HomeMy WebLinkAboutDERR-2024-010526 WESTECH EQUIPMENT
195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307
801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054
PRODUCT PIPING INTEGRITY TESTING
Facility Name: Harmon’s Brickyard Owner: Harmon’s Taylorsville, LLC
Address: 3270 South 1300 East Address: 3540 South 4000 West, Suite 500
City, State, Zip: Salt Lake City, Utah 84106 City, State, Zip: West Valley City, Utah 84120
Facility I.D.#: 4002598 Phone #: 385-255-1734
Testing Company: Westech Phone #: 801-266-2545 Date: 9/4/24
This procedure is to test the integrity of product piping. Tests were performed with Petro-Tite line tester.
Tank Number 1 2 3
Product Stored RUL PUL DSL
Piping Run Only Only Only
Piping Type Flex D/W Flex D/W Flex D/W
Test Pressure (psig) 50 50 50
Test Duration (minutes) 30 30 30
Leak Rate (GPH) 0.000 0.000 0.000
Test Results ☒Pass ☐Fail ☒Pass ☐Fail ☒Pass ☐Fail ☐Pass ☐Fail
Comments:
Tester’s Name Taber DeHart, UT-0394 Tester’s Signature
RU
L
D
i
e
s
e
l
R
U
L
WESTECH EQUIPMENT
195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307
801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054
MECHANICAL AND ELECTRONIC LINE LEAK DETECTOR PERFORMANCE TESTS
Facility Name: Harmon’s Brickyard Owner: Harmon’s Taylorsville, LLC
Address: 3270 South 1300 East Address: 3540 South 4000 West, Suite 500
City, State, Zip: Salt Lake City, Utah 84106 City, State, Zip: West Valley City, Utah 84120
Facility I.D.#: 4002598 Phone #: 385-255-1734
Testing Company: Westech Phone #: 801-266-2545 Date: 9/4/24
This data sheet can be used to test the mechanical line leak detector (MLLD) and electronic line leak detector (ELLD) with submersible turbine
pump (STP) systems. See PEI/RP 1200 Sections 9.1 and 9.2 for test procedures.
Line Number 1 2 3
Product Stored RUL PUL DSL
Leak Detector Manufacturer Red Jacket Red Jacket Red Jacket
Leak Detector Model FX1V FX1V FX1DV
Type Of leak Detector
☒MLLD
☐ELLD
☒MLLD
☐ELLD
☒MLLD
☐ELLD
☐MLLD
☐ELLD
MLLD (ALL PRESSURE MEASURMENTS ARE MADE IN PSIG)
STP full operating pressure 32 32 34
Check valve holding pressure 21 21 31
Line resiliency (ml) (line bleedback volume as measured
from check valve holding pressure to 0 psig) 100 115 110
Step through time in seconds (time the MLLD hesitates at
metering pressure before going to full operating pressure as
measured from 0 sig with no leak induced on the line)
1 1 1
Metering pressure (STP pressure when simulated leak rate 3
gph at 10 psig) 10 10 10
Opening time in seconds (the time the MLLD opens to allow
full pressure after simulated leak is stopped) 2 1 1
Does the STP pressure remain at or below the metering
pressure for at least 60 seconds when the simulated leak is
induced? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No
Does the leak detector reset (trip) when the line pressure is
bled off to zero psig? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No
Does STP properly clycle on/off under normal fuel system
operating conditions? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No
A "No" answer to any of the above questions indicates that the MLLD fails the test.
ELLD (ALL PRESSURE MEASURMENTS ARE MADE IN PSIG)
STP full operating pressure
How many test cycles are observed before alarm/shutdown
occurs?
Does the simulated leak cause on alarm? ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
A "No" answer to the above question indicates that the ELLD fails the test.
