure Piping Leak Detection
Does the pressurized piping system
have a line leak detector?Yes
Does the pressurized piping system
have a valid line leak detector test?Yes
Does the pressurized piping system
have a valid annual line tightness test
or valid monthly monitoring?
Yes
Tank 1 Spill/Overfill
Does the spill bucket have a valid 3-
year test, valid monthly monitoring for
DW buckets, or the tank is exempt?
Yes
Does the overfill device have a valid 3-
year test or the tank is exempt?Yes
2024-09-23 Page 4 of 10
Tank 1 SIR/MTG
SIR - Dispensers have current
calibration stickers or proper calibration
documentation?
Yes
SIR - Drop tubes are present and
extend to within one foot of the tank
bottom?
Yes
SIR - Inventory readings for product
inputs, withdrawals, and the amount
remaining in the tank are recorded and
available for each operating day?
Yes
SIR - Product inputs are reconciled with
delivery receipts by measurement of
the tank inventory volume before and
after deliveries?
Yes
SIR - Records include the appropriate
number of water readings, and water
readings are used to adjust inventory
balances as necessary?
Yes
SIR/MTG - An appropriate calibration
chart is used to convert product level
readings to gallons, and is available for
review?
Yes
SIR/MTG - Inventory readings are
properly reconciled monthly (weekly
and monthly for MTG) to the
appropriate allowable amount?
Yes
SIR/MTG - Equipment used to take
readings (ATG, Gauge Stick, etc.) is
adequate, accessible, and operational?
Yes
SIR/MTG - Documentation of valid
testing or monitoring is available (must
have records for the two most recent
months and 10 of last 12 months)?
Show results in the RD tab.
Yes
Tank 2 Cathodic Protection
Tanks are protected from corrosion?Yes
Piping is protected from corrosion?Yes
Flex connectors at the tank sub-pumps
are protected from corrosion?Yes
Containment sumps are sealed, free
from water, product, etc?Yes
Tank 2 Pressure Piping Leak Detection
Does the pressurized piping system
have a line leak detector?Yes
Does the pressurized piping system
have a valid line leak detector test?Yes
Does the pressurized piping system
have a valid annual line tightness test
or valid monthly monitoring?
Yes
Tank 2 Spill/Overfill
Does the spill bucket have a valid 3-
year test, valid monthly monitoring for
DW buckets, or the tank is exempt?
Yes
Does the overfill device have a valid 3-
year test or the tank is exempt?Yes
Tank 2 Spill/Overfill
Tank has a spill prevention device?Yes
Are you able to visually inspect the spill
containment bucket(s) for functionality?
(i.e. are the buckets clean enough to
see cracks, etc?)
Yes
Is the spill containment bucket intact?Yes
Is the spill containment bucket(s) able
to contain a spill? (i.e. is there water,
product, debris, etc in the spill bucket
to prevent it from containing a spill?)
Yes
Tank has an overfill device?Yes
Tank 2 SIR/MTG
SIR - Dispensers have current
calibration stickers or proper calibration
documentation?
Yes
SIR - Drop tubes are present and
extend to within one foot of the tank
bottom?
Yes
SIR - Inventory readings for product
inputs, withdrawals, and the amount
remaining in the tank are recorded and
available for each operating day?
Yes
SIR - Product inputs are reconciled with
delivery receipts by measurement of
the tank inventory volume before and
after deliveries?
Yes
SIR - Records include the appropriate
number of water readings, and water
readings are used to adjust inventory
balances as necessary?
Yes
SIR/MTG - An appropriate calibration
chart is used to convert product level
readings to gallons, and is available for
review?
Yes
SIR/MTG - Inventory readings are
properly reconciled monthly (weekly
and monthly for MTG) to the
appropriate allowable amount?
Yes
SIR/MTG - Equipment used to take
readings (ATG, Gauge Stick, etc.) is
adequate, accessible, and operational?
Yes
SIR/MTG - Documentation of valid
testing or monitoring is available (must
have records for the two most recent
months and 10 of last 12 months)?
Show results in the RD tab.
Yes
Tank 3 Cathodic Protection
Tanks are protected from corrosion?Yes
Piping is protected from corrosion?Yes
Flex connectors at the tank sub-pumps
are protected from corrosion?Yes
Containment sumps are sealed, free
from water, product, etc?Yes
2024-09-23 Page 5 of 10
Tank 3 Spill/Overfill
Tank has a spill prevention device?Yes
Are you able to visually inspect the spill
containment bucket(s) for functionality?
(i.e. are the buckets clean enough to
see cracks, etc?)
Yes
Is the spill containment bucket intact?Yes
Is the spill containment bucket(s) able
to contain a spill? (i.e. is there water,
product, debris, etc in the spill bucket
to prevent it from containing a spill?)
Yes
Tank has an overfill device?Yes
Tank 3 Suction Piping Leak Detection
U.S. suction piping has a valid LTT
every 3 years or monthly monitoring?Yes
Piping qualifies as Safe Suction.
