HomeMy WebLinkAboutDERR-2024-010628Utah Department of Environmental Quality - UST Release Detection
TANK OWNERSHIP
Name 7-ELEVEN INC
Address PO BOX 711
DALLAS, TX 75221
Contact 7-ELEVEN INC
Phone
Email Marc.Westfall@7-11.com
TANK LOCATION
Name 7-ELEVEN 1852-16345
Address 10592 S 700 E
SANDY, UT 84070
A Operator MARC WESTFALL
Phone (214) 415-0146
B Operator JACOB POWELL
Phone SAME
Facility ID: 4001419 Inspection Date: 09/05/2024
DISPENSER DETAILS
DISP
ID/ALT
ID
SUBSTANCE UDC PIPE FLEX LOC
INSTALL
DATE
UDC
INSTALL
DATE
FIRE
VALVE
SAT
PRESENT
UDC
TEST
DISP
FLEX
CP
TEST
1 - 1/3 Gasoline Yes Steel Flex in Sump Sept. 9,
1986
None Yes No None None
2 - 2/4 Gasoline Yes Steel Flex in Sump Sept. 9,
1986
None Yes No None None
3 - 5/7 Gasoline Yes Steel Flex in Sump Sept. 9,
1986
None Yes No None None
4 - 6/8 Gasoline Yes Steel Flex in Sump Sept. 9,
1986
None Yes No None None
TANK DETAILS
Tank ID/Alt ID 1 / 1
E-Gen/AST No / No
Siphon/Compart No / No
Tank Status Currently In Use
Installed/Cap/Loc Sept. 9, 1986 / 10000 / West
Substance
Stored Gasoline / Regular
Tank Material-
Mod
Galvanic Cathodic Protection
(STIP3)-None
ATG Veeder Root / TLS-350 CSLD No
Manifold
LTT Test Dec. 5, 2023
LLD Test Dec. 5, 2023
Pipe Material-
Mod
Fiberglass Reinforced Plastic /
None
Pipe type/STP
Cont Pressurized / No
STP Flex
Connectors Booted Steel Flex
LLD Model Vaporless LD2000
Spill/Overfill/Sm
Delivery
5 gal. Spill Bucket / Automatic
shutoff / No
PST Fund/Other
Type Yes / None
Tank/Pipe Rel
Det
TankATG
PipeAutoLineLeakDetection /
PipeLineTightness
CP Tank Test Sept. 28, 2021
CP Pipe Test None
2024-09-05 Page 1 of 6
Tank ID/Alt ID 2 / 2
E-Gen/AST No / No
Siphon/Compart No / No
Tank Status Currently In Use
Installed/Cap/Loc Sept. 9, 1986 / 10000 / Center
Substance
Stored Gasoline / Regular
Tank Material-
Mod
Galvanic Cathodic Protection
(STIP3)-None
ATG Veeder Root / TLS-350 CSLD No
Manifold
LTT Test Dec. 5, 2023
LLD Test Dec. 5, 2023
Pipe Material-
Mod
Fiberglass Reinforced Plastic /
None
Pipe type/STP
Cont Pressurized / No
STP Flex
Connectors Booted Steel Flex
LLD Model Vaporless LD2000
Spill/Overfill/Sm
Delivery
5 gal. Spill Bucket / Automatic
shutoff / No
PST Fund/Other
Type Yes / None
Tank/Pipe Rel
Det
TankATG
PipeAutoLineLeakDetection /
PipeLineTightness
CP Tank Test Sept. 28, 2021
CP Pipe Test None
Tank ID/Alt ID 3 / 3
E-Gen/AST No / No
Siphon/Compart No / No
Tank Status Currently In Use
Installed/Cap/Loc Sept. 9, 1986 / 10000 / East
Substance
Stored Gasoline / Premium
Tank Material-
Mod
Galvanic Cathodic Protection
(STIP3)-None
ATG Veeder Root / TLS-350 CSLD No
Manifold
LTT Test Dec. 5, 2023
LLD Test Dec. 5, 2023
Pipe Material-
Mod
Fiberglass Reinforced Plastic /
None
Pipe type/STP
Cont Pressurized / No
STP Flex
Connectors Booted Steel Flex
LLD Model Vaporless LD2000
Spill/Overfill/Sm
Delivery
5 gal. Spill Bucket / Automatic
shutoff / No
PST Fund/Other
Type Yes / None
Tank/Pipe Rel
Det
TankATG
PipeAutoLineLeakDetection /
PipeLineTightness
CP Tank Test Sept. 28, 2021
CP Pipe Test None
INSPECTION COMMENTS
Title: CP test due
9/28/2024
No Photos
2024-09-05 Page 2 of 6
FACILITY RESPONSES
The above accurately represents the
facility's release detection records Yes
Operator Training
A Operator current?Yes
B Operator current?Yes
Monthly checklist available and
complete?Yes
Is the site unmanned?No
C Operators trained?Yes
Cathodic Protection
The results of the last two cathodic
protection tests are available (within six
months of installation and every three
years thereafter)?