Does the simulated leak cause an STP shutdown? ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
Test Results ☒Pass ☐Fail ☒Pass ☐Fail ☒Pass ☐Fail ☐Pass ☐Fail
Comments:
Tester’s Name Taber DeHart, UT-0394 Tester’s Signature
WESTECH EQUIPMENT
195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307
801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054
AUTOMATIC TANK GAUGE OPERATION INSPECTION
Facility Name: Harmon’s Brickyard Owner: Harmon’s Taylorsville, LLC
Address: 3270 South 1300 East Address: 3540 South 4000 West, Suite 500
City, State, Zip: Salt Lake City, Utah 84106 City, State, Zip: West Valley City, Utah 84120
Facility I.D.#: 4002598 Phone #: 385-255-1734
Testing Company: Westech Phone #: 801-266-2545 Date:
This procedure is to determine whether the automatic tank gauge (ATG) is operating properly. See PEI/RP1200 Section 8.2 for the inspection
procedure. This procedure is applicable to tank monitor stems that touch the bottom of the tank when in place.
Tank Number 1 2 3
Product Stored RUL PUL DSL
ATG Brand and Model TLS450 TLS450 TLS450
1. Tank Volume, gallons 11,873 10,257 10,318
2. Tank Diameter, inches 119.7 119.7 119.7
3. After removing the ATG from the tank, it has been
inspected and any damaged or missing parts replaced? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No
4. Float moves freely on the stem without binding? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No
5. Fuel float level agree with the value programmed
into the console? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No
6. Water float level agree with the value programmed
into the console? ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No
7. Inch level from the bottom of the stem when 90%
alarm is triggered? 99 3/8 99 1/8 100 7/8
8. Inch level at which the overfill alarm activates
corresponds with the value programmed in the
gauge?
☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No
9. Inch level from the bottom when the water float
first triggers an alarm? 1 1 1
10. Inch level at which the water float alarm activates
corresponds with the value programmed in the
gauge?
☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No
If any answers in Lines 3, 4, 5, or 6 are "No" the system has failed the test.
Test Results ☒Pass ☐Fail ☒Pass ☐Fail ☒Pass ☐Fail ☐Pass ☐Fail
Comments: Battery OK
Tester’s Name Taber DeHart, UT-0394 Tester’s Signature
WESTECH EQUIPMENT
195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307
801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054
LIQUID SENSER FUNCTIONALITY TESTING
Facility Name: Harmon’s Brickyard Owner: Harmon’s Taylorsville, LLC
Address: 3270 South 1300 East Address: 3540 South 4000 West, Suite 500
City, State, Zip: Salt Lake City, Utah 84106 City, State, Zip: West Valley City, Utah 84120
Facility I.D.#: 4002598 Phone #: 385-255-1734
Testing Company: Westech Phone #: 801-266-2545 Date: 9/4/24
This procedure is to determine whether liquid sensors, located in the interstitial spaces of the UST systems, are able to det ect the presence of water and fuel. See
PEI/RP1200, Section 8.3 for the test procedure.
Sensor Location L1 INT L2 INT L3 STP L4 STP L5 STP L6 UDC 1/2 L7 UDC 3/4
Product Stored RUL PUL/DSL RUL PUL DSL All RUL/PUL
Type of Sensor
☐ Discriminating
☒ Non-Discrimi-
nating
☐ Discriminating
☒ Non-Discrimi-
nating
☐ Discriminating
☒ Non-Discrimi-
nating
☐ Discriminating
☒ Non-Discrimi-
nating
☐ Discriminating
☒ Non-Discrimi-
nating
☐ Discriminating
☒ Non-Discrimi-
nating
☐ Discriminating
☒ Non-Discrimi-
nating
Test Liquid ☒ Water
☐ Product
☒ Water
☐ Product
☒ Water
☐ Product
☒ Water
☐ Product
☒ Water
☐ Product
☒ Water
☐ Product
☒ Water
☐ Product
Is the ATG Console clear of any active or
recurring warnings or alarms regarding
the leak sensor? If the sensor is in alarm
and functioning, indicate why.
☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No
Is sensor alarm circuit
operational? ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No
Has sensor been inspected and in good
operating condition? ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No
When placed in test liquid, does the
sensor trigger an alarm? ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No
When alarm is trigger, is the sensor
identified on the ATG console? ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No ☒ Yes ☐ No
Any “No” answers indicate the sensor fails the test.