(Documentation is available and
verifiable to show that piping operates
at less than atmospheric pressure, has
only one check valve (under pump),
and has proper slope of piping. If all
these criteria are met, no leak
detection is required on the piping.)
Yes
Tank 3 Spill/Overfill
Does the spill bucket have a valid 3-
year test, valid monthly monitoring for
DW buckets, or the tank is exempt?
Yes
Does the overfill device have a valid 3-
year test or the tank is exempt?Yes
Tank 4 Spill/Overfill
Tank has a spill prevention device?Yes
Are you able to visually inspect the spill
containment bucket(s) for functionality?
(i.e. are the buckets clean enough to
see cracks, etc?)
Yes
Is the spill containment bucket intact?Yes
Is the spill containment bucket(s) able
to contain a spill? (i.e. is there water,
product, debris, etc in the spill bucket
to prevent it from containing a spill?)
Yes
Tank has an overfill device?Yes
Tank 3 Pressure Piping Leak Detection
Does the pressurized piping system
have a line leak detector?Yes
Does the pressurized piping system
have a valid line leak detector test?Yes
Does the pressurized piping system
have a valid annual line tightness test
or valid monthly monitoring?
Yes
Tank 3 SIR/MTG
SIR - Dispensers have current
calibration stickers or proper calibration
documentation?
Yes
SIR - Drop tubes are present and
extend to within one foot of the tank
bottom?
Yes
SIR - Inventory readings for product
inputs, withdrawals, and the amount
remaining in the tank are recorded and
available for each operating day?
Yes
SIR - Product inputs are reconciled with
delivery receipts by measurement of
the tank inventory volume before and
after deliveries?
Yes
SIR - Records include the appropriate
number of water readings, and water
readings are used to adjust inventory
balances as necessary?
Yes
SIR/MTG - An appropriate calibration
chart is used to convert product level
readings to gallons, and is available for
review?
Yes
SIR/MTG - Inventory readings are
properly reconciled monthly (weekly
and monthly for MTG) to the
appropriate allowable amount?
Yes
SIR/MTG - Equipment used to take
readings (ATG, Gauge Stick, etc.) is
adequate, accessible, and operational?
Yes
SIR/MTG - Documentation of valid
testing or monitoring is available (must
have records for the two most recent
months and 10 of last 12 months)?
Show results in the RD tab.
Yes
Tank 4 Cathodic Protection
Tanks are protected from corrosion?Yes
Piping is protected from corrosion?Yes
Flex connectors at the tank sub-pumps
are protected from corrosion?Yes
Containment sumps are sealed, free
from water, product, etc?Yes
2024-09-23 Page 6 of 10
Tank 4 ATG/IM
IM - Type of Documentation Used?ATG
IM - System capable of detecting a
release of regulated substances from
any portion of the primary tank/piping
within one month of release?
Yes
ATG/IM - Records on site document that
the system is properly installed,
calibrated, operated, and maintained
(system and tank setup reports,
maintenance records)? Written
documentation of calibration,
maintenance, and repair is kept for at
least one year after work is completed?
Yes
ATG/IM - ATG console or other
equipment used to take readings and
perform tests is adequate, accessible,
and operational?
Yes
ATG/IM - Documentation of valid testing
or monitoring is available (must have
records for the two most recent months
and 10 of last 12 months)? Show results
in the RD tab.
Yes
Tank 4 ATG/IM
Does the ATG system have a valid
annual test?Yes
Tank 4 Pressure Piping Leak Detection
Does the pressurized piping system
have a line leak detector?Yes
Does the pressurized piping system
have a valid line leak detector test?Yes
Does the pressurized piping system
have a valid annual line tightness test
or valid monthly monitoring?
Yes
Tank 4 Spill/Overfill
Does the spill bucket have a valid 3-
year test, valid monthly monitoring for
DW buckets, or the tank is exempt?
