HomeMy WebLinkAboutDDW-2024-011068Utah Department Of Environmental Quality Division Of Drinking Water Level 2 Assessment Level 2 Assessment General System Information Exception Granted: R309-550-11(3), R309-540-5(4)(c), and R309-105-9(3) | Deer Springs Ranch Lower Cabins Water System has four lots where adequate pressure cannot be provided according to the rules. Therefore, individual home booster pumps will be required to be able to provide pressure. Site Visit Info Management and Operations Site Visit Date Surveyor Name 08/16/2024 Luke Treutel DEER SPRINGS RANCH LOWER CABINS PWS ID: UTAH13056 Rating: Approved 12/17/2009 Active 1 Admin Contact (AC) [ eMail address is REQUIRED ] MIN | 15pts | SM | G004 | R309-100-4(5) | Rule requires a person or organization be designated as the owner of the system and name, address and phone number of such be supplied to the Division. *First Name: DANIELLE *Last Name: CLARKSON *Organization: *Address: Redacted *City: KANAB *State: UT *Zip: 84741 *Email: dsroa@deerspringsranch.org *Phone: 435-644-3007 2 Date of Survey (First Day of Field Work)08/16/2024 3 Date of Survey (Last Day of Field Work) ** this should match the Date of Survey in the header ** 08/16/2024 4 Date final report sent to system (questionnaire, deficiency report and cover letter)09/05/2024 5 Water system representative present during the survey:Bart Battista (Notes: Brent Fulmer and Cody Allred present as well.) 6 What condition triggered the level 2 assessment?LV04 DEQ | Drinking Water Run Date: 09/05/2024 12:52:38 | Rating: Approved UTAH13056 DEER SPRINGS RANCH LOWER CABINS page 1 of 13 7 For a community water system with water sources that require power to produce sufficient flow, system is equipped with standby power option. SIG | 25pts | SO | S033 | R309-515-6(2)(a) | Rule requires a community water system without naturally flowing water sources, such as springs or flowing wells, to have one or more of the system's sources equipped for operation during power outages. To ensure continuous service when the primary power has been interrupted, a redundant power supply is required. A redundant power supply may include a transfer switch for auxiliary power such as a generator or a power supply service with coverage from two independent substations. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. NA (Notes: N/A - Not a community water system) 8 There are no undocumented drinking water facilities (i.e. tanks, pump stations, treatment facilities, etc.) or recent modifications that have not gone through or in process of DDW review [LIST UNDOCUMENTED FACILITIES OR DESCRIBE MODIFICATIONS, IF APPLICABLE] [undocumented sources are covered in a different question] SIG | 50pts | SM | G001 | R309-100-5(2), R309-500-6, R309-500-9, R309-500-9(2) and (3) | Rule requires complete plans & specification for all public drinking water projects to be approved in writing by the Director. Any facility found that has not started DDW review shall be considered unapproved. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. C 9 Are there any individual home booster pumps installed in the distribution system (not for fire suppression)? Exception Granted: R309-550-11(3), R309-540-5(4)(c), and R309-105-9(3) | Deer Springs Ranch Lower Cabins Water System has four lots where adequate pressure cannot be provided according to the rules. Therefore, individual home booster pumps will be required to be able to provide pressure. SIG | 50pts | SM | M008 | R309-550-11(3) | R309-550-11(3) C (Notes: Exception granted) 10 Does the system haul water?N 11 For a community system serving 100 or more connections, at least 2 water sources are available. SIG | 50pts | SO | TGR7 | R309-515-4(3) | Rule requires Community Water Systems serving more than 100 connections to have a minimum of two sources except where served by a water treatment plant. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. NA (Notes: N/A - Not a community water system) 12 Does system have a consecutive connection to another water system not listed in the SOURCE section of Waterlink Report? If yes, answer the following question(s) N 13 Sell water? ... if yes, answer the following question(s)N 14 Does this system share any sources with another water system?N 15 Is the sample tap clean and free from obstruction?Y 16 Describe the type of sample tap (outside hose bib, frost free hydrant, kitchen tap, etc.)Kitchen tap w/ swivel 17 Was the sample collected on a supply line that is used regularly? (Samples should not be taken from a line with little or no use) Y 18 Have any conditions changed since the last sample collection?Y DEQ | Drinking Water Run Date: 09/05/2024 12:52:38 | Rating: Approved UTAH13056 DEER SPRINGS RANCH LOWER CABINS page 2 of 13 Cross Connection and Operator Certification 18A Have there been any plumbing changes or construction where the sample was collected? Y (Notes: An individual home booster pump was installed at a different unit prior to the positive sample.) 