HomeMy WebLinkAboutDDW-2024-011181Sanitary Survey - Deficiency Report
PWS Number:UTAH10041 Deficiency Points:75 Survey Date:09/19/2024
Survey Name:UNIVERSITY OF UTAH RIO
MESA CENTER
Surveyor:David Kruse
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Wells | WS002 | CAMPGROUND WELL
55. Wellhead is sealed to prevent contamination.
Rule: R309-515-6(6)(i)R309-515-6(6)(i) and R309-515-6(12)(b,c,d)require a sanitary seal be installed and
maintained at the wellhead and discharge piping. This significant deficiency should be
corrected within 120 days of notification or have a corrective action plan approved by
Notes:Wellhead is not sealed as evidenced by leaking water.
Deficiency Points: 50
Days until points become effective on IPS: 120
SDWIS Deficiency Description: S013 WELL LACKS THE REQUIRED WELL SEAL
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST001 | 3000-GALLON TANK
77C. Access opening lid properly gasketed
Rule: R309-545-14(2)Rule requires the access opening to a tank to be furnished with a gasket between the lid
and frame. This significant deficiency must be corrected within 120 days of notification
or have a corrective action plan approved by DDW.
Notes:Deteriorated gasket needs replacement.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V009 STORAGE TANK LID LACKS A FUNCTIONING GASKET BETWEEN THE LID AND
FRAME