Yes
Does the overfill device have a valid 3-
year test or the tank is exempt?Yes
DISPENSER RESPONSES
Dispenser 3/4
Flex connectors at the dispensers are
protected from corrosion?Yes
Containment sumps are sealed, free
from water, product, etc?Yes
Fire valve is anchored properly?Yes
Does the line tightness test port on the
fire valve have the manufacturers plug
installed in it? (no ball valves)
Yes
Is the fire valve located properly below
grade?Yes
Is the fire valve's fuseable link intact?Yes
Dispenser 7/8
Flex connectors at the dispensers are
protected from corrosion?Yes
Containment sumps are sealed, free
from water, product, etc?Yes
Fire valve is anchored properly?Yes
Does the line tightness test port on the
fire valve have the manufacturers plug
installed in it? (no ball valves)
Yes
Is the fire valve located properly below
grade?Yes
Is the fire valve's fuseable link intact?Yes
Dispenser 1/2
Flex connectors at the dispensers are
protected from corrosion?Yes
Containment sumps are sealed, free
from water, product, etc?Yes
Fire valve is anchored properly?Yes
Does the line tightness test port on the
fire valve have the manufacturers plug
installed in it? (no ball valves)
Yes
Is the fire valve located properly below
grade?Yes
Is the fire valve's fuseable link intact?Yes
Dispenser 5/6
Flex connectors at the dispensers are
protected from corrosion?Yes
Containment sumps are sealed, free
from water, product, etc?Yes
Fire valve is anchored properly?Yes
Does the line tightness test port on the
fire valve have the manufacturers plug
installed in it? (no ball valves)
Yes
Is the fire valve located properly below
grade?Yes
Is the fire valve's fuseable link intact?Yes
2024-09-23 Page 7 of 10
Dispenser 11/12
Flex connectors at the dispensers are
protected from corrosion?Yes
Containment sumps are sealed, free
from water, product, etc?Yes
Fire valve is anchored properly?Yes
Does the line tightness test port on the
fire valve have the manufacturers plug
installed in it? (no ball valves)
Yes
Is the fire valve located properly below
grade?Yes
Is the fire valve's fuseable link intact?Yes
Dispenser D 3/2S
Flex connectors at the dispensers are
protected from corrosion?Yes
Containment sumps are sealed, free
from water, product, etc?Yes
Fire valve is anchored properly?Yes
Does the line tightness test port on the
fire valve have the manufacturers plug
installed in it? (no ball valves)
Yes
Is the fire valve located properly below
grade?Yes
Is the fire valve's fuseable link intact?Yes
Dispenser D 5/4S
Flex connectors at the dispensers are
protected from corrosion?Yes
Containment sumps are sealed, free
from water, product, etc?Yes
Fire valve is anchored properly?Yes
Does the line tightness test port on the
fire valve have the manufacturers plug
installed in it? (no ball valves)
Yes
Is the fire valve located properly below
grade?Yes
Is the fire valve's fuseable link intact?Yes
Dispenser D 7/6S
Flex connectors at the dispensers are
protected from corrosion?Yes
Containment sumps are sealed, free
from water, product, etc?Yes
Fire valve is anchored properly?Yes
Does the line tightness test port on the
fire valve have the manufacturers plug
installed in it? (no ball valves)
Yes
Is the fire valve located properly below
grade?Yes
Is the fire valve's fuseable link intact?Yes
Dispenser 9/10
Flex connectors at the dispensers are
protected from corrosion?Yes
Containment sumps are sealed, free
from water, product, etc?Yes
Fire valve is anchored properly?Yes
Does the line tightness test port on the
fire valve have the manufacturers plug
installed in it? (no ball valves)
Yes
Is the fire valve located properly below
grade?Yes
Is the fire valve's fuseable link intact?Yes
Dispenser D 1/2
Flex connectors at the dispensers are
protected from corrosion?Yes
Containment sumps are sealed, free
from water, product, etc?Yes
Fire valve is anchored properly?Yes
Does the line tightness test port on the
fire valve have the manufacturers plug
installed in it? (no ball valves)
Yes
Is the fire valve located properly below
grade?Yes
Is the fire valve's fuseable link intact?Yes
Dispenser D 4/3S
Flex connectors at the dispensers are
protected from corrosion?Yes
Containment sumps are sealed, free
from water, product, etc?Yes
Fire valve is anchored properly?Yes
Does the line tightness test port on the
fire valve have the manufacturers plug
installed in it? (no ball valves)
Yes
Is the fire valve located properly below
grade?Yes
Is the fire valve's fuseable link intact?Yes
Dispenser D 6/5S
Flex connectors at the dispensers are
protected from corrosion?Yes
Containment sumps are sealed, free
from water, product, etc?Yes
Fire valve is anchored properly?Yes
Does the line tightness test port on the
fire valve have the manufacturers plug
installed in it? (no ball valves)
Yes
Is the fire valve located properly below
grade?Yes
Is the fire valve's fuseable link intact?Yes
2024-09-23 Page 8 of 10
Dispenser D 7S
Flex connectors at the dispensers are
protected from corrosion?Yes
Containment sumps are sealed, free
from water, product, etc?Yes
Fire valve is anchored properly?Yes
Does the line tightness test port on the
fire valve have the manufacturers plug
installed in it? (no ball valves)
Yes
Is the fire valve located properly below
grade?Yes
Is the fire valve's fuseable link intact?Yes
MONTHLY LEAK DETECTION MONITORING
Sep '23 Oct '23 Nov '23 Dec '23 Jan '24 Feb '24 Mar '24 Apr '24 May '24 Jun '24 Jul '24 Aug '24
Tank 1 Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass
Line Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl
Tank 2 Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass
Line Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl
Tank 3 Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass
Line Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl
Tank 4 Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass
Line Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl
NON-COMPLIANCE ITEMS
All items are in compliance.
2024-09-23 Page 9 of 10
Prepared by fueloperator.com
Inspection Information
Inspector:Lundell, Phillip
Record
Created:
Sept. 23, 2024, 10:45
a.m.
Inspection
Date:Sept. 23, 2024
2024-09-23 Page 10 of 10