18B Have there been any plumbing breaks or failure in the premise plumbing?N 19 Are there any cross-connections after the service connection or in premise plumbing?N 20 Were there any low pressure events or changes in the water pressure after the service connection or in premise plumbing? N 21 Are there any treatment devices after the service connection or in the premise piping?N 22 Could the sample be mixed with hot water or water passing through a water softener?N 23 Was the sample representative of the water system?Y 24 Did the sampler explain their procedures for collecting samples?Y 25 Was the sample tap adequately flushed prior to taking sample?Y 26 Was the sample tap properly disinfected?Y 27 If the sample tap has an aerator, was the aerator removed before taking the sample?Y 28 Was the sample taken from a tap with a swivel connection?Y 29 Were sealed, fresh sample bottles used?Y 30 Are sample bottles properly stored?Y 31 Were there any adverse environmental conditions when the TC+ sample was collected? N 32 Were samples kept on ice during transportation to the laboratory?Y 33 Were samples transported to the laboratory within the 30 hour holding time?Y 34 Was a Boil Water Order issued for the E.coli sample results?NA (Notes: N/A - No EC+, only TC+) 35 Was the Boil Water Order lifted?NA (Notes: N/A - No EC+, only TC+) 36 Does the system have any unresolved significant deficiencies?N 37 Legally adopted authority statement MIN | 15pts | SM | M003 | R309-105-12(2) | Rule requires each public water system to have a cross connection control program that includes a legally adopted and functional local authority to enforce the program (i.e., ordinance, bylaw, or policy). C 38 Documentation of annual public awareness and/or employee training MIN | 15pts | SM | M004 | R309-105-12(2) | Rule requires each public water system to have a cross connection control program that includes providing public education or awareness material or presentations. C DEQ | Drinking Water Run Date: 09/05/2024 12:52:38 | Rating: Approved UTAH13056 DEER SPRINGS RANCH LOWER CABINS page 3 of 13 General Maintenance and Environment 39 Documentation of personnel trained to manage the program (COMMUNITY WATER SYSTEMS POPULATION 500 AND ABOVE REQUIRE A DDW CERTIFIED CCC PROGRAM ADMINISTRATOR. ALL OTHER WATER SYSTEMS REQUIRE AT A MINIMUM BACKFLOW 101 OR EQUIVALENT/ GREATER CCC TRAINING) MIN | 15pts | SM | M005 | R309-105-12(2) | Rule requires each public water system to have a cross connection control program that includes an operator with adequate training in the area of cross connection control or backflow prevention. C 40 Does the water system have detailed records of cross connection control activities? (inventories of backflow assemblies, devices, and air gaps installed within the system) MIN | 15pts | SM | M006 | R309-105-12(2) | Rule requires each public water system to have a cross connection control program that includes written records of cross connection control activities. C 41 Does the water system have records of on-going enforcement activities? (test history, enforcement activities, hazard assessments) MIN | 15pts | SM | M007 | R309-105-12(2) | Rule requires each public water system to have a cross connection control program that includes test history and documentation of on-going enforcement activities. C 42 Sampler's Last Name Fulmer 43 Sampler's First Name Brent 44 Sampler's telephone number 435-644-3007 45 Sampler's eMail address N/A (Notes: No email for Brent. Can email Bart Battista at bartbattista@gmail.com) 46 Emergency phone number:808-348-9769 47 How long has the sampler been taking TCR samples?Many years 48 Is the sampler certified in either distribution or treatment?N (Notes: Not required for TNC systems) 49 Has there been a loss of power to any portion(s) of the system?N 50 Has there been any loss of pressure events?N 51 Have there been any customer complaints (cloudy water, smell, taste, interruptions of service)? N DEQ | Drinking Water Run Date: 09/05/2024 12:52:38 | Rating: Approved UTAH13056 DEER SPRINGS RANCH LOWER CABINS page 4 of 13 52 Are there any visual indications of unsanitary conditions? SIG | 50pts | SM | M017 | R309-200-6, R309-105-18, R309-215-4(3) | R309-200-6 The Secondary Maximum Contaminant Levels for public water systems deals with substances which affect the aesthetic quality of drinking water. They are presented here as recommended limits or ranges and are not grounds for