HomeMy WebLinkAboutDDW-2024-011171Sanitary Survey - Deficiency Report
PWS Number:UTAH09001 Deficiency Points:100 Survey Date:09/17/2024
Survey Name:ANTIMONY TOWN WATER
SYSTEM
Surveyor:Luke Treutel
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Springs | WS002 | EAST BENCH SPRING
79. No deep-rooted vegetation is within the 50 ft collection area.
Rule: R309-515-7(7)(f)All deep-rooted vegetation within the fenced collection area shall be removed by a
means not negatively affecting water quality. This significant deficiency must be
corrected within 120 days of notification or have a corrective action plan approved by
DDW.
Notes:Many trees and shrubs in spring collection area
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: SS07 DEEP ROOTED VEGETATION IN SPRING COLLECTION AREA
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Springs | WS002 | EAST BENCH SPRING
80. No roots seen in collection boxes and junctions.
Rule: R309-105-10(4)(a), R309-515-8(1)(a)Spring collection areas shall be periodically (preferably annually) cleared of deep-
rooted vegetation to prevent root growth from clogging collection lines. This significant
deficiency must be corrected within 120 days of notification or have a corrective action
plan approved by DDW.
Notes:Roots observed in 2 southern spring boxes
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: SS08 ROOTS IN SPRING COLLECTION PIPES
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Springs | WS002 | EAST BENCH SPRING
81B. Spring box lid is gasketed
Rule: R309-515-7(7)(d), R309-545-14 (2)Access openings shall comply with R309-545 and be provided with a cover furnished
with a gasket between the lid and frame. This significant deficiency must be corrected
within 120 days of notification or have a corrective action plan approved by DDW.
Notes:SW spring box is missing gasket
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: SS10 SPRING BOX LID LACKS A GASKET
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST002 | EAST BENCH RESERVOIR
110A. Overflow line discharges at least 12 inches above ground or the flood rim of receiving basin?
Rule: R309-545-13 Rule requires all water storage tanks to be provided with an overflow that discharges at
an elevation between 12 and 24 inches above the ground surface or the rim of the
receiving basin.
Notes:Line discharges below rim of receiving basin
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V011 END OF STORAGE TANK OVERFLOW LACKS A CLEARANCE OF BETWEEN 12
AND 24 INCHES FROM GROUND SURFACE