HomeMy WebLinkAboutDDW-2024-010888Sanitary Survey - Deficiency Report
PWS Number:UTAH18140 Deficiency Points:25 Survey Date:08/23/2024
Survey Name:CARDIFF A.P.O Surveyor:Brad Johnson
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Springs | WS001 | CARDIFF SPRING
67B. Vent has #14 or finer non-corrodible mesh screen and a protective screen/covering if 6-inch diameter or greater.
Rule: R309-515-7(7)(d), R309-545-15(4) and (5)All vents on junction and collection boxes shall comply with R309-545 and be fitted
with No. 14 or finer non-corrodible mesh screen. Vents 6-inch diameter or larger shall
be fitted with additional heavy gage screen or substantial covering to protect the No. 14
mesh screen. This significant deficiency must be corrected within 120 days of
notification or have a corrective action plan approved by DDW.
Notes:Spring line has an additional vent before the tank that was missing the #14 mesh screen
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: SS17 SPRING BOX VENT LACKS NO. 14 SCREEN