rejection. The taste of water may be unpleasant and the usefulness of the water may be impaired if these standards are significantly exceeded. R309-105-18 The Director or the local health department shall be informed by telephone by a water supplier of any "emergency situation". The term "emergency situation... R309-215-4(3) If the water fails to meet minimum standards, then certain public notification procedures shall be carried out, as outlined in R309-220. Water suppliers shall also keep analytical records in their possession, for a required length of time, as outlined in R309-105-17. C 53 Has there been any operation, maintenance, or repair activities that could have introduced total coliform or E.coli into the system? N 54 Has there been any vandalism and/or unauthorized access to facilities?N 55 Has there been any recent fire fighting events, flushing operations, sheared hydrants, etc.? N 56 Has there been any recent construction activities such as a new water line, tank, pump station, well installation, etc. or other facility that has been tied into the existing distribution system? Y (Notes: An in-home booster pump unit was installed recently.) 57 Have there been any analytical results or any additional samples collected, including source samples which were positive (not for compliance)? N 58 Has there been any community illness suspected of being waterborne?N 59 Did the water system receive any TCR monitoring violations in the past 12 months?N 60 What was the most recent date on which a satisfactory total coliform sample(s) were taken? 07/09/2024 61 Is there any evidence of intentional contamination of the system?N 62 Was there an increase in water turbidity at any point in the system?N 63 Have there been any recent modifications to the water system that could lead to contamination of the system? Y (Notes: In-home booster pump units recently installed.) 64 Have any new sources been added to the system?N 65 Have any inactive sources recently been introduced into the system (e.g. existing source, auxiliary systems)? N 66 Has there been any recent treatment or operational changes?N 67 Is there any evidence of potential sources of contamination?N 68 Was there any unusually high (or low) water demand that might have altered typical flow patterns in the water system? Y (Notes: There was increased usage at hauling station after June due to ranching activities) 69 Have there been any sewer spills, source water spills or other disturbances?N 70 Have there been any algal blooms?N 71 Has source water turnover occurred?NA (Notes: System utilizes one groundwater well - source water turnover only applies to surface water sources.) DEQ | Drinking Water Run Date: 09/05/2024 12:52:38 | Rating: Approved UTAH13056 DEER SPRINGS RANCH LOWER CABINS page 5 of 13 Distribution 72 Has there been any unusual weather events that could have contributed to the TC+/EC+ samples? N 73 Has there been any recent heavy rainfall?N 74 Has there been any rapid snow melt or flooding?N 75 Have there been any changes in available source water? (e.g. significant drop in water table, well output reservoir capacity, etc.) N 76 Have there been any extremes in heat or cold?Y (Notes: Recent excessive heat and wildfires in the area) 77 No unprotected connection between the distribution system and a source of contamination. (If there is an unprotected connection, describe the location in detail.) SIG | 50pts | DS | D009 | R309-550-5(11) | R309-550-5(11) C 78 Are air release/vacuum valves in the distribution system? ... if yes, answer the following question(s) N 79 Water system has a program to maintain, operate, or control the use of fire hydrants. REC | 0pts | DS | D012 | N/A | Fire hydrants provide a direct access to the water in the distribution system. In order to protect the quality and integrity of the water, fire hydrant access should be controlled. NA (Notes: No hydrants) 80 Blow offs or air release valves are not directly connected to a sanitary sewer line. SIG | 50pts | DS | D013 | R309-550-6(5)(a), R309-550-6(6)(c) and (7)(a) | Rule states blow-offs or air relief valves shall not be connected directly to a sewer. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. NA (Notes: No sewer present) 81 Blow offs or air release valves do not discharge below flood level in ditches or streams. SIG | 50pts | DS | D016 | R309-550-9(1) and (2), R309-550-13(2) | R309-550-9(1 & 3) C 82 Does the system have fire hydrants or blow offs?N 83 All water mains installed after 1995 that provide fire flow are at least 8 inches in diameter. MIN | 15pts | DS | D019 | R309-550-5(4) & (5) | Rule states that the minimum line size serving a fire hydrant lateral shall be 8-inch diameter unless a hydraulic analysis indicates that required flow and pressures can be maintained by 6-inch lines. NA (Notes: No fire flow) 84 Distribution system capable of providing minimum pressure of 20 psi at all service connections. SIG | 50pts | DS | D003 | R309-105-9, R309-550-5(1) | Rule states the distribution system shall maintain minimum pressures as required by R309-105-9 at all points of connection under all flow conditions. