HomeMy WebLinkAboutDDW-2024-010866Sanitary Survey - Deficiency Report
PWS Number:UTAH22011 Deficiency Points:75 Survey Date:08/29/2024
Survey Name:PARK CITY WATER SYSTEM Surveyor:Danielle Zebelean
Sanitary Survey Category: DS
SDWIS Severity Code: Significant Deficiency
Distribution | DS001 | UTAH22011 DISTRIBUTION SYSTEM
44B. For a valve in a chamber, open end of vent pipe is at least 12 inches above grade or one foot above distribution line in a chamber that does
not flood.
Rule: R309-550-6(6)(b)Rule states the open end of the air relief vent pipe from automatic valves shall be
provided with a #14 mesh, non-corrodible screen and a downward elbow, and where
possible, be extended to at least one foot above grade. This significant deficiency must
be corrected within 120 days of notification or have a corrective action plan approved
by DDW.
Notes:One air vac in Park City Heights terminates about 1 inch above the ground
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: D006 AIR RELIEF VALVE PIPE NOT DOWNTURNED
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Springs | WS003 | THIRIOT SPRING
94F. All openings/penetrations in the spring collection box are sealed.
Rule: R309-515-7(7)(d), R309-545-9(1) and (2)All junction and collection boxes shall comply with R309-545 and shall have suitable
watertight roofs and sidewalls that exclude birds, animals, insects, and excessive dust.
All openings shall be kept to a minimum and be watertight. Pipes that may contain
water of lesser quality than drinking water shall not penetrate the spring box. This
significant deficiency must be corrected within 120 days of notification or have a
corrective action plan approved by DDW.
Notes:Small hole in side of access hatch
Deficiency Points: 50
Days until points become effective on IPS: 120
SDWIS Deficiency Description: SS20 UNSEALED OPENINGS IN SPRING COLLECTION BOX