HomeMy WebLinkAboutDDW-2024-010866Sanitary Survey - Deficiency Report PWS Number:UTAH22011 Deficiency Points:75 Survey Date:08/29/2024 Survey Name:PARK CITY WATER SYSTEM Surveyor:Danielle Zebelean Sanitary Survey Category: DS SDWIS Severity Code: Significant Deficiency Distribution | DS001 | UTAH22011 DISTRIBUTION SYSTEM 44B. For a valve in a chamber, open end of vent pipe is at least 12 inches above grade or one foot above distribution line in a chamber that does not flood. Rule: R309-550-6(6)(b)Rule states the open end of the air relief vent pipe from automatic valves shall be provided with a #14 mesh, non-corrodible screen and a downward elbow, and where possible, be extended to at least one foot above grade. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:One air vac in Park City Heights terminates about 1 inch above the ground Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: D006 AIR RELIEF VALVE PIPE NOT DOWNTURNED Sanitary Survey Category: SO SDWIS Severity Code: Significant Deficiency Springs | WS003 | THIRIOT SPRING 94F. All openings/penetrations in the spring collection box are sealed. Rule: R309-515-7(7)(d), R309-545-9(1) and (2)All junction and collection boxes shall comply with R309-545 and shall have suitable watertight roofs and sidewalls that exclude birds, animals, insects, and excessive dust. All openings shall be kept to a minimum and be watertight. Pipes that may contain water of lesser quality than drinking water shall not penetrate the spring box. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:Small hole in side of access hatch Deficiency Points: 50 Days until points become effective on IPS: 120 SDWIS Deficiency Description: SS20 UNSEALED OPENINGS IN SPRING COLLECTION BOX