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. C (Notes: Temporary exception granted for in-home booster pumps.) 85 Was the water system constructed or new portions added after January 1, 2007? ... if yes, answer the following question(s) N 86 Is there any evidence that the system experienced low or negative pressure?N 87 Is there adequate pressure throughout the entire distribution system at all times?Y 88 Does the system have pressure reducing / sustaining valve stations?Y (Notes: 1PRV in vault) 88A Do the valves function properly?Y DEQ | Drinking Water Run Date: 09/05/2024 12:52:38 | Rating: Approved UTAH13056 DEER SPRINGS RANCH LOWER CABINS page 6 of 13 General Disinfection WS002 - 2003 WELL - Active 88B Is the valve vault free of standing water, debris, etc.?Y 89 Are blow offs or air relief valves directly connected to a sewer or do not have a proper air gap or do they exit below flood level in ditches or streams? NA (Notes: No sewer present) 90 Has appropriate backflow prevention (devices/assemblies) been installed on all high risk (hazard) sites? Y 90A Have these devices/assemblies been inspected, maintained and/or tested at least annually? N (Notes: Recommend devices be tested in 2024) 91 Water system follows AWWA disinfection procedures for new, repaired, or seasonal water mains and tanks. SIG | 25pts | MR | D018 | R309-550-8(10) | All new and repaired water mains and appurtenances shall be disinfected in accordance with AWWA Standard C651. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. C 92 How often do you periodically disinfect any or all parts of your water system (i.e. batch disinfection) other than for repairs or maintenance? SIG | 50pts | SM | G006 | R309-105-6(1)(a), R309-500-6 | R309-105-6(1) Approval of Engineering Plans and Specifications R309-500-6 Plan Approval Procedure. C 93 Did the system batch disinfect for this TC+, EC+ event?N 94 Did the system conduct any flushing associated with this event?N 95 Has the system completed any recent water main, service connection repairs, maintenance on a well or pump, fire hydrant, pressure regulator, etc. that may have introduced contamination into the distribution system?, Y 95A Describe recent construction/repair activity:Recent work on the service line for unit 144 96 Were investigative TCR samples taken after repairs were made?N 97 Were any isolation valves recently opened, closed or damaged?N 98 Operating Period (Start Date)01/01 99 Operating Period (Ending Date)12/31 100 Undocumented sources shall not be physically connected to the drinking water system. (IF SOURCE IS NOT IN SYSTEM INVENTORY MARK "DEFICIENT") SIG | 200pts | SO | S001 | R309-515-6(5), R309-515-7(4), R309-500-9(2) and (3) | R309-105-6(1) requires plans and specifications for all public drinking water projects to be approved in writing by the Director prior to the commencement of construction. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. C DEQ | Drinking Water Run Date: 09/05/2024 12:52:38 | Rating: Approved UTAH13056 DEER SPRINGS RANCH LOWER CABINS page 7 of 13 101 Well casing is at least 18 inches above finished ground surface and 12 inches above well house floor. SIG | 25pts | SO | S003 | R309-515-6(6)(b)(vi), R309-515-6(12)(c)(ii), R309-515- 6(13)(a) | Rule requires the permanent well casing to project at least 18 inches above the final ground surface and 12 inches above the pump house floor; at sites subject to flooding, the top of the casing must terminate at least 3 feet above the 100-year flood level or highest known flood elevation, whichever is higher. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. C 102 Wellhead is sealed to prevent contamination. SIG | 50pts | SO | S013 | R309-515-6(6)(i) | R309-515-6(6)(i) and R309-515- 6(12)(b,c,d)require a sanitary seal be installed and maintained at the wellhead and discharge piping. This significant deficiency should be corrected within 120 days of notification or have a corrective action plan approved by D (Notes: Conduit is cracked - needs to be repaired so well head is sealed from environment) 103 Is the well casing vented? ... if yes, answer the following question(s)Y 103A Vent screened with #14 mesh screen SIG | 25pts | SO | S006 | R309-515-6(12)(d)(iii) | Guidance states provisions should be made for venting the well casing, however if