Yes
Financial Responsibility
Financial responsibility method is ok?Yes
TANK RESPONSES
Tank 1 Spill/Overfill
Tank has a spill prevention device?Yes
Are you able to visually inspect the spill
containment bucket(s) for functionality?
(i.e. are the buckets clean enough to
see cracks, etc?)
Yes
Is the spill containment bucket intact?Yes
Is the spill containment bucket(s) able
to contain a spill? (i.e. is there water,
product, debris, etc in the spill bucket
to prevent it from containing a spill?)
Yes
Tank has an overfill device?Yes
Tank 1 ATG/IM
ATG/IM - Records on site document that
the system is properly installed,
calibrated, operated, and maintained
(system and tank setup reports,
maintenance records)? Written
documentation of calibration,
maintenance, and repair is kept for at
least one year after work is completed?
Yes
ATG/IM - ATG console or other
equipment used to take readings and
perform tests is adequate, accessible,
and operational?
Yes
ATG/IM - Documentation of valid testing
or monitoring is available (must have
records for the two most recent months
and 10 of last 12 months)? Show results
in the RD tab.
Yes
ATG - The tank was filled to at least the
minimum level required to ensure a
valid leak test, and the tank size is
within the allowed upper and lower size
limits?
Yes
Tank 1 ATG/IM
Does the ATG system have a valid
annual test?Yes
Tank 1 Cathodic Protection
Tanks are protected from corrosion?Yes
Piping is protected from corrosion?Yes
Flex connectors at the tank sub-pumps
are protected from corrosion?Yes
Tank 1 Pressure Piping Leak Detection
Does the pressurized piping system
have a line leak detector?Yes
Does the pressurized piping system
have a valid line leak detector test?Yes
Does the pressurized piping system
have a valid annual line tightness test
or valid monthly monitoring?
Yes
Tank 1 Spill/Overfill
Does the spill bucket have a valid 3-
year test, valid monthly monitoring for
DW buckets, or the tank is exempt?
Yes
Does the overfill device have a valid 3-
year test or the tank is exempt?Yes
Tank 2 Cathodic Protection
Tanks are protected from corrosion?Yes
Piping is protected from corrosion?Yes
Flex connectors at the tank sub-pumps
are protected from corrosion?Yes
Tank 2 Pressure Piping Leak Detection
Does the pressurized piping system
have a line leak detector?Yes
Does the pressurized piping system
have a valid line leak detector test?Yes
Does the pressurized piping system
have a valid annual line tightness test
or valid monthly monitoring?
Yes
2024-09-05 Page 3 of 6
Tank 2 Spill/Overfill
Tank has a spill prevention device?Yes
Are you able to visually inspect the spill
containment bucket(s) for functionality?
(i.e. are the buckets clean enough to
see cracks, etc?)
Yes
Is the spill containment bucket intact?Yes
Is the spill containment bucket(s) able
to contain a spill? (i.e. is there water,
product, debris, etc in the spill bucket
to prevent it from containing a spill?)
Yes
Tank has an overfill device?Yes
Tank 2 ATG/IM
ATG/IM - Records on site document that
the system is properly installed,
calibrated, operated, and maintained
(system and tank setup reports,
maintenance records)? Written
documentation of calibration,
maintenance, and repair is kept for at
least one year after work is completed?
Yes
ATG/IM - ATG console or other
equipment used to take readings and
perform tests is adequate, accessible,
and operational?
Yes
ATG/IM - Documentation of valid testing
or monitoring is available (must have
records for the two most recent months
and 10 of last 12 months)? Show results
in the RD tab.
