Loading...
HomeMy WebLinkAboutDDW-2024-011181Sanitary Survey - Deficiency Report PWS Number:UTAH10041 Deficiency Points:75 Survey Date:09/19/2024 Survey Name:UNIVERSITY OF UTAH RIO MESA CENTER Surveyor:David Kruse Sanitary Survey Category: SO SDWIS Severity Code: Significant Deficiency Wells | WS002 | CAMPGROUND WELL 55. Wellhead is sealed to prevent contamination. Rule: R309-515-6(6)(i)R309-515-6(6)(i) and R309-515-6(12)(b,c,d)require a sanitary seal be installed and maintained at the wellhead and discharge piping. This significant deficiency should be corrected within 120 days of notification or have a corrective action plan approved by Notes:Wellhead is not sealed as evidenced by leaking water. Deficiency Points: 50 Days until points become effective on IPS: 120 SDWIS Deficiency Description: S013 WELL LACKS THE REQUIRED WELL SEAL Sanitary Survey Category: FW SDWIS Severity Code: Significant Deficiency Storage Tanks | ST001 | 3000-GALLON TANK 77C. Access opening lid properly gasketed Rule: R309-545-14(2)Rule requires the access opening to a tank to be furnished with a gasket between the lid and frame. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:Deteriorated gasket needs replacement. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: V009 STORAGE TANK LID LACKS A FUNCTIONING GASKET BETWEEN THE LID AND FRAME