vented R309-515-6(12)(d)(iii) and R309- 550-6(6)(a)require vents be fitted with a #14 mesh or finer non-corrodible screen. C 103B Vent down-turned SIG | 25pts | SO | S007 | R309-515-6(12)(d)(iii) | Guidance states provisions should be made for venting the well casing, however if vented R309-515-6(12)(d)(iii) and R309- 550-6(6)(b) requires vents be downturned or shielded to prevent the entrance of surface water or rainwater. C 103C Vent has adequate clearance to prevent contamination from entering the well SIG | 25pts | SO | S008 | R309-515-6(12)(d)(iii) | Guidance states provisions should be made for venting the well casing, however if vented R309-515-6(12)(d)(iii) and R309- 550-6(6)(b) requires vents be terminated with a discharge with an appropriate air gap. C 104 Does the well have a pump to waste line? ... if yes, answer the following question(s)N 105 Provisions available to periodically measure water levels MIN | 5pts | SO | S015 | R309-515-6(12)(e ), R309-515-6(12)(c)(vi) | Rule requires provisions be made to permit periodic measurement of water levels in the completed well. C 106 Wellhead secured to protect quality water SIG | 25pts | SO | S002 | R309-105-10(5) | All water system facilities shall be secure. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. C DEQ | Drinking Water Run Date: 09/05/2024 12:52:38 | Rating: Approved UTAH13056 DEER SPRINGS RANCH LOWER CABINS page 8 of 13 107 Well head or well house and equipment protected from flooding SIG | 25pts | SO | S020 | R309-515-6(6)(b)(vi), R309-515-6(12)(d)(iii), R309-515- 6(13)(a) to (d) | Top of well casing shall terminate at least 18” above ground level or 12” above well house floor and for sites that flood at least 3’ above 100-year flood level or highest known flood elevation. Well casing terminating in underground vault shall have a drain to daylight and surface runoff directed away from vault access. Well house floor shall be sloped for drainage, and have a drain to daylight unless highly impractical. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. C 108 There are no unprotected cross-connections in well discharge piping. SIG | 50pts | SO | S021 | R309-105-12(1), R309-515-6(12)(d)(iii) | Rule requires the well discharge piping to be protected against the entrance of contamination. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. C 109 No toxic chemicals, hazardous or flammable materials, or lubricants inside the well house or near well head? MIN | 15pts | TR | TGR9 | R309-105-7, 8 & 18, R309-100 through 605 | Trigger for regulatory followup to address concerns. C 110 Well discharge line has a smooth-nosed sampling tap, which samples the well water before any chemical injection. (first item from the wellhead). MIN | 5pts | SO | S023 | R309-515-6(12)(d)(iv) | Rule requires the discharge piping to be equipped with a smooth nosed sampling tap, a check valve, a pressure gauge, a means of measuring flow, and a shutoff valve. (smooth nosed sampling tap being the first item from the well head and the shut-off valve as the last item) C 111 Well discharge line has a check valve. MIN | 5pts | SO | S024 | R309-515-6(12)(d)(iv) | Rule requires the discharge piping to be equipped with (in order of placement from the wellhead) a smooth nosed sampling tap, a check valve, a pressure gauge, a means of measuring flow, and a shutoff valve. C 112 Well discharge line has a pressure gauge. MIN | 5pts | SO | S025 | R309-515-6(12)(d)(iv) | Rule requires the discharge piping to be equipped with (in order of placement from the wellhead) a smooth nosed sampling tap, a check valve, a pressure gauge, a means of measuring flow, and a shutoff valve. C 113 Well discharge line has a means to measure flow. MIN | 5pts | SO | S026 | R309-515-6(12)(d)(iv) | Rule requires the discharge piping to be equipped with (in order of placement from the wellhead) a smooth nosed sampling tap, a check valve, a pressure gauge, a means of measuring flow, and a shutoff valve. C 114 Well discharge line has a shut-off valve (last item from the well head). MIN | 5pts | SO | S027 | R309-515-6(12)(d)(iv) | Rule requires the discharge piping to be equipped with (in order of placement from the wellhead) a smooth nosed sampling tap, a check valve, a pressure gauge, a means of measuring flow, and a shutoff valve. C 115 Is there an air/vac valve on the well discharge line? If yes, answer the following question(s) N DEQ | Drinking Water Run Date: 09/05/2024 12:52:38 | Rating: Approved UTAH13056 DEER SPRINGS RANCH LOWER CABINS page 9 of 13 ST001 - STORAGE FACILITY ST001 - Active 116 Wells that pump directly into a distribution system have means to release trapped air from pump discharge piping (for example, pumps directly to a tank, has an