Yes
ATG - The tank was filled to at least the
minimum level required to ensure a
valid leak test, and the tank size is
within the allowed upper and lower size
limits?
Yes
Tank 2 ATG/IM
Does the ATG system have a valid
annual test?Yes
Tank 3 Spill/Overfill
Tank has a spill prevention device?Yes
Are you able to visually inspect the spill
containment bucket(s) for functionality?
(i.e. are the buckets clean enough to
see cracks, etc?)
Yes
Is the spill containment bucket intact?Yes
Is the spill containment bucket(s) able
to contain a spill? (i.e. is there water,
product, debris, etc in the spill bucket
to prevent it from containing a spill?)
Yes
Tank has an overfill device?Yes
Tank 2 Spill/Overfill
Does the spill bucket have a valid 3-
year test, valid monthly monitoring for
DW buckets, or the tank is exempt?
Yes
Does the overfill device have a valid 3-
year test or the tank is exempt?Yes
Tank 3 Cathodic Protection
Tanks are protected from corrosion?Yes
Piping is protected from corrosion?Yes
Flex connectors at the tank sub-pumps
are protected from corrosion?Yes
Tank 3 Pressure Piping Leak Detection
Does the pressurized piping system
have a line leak detector?Yes
Does the pressurized piping system
have a valid line leak detector test?Yes
Does the pressurized piping system
have a valid annual line tightness test
or valid monthly monitoring?
Yes
Tank 3 Spill/Overfill
Does the spill bucket have a valid 3-
year test, valid monthly monitoring for
DW buckets, or the tank is exempt?
Yes
Does the overfill device have a valid 3-
year test or the tank is exempt?Yes
2024-09-05 Page 4 of 6
Tank 3 ATG/IM
ATG/IM - Records on site document that
the system is properly installed,
calibrated, operated, and maintained
(system and tank setup reports,
maintenance records)? Written
documentation of calibration,
maintenance, and repair is kept for at
least one year after work is completed?
Yes
ATG/IM - ATG console or other
equipment used to take readings and
perform tests is adequate, accessible,
and operational?
Yes
ATG/IM - Documentation of valid testing
or monitoring is available (must have
records for the two most recent months
and 10 of last 12 months)? Show results
in the RD tab.
Yes
ATG - The tank was filled to at least the
minimum level required to ensure a
valid leak test, and the tank size is
within the allowed upper and lower size
limits?
Yes
Tank 3 ATG/IM
Does the ATG system have a valid
annual test?Yes
DISPENSER RESPONSES
Dispenser 2/4
Flex connectors at the dispensers are
protected from corrosion?Yes
Containment sumps are sealed, free
from water, product, etc?Yes
Fire valve is anchored properly?Yes
Does the line tightness test port on the
fire valve have the manufacturers plug
installed in it? (no ball valves)
Yes
Is the fire valve located properly below
grade?Yes
Is the fire valve's fuseable link intact?Yes
Dispenser 6/8
Flex connectors at the dispensers are
protected from corrosion?Yes
Containment sumps are sealed, free
from water, product, etc?Yes
Fire valve is anchored properly?Yes
Does the line tightness test port on the
fire valve have the manufacturers plug
installed in it? (no ball valves)
Yes
Is the fire valve located properly below
grade?Yes
Is the fire valve's fuseable link intact?Yes
Dispenser 1/3
Flex connectors at the dispensers are
protected from corrosion?Yes
Containment sumps are sealed, free
from water, product, etc?Yes
Fire valve is anchored properly?Yes
Does the line tightness test port on the
fire valve have the manufacturers plug
installed in it? (no ball valves)
Yes
Is the fire valve located properly below
grade?Yes
Is the fire valve's fuseable link intact?Yes
Dispenser 5/7
Flex connectors at the dispensers are
protected from corrosion?Yes
Containment sumps are sealed, free
from water, product, etc?Yes
Fire valve is anchored properly?Yes
Does the line tightness test port on the
fire valve have the manufacturers plug
installed in it? (no ball valves)
Yes
Is the fire valve located properly below
grade?Yes
Is the fire valve's fuseable link intact?Yes
2024-09-05 Page 5 of 6
Prepared by fueloperator.com
MONTHLY LEAK DETECTION MONITORING
Sep '23 Oct '23 Nov '23 Dec '23 Jan '24 Feb '24 Mar '24 Apr '24 May '24 Jun '24 Jul '24 Aug '24
Tank 1 Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass
Line Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl
Tank 2 Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass
Line Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl
Tank 3 Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass
Line Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl
NON-COMPLIANCE ITEMS
All items are in compliance.