Test Results: ☒ Pass ☐ Fail ☒ Pass ☐ Fail ☒ Pass ☐ Fail ☒ Pass ☐ Fail ☒ Pass ☐ Fail ☒ Pass ☐ Fail ☒ Pass ☐ Fail
Comments:
Tester’s Name: Taber DeHart, UT-0394 Tester’s Signature
WESTECH EQUIPMENT
195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307
801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054
LIQUID SENSER FUNCTIONALITY TESTING
Facility Name: Harmon’s Brickyard Owner: Harmon’s Taylorsville, LLC
Address: 3270 South 1300 East Address: 3540 South 4000 West, Suite 500
City, State, Zip: Salt Lake City, Utah 84106 City, State, Zip: West Valley City, Utah 84120
Facility I.D.#: 4002598 Phone #: 385-255-1734
Testing Company: Westech Phone #: 801-266-2545 Date: 9/4/24
This procedure is to determine whether liquid sensors, located in the interstitial spaces of the UST systems, are able to detect the presence of water and fuel. See
PEI/RP1200, Section 8.3 for the test procedure.
Sensor Location L8 UDC 5/6
Product Stored ALL
Type of Sensor
☐ Discriminating
☒ Non-Discrimi-
nating
☐ Discriminating
☐ Non-Discrimi-
nating
☐ Discriminating
☐ Non-Discrimi-
nating
☐ Discriminating
☐ Non-Discrimi-
nating
☐ Discriminating
☐ Non-Discrimi-
nating
☐ Discriminating
☐ Non-Discrimi-
nating
☐ Discriminating
☐ Non-Discrimi-
nating
Test Liquid ☒ Water
☐ Product
☐ Water
☐ Product
☐ Water
☐ Product
☐ Water
☐ Product
☐ Water
☐ Product
☐ Water
☐ Product
☐ Water
☐ Product
Is the ATG Console clear of any active or
recurring warnings or alarms regarding
the leak sensor? If the sensor is in alarm
and functioning, indicate why.
☒ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No
Is sensor alarm circuit
operational? ☒ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No
Has sensor been inspected and in good
operating condition? ☒ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No
When placed in test liquid, does the
sensor trigger an alarm? ☒ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No
When alarm is trigger, is the sensor
identified on the ATG console? ☒ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No ☐ Yes ☐ No
Any “No” answers indicate the sensor fails the test.
Test Results: ☒ Pass ☐ Fail ☐ Pass ☐ Fail ☐ Pass ☐ Fail ☐ Pass ☐ Fail ☐ Pass ☐ Fail ☐ Pass ☐ Fail ☐ Pass ☐ Fail
Comments:
Tester’s Name: Taber DeHart, UT-0394 Tester’s Signature
WESTECH EQUIPMENT
195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307
801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054
PRESSURE/VACUUM VENT CAP
LEAK RATES AND OPENING PRESSURES
Facility Name: Harmon’s Brickyard Owner: Harmon’s Taylorsville, LLC
Address: 3270 South 1300 East Address: 3540 South 4000 West, Suite 500
City, State, Zip: Salt Lake City, Utah 84106 City, State, Zip: West Valley City, Utah 84120
Facility I.D.#: 4002598 Phone #: 385-255-1734
Testing Company: Westech Phone #: 801-266-2545 Date: 9/4/24
This procedure is to determine pressure/vent cap specifications. See 40 CFR 63 CCCCCC for the inspection procedure.
Tank Number 1 2
Product Grade RUL PUL
PV Manufacturer OPW OPW
Model Number 623V 623V
PRESSURE TEST
Passing 2” Leak Rate (CFH) <0.05
Measured 2” Leak Rate (CFH) New Cap New Cap
Passing Positive Opening Pressure (Inches WC) 2.5 – 6.0
Measured Positive Opening Pressure (Inches WC) New Cap New Cap
VACUUM TEST
Passing -4” Leak Rate (CFH) <0.21
Measured -4” Leak Rate (CFH) New Cap New Cap
Passing Negative Opening Pressure (Inched WC) 6.0 – 10.0
Measured Negative Opening Pressure (Inched WC) New Cap New Cap
Test Results ☒Pass ☐Fail ☒Pass ☐Fail ☐Pass ☐Fail ☐Pass ☐Fail
Comments: New PV caps installed 7/24/24.
Tester’s Name Taber DeHart, UT-0394 Tester’s Signature