air release valve or pump to waste line) MIN | 5pts | SO | SL01 | R309-515-6(12)(d)(v) | Rule requires a well that pumps directly into the distribution system be equipped with an air release/vacuum relief valve located upstream of the check valve, unless the wellhead valve and piping provide for pumping to waste all trapped air before water is introduced into the distribution system. C (Notes: Pumps to tank) 117 Does well require oil-lubrication?N 118 How is the well used?Fills up tank for culinary use 119 How deep is the well (in feet)?Unknown (Notes: No record of well depth available) 120 What is the output of the well (gpm) and has it changed recently?40 GPM, no recent changes 121 Is there evidence of standing water, floodwater or runoff, depressions, unsanitary conditions, rodents or animals, birds near the wellhead? N 122 Storage tank capacity in gallons (from SDWIS; if different explain why in the comments) 40000 123 There are no undocumented drinking water facilities (i.e. tanks, pump stations, treatment facilities, etc.) or recent modifications that have not gone through DDW review SIG | 50pts | SM | G001 | R309-100-5(2), R309-500-6, R309-500-9, R309-500-9(2) and (3) | Rule requires complete plans & specification for all public drinking water projects to be approved in writing by the Director. Any facility found that has not started DDW review shall be considered unapproved. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. C 124 Ladders, ladder guards, platform railings, or safely located entrance hatches are provided. MIN | 15pts | FW | V004 | R309-545-18 | Rule requires ladders, ladder guards, platform railings, and safely located entrance hatches where applicable for water storage tanks and requires safety practices to conform to pertinent laws and regulations of the Utah Occupational Safety and Health Division. C 125 Tank is vented. SIG | 25pts | FW | VL02 | R309-545-15 | Rule requires drinking water storage tanks to be vented. Overflows cannot be considered or used as vents. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. C 126 Are air vents present? ... if yes, answer the following question(s)Y 126A Vent is either down-turned or shielded from contaminants (at least 2 inches below the bottom of the opening) SIG | 25pts | FW | V005 | R309-545-15(1) | Rule requires inverted vents on water storage tanks to be down-turned a minimum of 2 inches below any opening and shielded to prevent the entrance of contaminants. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. C DEQ | Drinking Water Run Date: 09/05/2024 12:52:38 | Rating: Approved UTAH13056 DEER SPRINGS RANCH LOWER CABINS page 10 of 13 126B End of vent terminates at least 24 inches above earthen cover (buried tank) and is located and sized to avoid blockage during winter. MIN | 15pts | FW | V006 | R309-545-15(2) | For buried structures, the rule requires the end of the vent discharge to be a minimum of 24 inches above the earthen covering. C 126C Vent covered with #14 or finer non-corrodible mesh screen. SIG | 25pts | FW | V007 | R309-545-15(4) | Rule requires a water storage tank vent to be fitted with #14 mesh or finer non-corrodible screen and vents 6-inches or greater in diameter to be fitted with additional heavy gauge screen or substantial covering to protect the #14 mesh screen from vandalism or damage. This significant deficiency must be corrected within 120 days of notification or have a compliance action plan approved by DDW. C 126D Vent 6-inch diameter and larger protected with additional heavy-gauge screen or substantial covering. MIN | 5pts | FW | V035 | R309-545-15(5) | Rule requires vents that are 6-inch diameter or greater to be fitted with additional heavy gauge screen or substantial covering, which will protect the No. 14 mesh screen against vandalism or damage. C 127 Are access openings present? ... if yes, answer the following question(s) MIN | 15pts | FW | VL03 | R309-545-14 and 14(1) | Rule requires drinking water storage tanks to be designed with reasonably convenient access to the interior for cleaning and maintenance. Y 127A Access opening framed at least 4 inches above roof surface or 18 inches above earthen cover. MIN | 15pts | FW | V008 | R309-545-14(1) | Rule requires tank access opening to be framed at least 4 inches above the surface of the roof, or on a buried tank, to be at least 18 inches above any earthen cover over the tank. C 127B Access opening shoe box type with at least 2 inches of overlap SIG | 25pts | FW | V010 | R309-545-14(2) | Rule requires the frame of an access opening to be provided with a close fitting solid shoebox type cover which extends down around the frame at least two inches and is furnished with a gasket(s) between the lid and frame. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. C 127C Access opening lid properly gasketed SIG | 25pts | FW | V009 | R309-545-14(2) | Rule requires the access opening to a tank to be furnished with a gasket between the lid and frame. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. C 128 Access opening locked SIG | 25pts | FW | V029 | R309-545-14(3) | Rule requires the lid to any access opening to have a locking device. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. C DEQ | Drinking Water Run Date: 09/05/2024 12:52:38 | Rating: Approved UTAH13056 DEER SPRINGS RANCH LOWER CABINS page 11 of 13 129 Roof or wall penetrations sealed SIG | 100pts | FW | V017 | R309-545-6(1) and 545-9 | Rule requires openings in a storage tank roof or top, designed to accommodate control apparatus or pump columns, to be welded, gasketed, or curbed and sleeved and to have additional proper shielding to prevent vandalism. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. C 130 Area surrounding ground-level or buried storage tank is graded to prevent surface water from standing within 50 feet. SIG | 25pts | TR | V001 | R309-545-7(4) | Rule requires the area surrounding a ground-level or buried water storage tank be graded in a manner to prevent surface water from standing within 50 feet of the tank. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. C 131 Storage tank roof is sloped to prevent ponding MIN | 15pts | FW | V003 | R309-545-9(4) | Rule requires drainage of storage tank roofs to eliminate water ponding. C 132 Are there cracks in the walls or roof of the storage tank? (if yes, select only one of the following options) N 133 Is a tank overflow present? ... if yes, answer the following question(s) SIG | 25pts | FW | VL01 | R309-545-13 | Rule requires all storage tanks to be provided with an overflow that discharges at an an elevation between 12 and 24 inches above the ground surface or the rim of the receiving basin. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Y 133A Overflow line discharges at least 12 inches above ground or the flood rim of receiving basin? SIG | 25pts | FW | V011 | R309-545-13 | Rule requires all water storage tanks to be provided with an overflow that discharges at an elevation between 12 and 24 inches above the ground surface or the rim of the receiving basin. C 133B Overflow line covered with #4 mesh non-corrodible screen SIG | 25pts | FW | V012 | R309-545-13(3) | Rule requires overflow pipes to be screened with #4 mesh non-corrodible screens installed at a location least susceptible to damage by vandalism. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. C 133C Overflow line connected or discharges to a sanitary sewer drain? SIG | 50pts | FW | V013 | R309-545-13(5) | Rule prohibits overflow pipes from connecting to, or discharging into, a sanitary sewer system. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. NA (Notes: No sewer present.) 134 Are the drain line and overflow combined?N DEQ | Drinking Water Run Date: 09/05/2024 12:52:38 | Rating: Approved UTAH13056 DEER SPRINGS RANCH LOWER CABINS page 12 of 13 134A Drain line shall terminate at least 12 inches above ground or flood rim of receiving basin SIG | 25pts | FW | V016 | R309-545-10(1)(d) | If the local authority allows discharge to a storm drain, the rule requires the drain discharge to have a physical clearance of at least 12 inches between the discharge end of the pipe and the overflow rim of the receiving basin. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. C 135 Is the storage structure interior coating or liner peeling or cracked? REC | 0pts | FW | V019 | N/A | The integrity of the interior coating or liner is essential for proper quality control of the drinking water and may be intergral to the structural integrity of the tank. The system management should closely monitor the status of the liner and make plans C 136 If the tank interior has been re-coated, did the materials used comply with ANSI/ NSF Standard 61? NA 137 When was the tank last inspected/cleaned?08/09/2024 138 Do you perform routine security checks of this tank?Y 138A How often do you perform routine secutity checks of this tank?Weekly 139 Could the physical condition of the tank be a source of contamination?N 140 Is proper O&M being performed for this storage tank?Y 141 Does the tank have an excess of floating material on the surface of the water and/or sediment on the bottom of the tank? N 142 Is there evidence of outside water intrusion into the tank?N 143 Are the inside walls of the tank free from staining or bacteral growth?Y DEQ | Drinking Water Run Date: 09/05/2024 12:52:38 | Rating: Approved UTAH13056 DEER SPRINGS RANCH LOWER CABINS page 13 of 13