Inspection Information
Inspector:Wilson, David
Record Created:Sept. 5, 2024, 12:18
p.m.
Inspection
Date:Sept. 5, 2024
2024-09-05 Page 6 of 6
Facility Compliance Report
Period: August 1 - August 31, 2024
Company Information
Company Name:7-ELEVEN, INC
Address:Cypress Waters - Store Support Center
3200 Hackberry Road
Irving, TX 75063
Phone Number:(972) 828-0711
Regional Compliance Manager -
A Operator:
Marc Westfall
Regional Compliance Specialist -
B Operator:
Jacob Powell 972-828-6511
Facility Information
Facility Name: 16345
State ID: 4001419
Status:Managed (by Company)
Address: 10580 SOUTH 700 EAST
SANDY, UT 84070-4979
County:Salt Lake County
Phone Number: (801)571-2662
Gas Brand: 7-Eleven
Tank Release Detection Results
ATG
Tank # /
Cert # Product Release Detection Method Test Type Test Date Volume % Volume Result
Primary Release Detection
1 / 1 Regular (Ethanol)ATG CSLD (Tank, Continuous)_
PTT
0.20 gal/hr test
(Continuous)
8/1/2024 4,869.34 47.96 PASS
2 / 2 Regular (Ethanol)ATG CSLD (Tank, Continuous) 0.20 gal/hr test
(Continuous)
8/1/2024 4,459.77 43.93 PASS
3 / 3 Premium (Ethanol)ATG CSLD (Tank, Continuous)_
PTT
0.20 gal/hr test
(Continuous)
8/1/2024 3,270.11 32.21 PASS
Automatically approved by System on 9/2/2024 4:05:33 AM -04:00
Report Generated on 9/2/2024 4:05:33 AM -04:00
16345 - AUGUST 1 - AUGUST 31, 2024 Page 1
Titan Cloud Software 4031 Aspen Grove Dr., Ste 240 Franklin, Tennessee 37067 (615) 372-6000
Facility Compliance Report
Period: July 1 - July 31, 2024
Company Information
Company Name:7-ELEVEN, INC
Address:Cypress Waters - Store Support Center
3200 Hackberry Road
Irving, TX 75063
Phone Number:(972) 828-0711
Regional Compliance Manager -
A Operator:
Marc Westfall
Regional Compliance Specialist -
B Operator:
Jacob Powell 972-828-6511
Facility Information
Facility Name: 16345
State ID: 4001419
Status:Managed (by Company)
Address: 10580 SOUTH 700 EAST
SANDY, UT 84070-4979
County:Salt Lake County
Phone Number: (801)571-2662
Gas Brand: 7-Eleven
Tank Release Detection Results
ATG
Tank # /
Cert # Product Release Detection Method Test Type Test Date Volume % Volume Result
Primary Release Detection
1 / 1 Regular (Ethanol)ATG CSLD (Tank, Continuous)_
PTT
0.20 gal/hr test
(Continuous)
7/1/2024 3,691.00 36.36 PASS
2 / 2 Regular (Ethanol)ATG CSLD (Tank, Continuous) 0.20 gal/hr test
(Continuous)
7/1/2024 4,269.25 42.05 PASS
3 / 3 Premium (Ethanol)ATG CSLD (Tank, Continuous)_
PTT
0.20 gal/hr test
(Continuous)
7/1/2024 6,072.42 59.82 PASS
Automatically approved by System on 8/2/2024 4:06:27 AM -04:00
Report Generated on 8/2/2024 4:06:27 AM -04:00
16345 - JULY 1 - JULY 31, 2024 Page 1
Titan Cloud Software 4031 Aspen Grove Dr., Ste 240 Franklin, Tennessee 37067 (615) 372-6000
Facility Compliance Report
Period: June 1 - June 30, 2024
Company Information
Company Name:7-ELEVEN, INC
Address:Cypress Waters - Store Support Center
3200 Hackberry Road
Irving, TX 75063
Phone Number:(972) 828-0711
Regional Compliance Manager -
A Operator:
Marc Westfall
Regional Compliance Specialist -
B Operator:
Jacob Powell 972-828-6511
Facility Information
Facility Name: 16345
State ID: 4001419
