HomeMy WebLinkAboutDDW-2024-010627Sanitary Survey - Deficiency Report PWS Number:UTAH18019 Deficiency Points:50 Survey Date:08/06/2024 Survey Name:WHITE CITY WID Surveyor:Brad Johnson Sanitary Survey Category: SO SDWIS Severity Code: Significant Deficiency Wells | WS010 | WELL NO 8 139B. Air vacuum relief valve on well discharge piping screened with #14 mesh screen Rule: R309-515-6(12)(d)(v)Rule requires the exhaust/relief piping on an air release/vacuum relief valve on the well discharge piping to be covered with a #14 mesh corrosion-resistant screen. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:#4 mesh screen but no #14 mesh screen Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: S029 END OF AIR RELEASE VACUUM RELIEF VALVE PIPING LACKS NO. 14 SCREEN Sanitary Survey Category: SO SDWIS Severity Code: Significant Deficiency Wells | WS013 | WELL NO 10 169A. Vent screened with #14 mesh screen Rule: R309-515-6(12)(d)(iii)Guidance states provisions should be made for venting the well casing, however if vented R309-515-6(12)(d)(iii) and R309-550-6(6)(a)require vents be fitted with a #14 mesh or finer non-corrodible screen. Notes:#4 mesh screen but no #14 mesh screen Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: S006 END OF WELL CASING VENT LACKS NO. 14 SCREEN