Status:Managed (by Company)
Address: 10580 SOUTH 700 EAST
SANDY, UT 84070-4979
County:Salt Lake County
Phone Number: (801)571-2662
Gas Brand: 7-Eleven
Tank Release Detection Results
ATG
Tank # /
Cert # Product Release Detection Method Test Type Test Date Volume % Volume Result
Primary Release Detection
1 / 1 Regular (Ethanol)ATG CSLD (Tank, Continuous)_
PTT
0.20 gal/hr test
(Continuous)
6/2/2024 5,602.57 55.19 PASS
2 / 2 Regular (Ethanol)ATG CSLD (Tank, Continuous) 0.20 gal/hr test
(Continuous)
6/2/2024 5,962.19 58.73 PASS
3 / 3 Premium (Ethanol)ATG CSLD (Tank, Continuous)_
PTT
0.20 gal/hr test
(Continuous)
6/2/2024 3,413.33 33.62 PASS
Automatically approved by System on 7/2/2024 4:05:32 AM -04:00
Report Generated on 7/2/2024 4:05:32 AM -04:00
16345 - JUNE 1 - JUNE 30, 2024 Page 1
Titan Cloud Software 4031 Aspen Grove Dr., Ste 240 Franklin, Tennessee 37067 (615) 372-6000
Facility Compliance Report
Period: May 1 - May 31, 2024
Company Information
Company Name:7-ELEVEN, INC
Address:Cypress Waters - Store Support Center
3200 Hackberry Road
Irving, TX 75063
Phone Number:(972) 828-0711
Regional Compliance Manager -
A Operator:
Marc Westfall
Regional Compliance Specialist -
B Operator:
Jacob Powell 972-828-6511
Facility Information
Facility Name: 16345
State ID: 4001419
Status:Managed (by Company)
Address: 10580 SOUTH 700 EAST
SANDY, UT 84070-4979
County:Salt Lake County
Phone Number: (801)571-2662
Gas Brand: 7-Eleven
Tank Release Detection Results
ATG
Tank # /
Cert # Product Release Detection Method Test Type Test Date Volume % Volume Result
Primary Release Detection
1 / 1 Regular (Ethanol)ATG CSLD (Tank, Continuous)_
PTT
0.20 gal/hr test
(Continuous)
5/1/2024 5,847.67 57.60 PASS
2 / 2 Regular (Ethanol)ATG CSLD (Tank, Continuous) 0.20 gal/hr test
(Continuous)
5/1/2024 3,254.09 32.05 PASS
3 / 3 Premium (Ethanol)ATG CSLD (Tank, Continuous)_
PTT
0.20 gal/hr test
(Continuous)
5/1/2024 3,348.82 32.99 PASS
Automatically approved by System on 6/2/2024 4:05:25 AM -04:00
Report Generated on 6/2/2024 4:05:25 AM -04:00
16345 - MAY 1 - MAY 31, 2024 Page 1
Titan Cloud Software 4031 Aspen Grove Dr., Ste 240 Franklin, Tennessee 37067 (615) 372-6000
Facility Compliance Report
Period: April 1 - April 30, 2024
Company Information
Company Name:7-ELEVEN, INC
Address:Cypress Waters - Store Support Center
3200 Hackberry Road
Irving, TX 75063
Phone Number:(972) 828-0711
Regional Compliance Manager -
A Operator:
Marc Westfall
Regional Compliance Specialist -
B Operator:
Jacob Powell 972-828-6511
Facility Information
Facility Name: 16345
State ID: 4001419
Status:Managed (by Company)
Address: 10580 SOUTH 700 EAST
SANDY, UT 84070-4979
County:Salt Lake County
Phone Number: (801)571-2662
Gas Brand: 7-Eleven
Tank Release Detection Results
ATG
Tank # /
Cert # Product Release Detection Method Test Type Test Date Volume % Volume Result
Primary Release Detection
1 / 1 Regular (Ethanol)ATG CSLD (Tank, Continuous) 0.20 gal/hr test
(Continuous)
4/16/2024 3,276.07 32.27 PASS
2 / 2 Regular (Ethanol)ATG CSLD (Tank, Continuous) 0.20 gal/hr test
(Continuous)
4/1/2024 4,756.60 46.85 PASS
3 / 3 Premium (Ethanol)ATG CSLD (Tank, Continuous) 0.20 gal/hr test
(Continuous)
4/1/2024 2,146.39 21.14 PASS
Automatically approved by System on 5/2/2024 4:05:42 AM -04:00
Report Generated on 5/2/2024 4:05:42 AM -04:00
16345 - APRIL 1 - APRIL 30, 2024 Page 1
Titan Cloud Software 4031 Aspen Grove Dr., Ste 240 Franklin, Tennessee 37067 (615) 372-6000
Facility Compliance Report
Period: March 1 - March 31, 2024
Company Information
Company Name:7-ELEVEN, INC
Address:Cypress Waters - Store Support Center
3200 Hackberry Road
Irving, TX 75063
Phone Number:(972) 828-0711
Regional Compliance Manager -
A Operator:
Marc Westfall
Regional Compliance Specialist -
B Operator:
Jacob Powell 972-828-6511
Facility Information
Facility Name: 16345
State ID: 4001419
Status:Managed (by Company)
Address: 10580 SOUTH 700 EAST
SANDY, UT 84070-4979
County:Salt Lake County
Phone Number: (801)571-2662
Gas Brand: 7-Eleven
Tank Release Detection Results
ATG
Tank # /
Cert # Product Release Detection Method Test Type Test Date Volume % Volume Result
Primary Release Detection
1 / 1 Regular (Ethanol)ATG CSLD (Tank, Continuous) 0.20 gal/hr test
(Continuous)
3/1/2024 1,569.61 15.46 PASS
2 / 2 Regular (Ethanol)ATG CSLD (Tank, Continuous) 0.20 gal/hr test
(Continuous)
3/1/2024 5,436.24 53.55 PASS
3 / 3 Premium (Ethanol)ATG CSLD (Tank, Continuous) 0.20 gal/hr test
(Continuous)
3/1/2024 3,361.83 33.11 PASS
Automatically approved by System on 4/2/2024 4:04:56 AM -04:00
Report Generated on 4/2/2024 4:04:56 AM -04:00
16345 - MARCH 1 - MARCH 31, 2024 Page 1
Titan Cloud Software 4031 Aspen Grove Dr., Ste 240 Franklin, Tennessee 37067 (615) 372-6000
Facility Compliance Report
Period: February 1 - February 29, 2024
Company Information
Company Name:7-ELEVEN, INC
Address:Cypress Waters - Store Support Center
3200 Hackberry Road
Irving, TX 75063
Phone Number:(972) 828-0711
Regional Compliance Manager -
A Operator:
Marc Westfall
Regional Compliance Specialist -
B Operator:
Jacob Powell 972-828-6511
Facility Information
Facility Name: 16345
State ID: 4001419
Status:Managed (by Company)
Address: 10580 SOUTH 700 EAST
SANDY, UT 84070-4979
County:Salt Lake County
Phone Number: (801)571-2662
Gas Brand: 7-Eleven
Tank Release Detection Results
ATG
Tank # /
Cert # Product Release Detection Method Test Type Test Date Volume % Volume Result
Primary Release Detection
1 / 1 Regular (Ethanol)ATG CSLD (Tank, Continuous) 0.20 gal/hr test
(Continuous)
2/1/2024 6,170.51 60.78 PASS
2 / 2 Regular (Ethanol)ATG CSLD (Tank, Continuous) 0.20 gal/hr test
(Continuous)
2/1/2024 6,747.59 66.47 PASS
3 / 3 Premium (Ethanol)ATG CSLD (Tank, Continuous) 0.20 gal/hr test
(Continuous)
2/1/2024 5,684.09 55.99 PASS
Automatically approved by System on 3/2/2024 4:05:21 AM -05:00
Report Generated on 3/2/2024 4:05:21 AM -05:00
16345 - FEBRUARY 1 - FEBRUARY 29, 2024 Page 1
Titan Cloud Software 4031 Aspen Grove Dr., Ste 240 Franklin, Tennessee 37067 (615) 372-6000
Facility Compliance Report
Period: January 1 - January 31, 2024
Company Information
Company Name:7-ELEVEN, INC
Address:Cypress Waters - Store Support Center
3200 Hackberry Road
Irving, TX 75063
Phone Number:(972) 828-0711
Regional Compliance Manager -
A Operator:
Marc Westfall
Regional Compliance Specialist -
B Operator:
Jacob Powell 972-828-6511
Facility Information
Facility Name: 16345
State ID: 4001419
Status:Managed (by Company)
Address: 10580 SOUTH 700 EAST
SANDY, UT 84070-4979
County:Salt Lake County
Phone Number: (801)571-2662
Gas Brand: 7-Eleven
Tank Release Detection Results
ATG
Tank # /
Cert # Product Release Detection Method Test Type Test Date Volume % Volume Result
Primary Release Detection
1 / 1 Regular (Ethanol)ATG CSLD (Tank, Continuous) 0.20 gal/hr test
(Continuous)
1/1/2024 5,429.98 53.49 PASS
2 / 2 Regular (Ethanol)ATG CSLD (Tank, Continuous) 0.20 gal/hr test
(Continuous)
1/1/2024 4,092.80 40.32 PASS
3 / 3 Premium (Ethanol)ATG CSLD (Tank, Continuous) 0.20 gal/hr test
(Continuous)
1/1/2024 6,029.17 59.39 PASS
Automatically approved by System on 2/2/2024 4:05:22 AM -05:00
Report Generated on 2/2/2024 4:05:22 AM -05:00
16345 - JANUARY 1 - JANUARY 31, 2024 Page 1
Titan Cloud Software 4031 Aspen Grove Dr., Ste 240 Franklin, Tennessee 37067 (615) 372-6000
Facility Compliance Report
Period: December 1, 2023 - December 31, 2023
Company Information
Company Name:7-ELEVEN, INC
Address:Cypress Waters - Store Support Center
3200 Hackberry Road
Irving, TX 75063
Phone Number:(972) 828-0711
Regional Compliance Manager -
A Operator:
Marc Westfall
Regional Compliance Specialist -
B Operator:
Jacob Powell 972-828-6511
Facility Information
Facility Name: 16345
State ID: 4001419
Status:Managed (by Company)
Address: 10580 SOUTH 700 EAST
SANDY, UT 84070-4979
County:Salt Lake County
Phone Number: (801)571-2662
Gas Brand: 7-Eleven
Tank Release Detection Results
ATG
Tank # /
Cert # Product Release Detection Method Test Type Test Date Volume % Volume Result
Primary Release Detection
1 / 1 Regular (Ethanol)ATG CSLD (Tank, Continuous) 0.20 gal/hr test
(Continuous)
12/1/2023 7,174.35 70.67 PASS
2 / 2 Regular (Ethanol)ATG CSLD (Tank, Continuous) 0.20 gal/hr test
(Continuous)
12/1/2023 6,454.17 63.58 PASS
3 / 3 Premium (Ethanol)ATG CSLD (Tank, Continuous) 0.20 gal/hr test
(Continuous)
12/1/2023 3,560.14 35.07 PASS
Automatically approved by System on 1/2/2024 4:09:31 AM -05:00
Report Generated on 1/2/2024 4:09:31 AM -05:00
16345 - DECEMBER 1, 2023 - DECEMBER 31, 2023 Page 1
Titan Cloud Software 4031 Aspen Grove Dr., Ste 240 Franklin, Tennessee 37067 (615) 372-6000
Facility Compliance Report
Period: November 1 - November 30, 2023
Company Information
Company Name:7-ELEVEN, INC
Address:Cypress Waters - Store Support Center
3200 Hackberry Road
Irving, TX 75063
Phone Number:(972) 828-0711
Regional Compliance Manager -
A Operator:
Marc Westfall
Regional Compliance Specialist -
B Operator:
Jacob Powell 972-828-6511
Facility Information
Facility Name: 16345
State ID: 4001419
Status:Managed (by Company)
Address: 10580 SOUTH 700 EAST
SANDY, UT 84070-4979
County:Salt Lake County
Phone Number: (801)571-2662
Gas Brand: 7-Eleven
Tank Release Detection Results
ATG
Tank # /
Cert # Product Release Detection Method Test Type Test Date Volume % Volume Result
Primary Release Detection
1 / 1 Regular (Ethanol)ATG CSLD (Tank, Continuous) 0.20 gal/hr test
(Continuous)
11/1/2023 4,511.90 44.44 PASS
2 / 2 Regular (Ethanol)ATG CSLD (Tank, Continuous) 0.20 gal/hr test
(Continuous)
11/1/2023 7,097.26 69.91 PASS
3 / 3 Premium (Ethanol)ATG CSLD (Tank, Continuous) 0.20 gal/hr test
(Continuous)
11/1/2023 5,650.18 55.66 PASS
Automatically approved by System on 12/2/2023 4:05:19 AM -05:00
Report Generated on 12/2/2023 4:05:19 AM -05:00
16345 - NOVEMBER 1 - NOVEMBER 30, 2023 Page 1
Titan Cloud Software 4031 Aspen Grove Dr., Ste 240 Franklin, Tennessee 37067 (615) 372-6000
Facility Compliance Report
Period: October 1 - October 31, 2023
Company Information
Company Name:7-ELEVEN, INC
Address:Cypress Waters - Store Support Center
3200 Hackberry Road
Irving, TX 75063
Phone Number:(972) 828-0711
Regional Compliance Manager -
A Operator:
Marc Westfall
Regional Compliance Specialist -
B Operator:
Jacob Powell 972-828-6511
Facility Information
Facility Name: 16345
State ID: 4001419
Status:Managed (by Company)
Address: 10580 SOUTH 700 EAST
SANDY, UT 84070-4979
County:Salt Lake County
Phone Number: (801)571-2662
Gas Brand: 7-Eleven
Tank Release Detection Results
ATG
Tank # /
Cert # Product Release Detection Method Test Type Test Date Volume % Volume Result
Primary Release Detection
1 / 1 Regular (Ethanol)ATG CSLD (Tank, Continuous) 0.20 gal/hr test
(Continuous)
10/1/2023 6,792.76 66.91 PASS
2 / 2 Regular (Ethanol)ATG CSLD (Tank, Continuous) 0.20 gal/hr test
(Continuous)
10/1/2023 6,827.32 67.25 PASS
3 / 3 Premium (Ethanol)ATG CSLD (Tank, Continuous) 0.20 gal/hr test
(Continuous)
10/1/2023 6,136.74 60.45 PASS
Automatically approved by System on 11/2/2023 4:06:55 AM -04:00
Report Generated on 11/2/2023 4:06:55 AM -04:00
16345 - OCTOBER 1 - OCTOBER 31, 2023 Page 1
Titan Cloud Software 4031 Aspen Grove Dr., Ste 240 Franklin, Tennessee 37067 (615) 372-6000
Facility Compliance Report
Period: September 1 - September 30, 2023
Company Information
Company Name:7-ELEVEN, INC
Address:Cypress Waters - Store Support Center
3200 Hackberry Road
Irving, TX 75063
Phone Number:(972) 828-0711
Regional Compliance Manager -
A Operator:
Marc Westfall
Regional Compliance Specialist -
B Operator:
Jacob Powell 972-828-6511
Facility Information
Facility Name: 16345
State ID: 4001419
Status:Managed (by Company)
Address: 10580 SOUTH 700 EAST
SANDY, UT 84070-4979
County:Salt Lake County
Phone Number: (801)571-2662
Gas Brand: 7-Eleven
Tank Release Detection Results
ATG
Tank # /
Cert # Product Release Detection Method Test Type Test Date Volume % Volume Result
Primary Release Detection
1 / 1 Regular (Ethanol)ATG CSLD (Tank, Continuous) 0.20 gal/hr test
(Continuous)
9/1/2023 6,513.37 64.16 PASS
2 / 2 Regular (Ethanol)ATG CSLD (Tank, Continuous) 0.20 gal/hr test
(Continuous)
9/1/2023 6,663.73 65.64 PASS
3 / 3 Premium (Ethanol)ATG CSLD (Tank, Continuous) 0.20 gal/hr test
(Continuous)
9/1/2023 3,024.99 29.80 PASS
Automatically approved by System on 10/2/2023 4:06:54 AM -04:00
Report Generated on 10/2/2023 4:06:54 AM -04:00
16345 - SEPTEMBER 1 - SEPTEMBER 30, 2023 Page 1
Titan Cloud Software 4031 Aspen Grove Dr., Ste 240 Franklin, Tennessee 37067 (615) 372-6000