HomeMy WebLinkAboutDDW-2024-010617Sanitary Survey - Deficiency Report
PWS Number:UTAH26069 Deficiency Points:150 Survey Date:08/21/2024
Survey Name:CANYON MEADOWS
MUTUAL WATER COMPANY
Surveyor:Julie Cobleigh
Sanitary Survey Category: FW
SDWIS Severity Code: Minor Deficiency
Management and Operations | DS001 | UTAH26069 DISTRIBUTION SYSTEM
29A. System lacks required storage capacity due to fire demand
Rule: R309-510-8(1)(b)Rule requires a public water system to provide equalization storage volume (to meet
average day demands for indoor and irrigation water use), fire flow storage volume (if
equipped with fire hydrants for fire suppression or required by the local fire code
official), and emergency storage (if deemed appropriate by the water system or the
Director).
Notes:Systems lacks 13,639 gallons of required storage capacity. New tank is almost complete
which will resolve this deficiency.
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: VF34 SYSTEM LACKS REQUIRED STORAGE CAPACITY DUE TO FIRE DEMAND BUT
HAS SOP FOR FOLLOWING FIRE INCIDENT
Sanitary Survey Category: SM
SDWIS Severity Code: Minor Deficiency
Cross Connection and Operator Certification | DS001 | UTAH26069 DISTRIBUTION SYSTEM
37. Documentation of personnel trained to manage the program (ALL COMUNITY WATER SYSTEMS REQUIRE A DDW CERTIFIED CCC
PROGRAM ADMINISTRATOR. ALL OTHER WATER SYSTEMS REQUIRE AT A MINIMUM BACKFLOW 101 OR EQUIVALENT/
GREATER CCC TRAINING)
Rule: R309-105-12(2)Rule requires each public water system to have a cross connection control program
that includes an operator with adequate training in the area of cross connection control
or backflow prevention.
Notes:needs program administrator
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: M005 CCC-LACKS OPERATOR TRAINING
Sanitary Survey Category: SM
SDWIS Severity Code: Minor Deficiency
Cross Connection and Operator Certification | DS001 | UTAH26069 DISTRIBUTION SYSTEM
39. Does the water system have records of on-going enforcement activities? (test history, enforcement activities, hazard assessments)
Rule: R309-105-12(2)Rule requires each public water system to have a cross connection control program
that includes test history and documentation of on-going enforcement activities.
Notes:needs to complete the administrator course
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: M007 CCC-LACKS ON-GOING ENFORCEMENT IMPLEMENTATION
Sanitary Survey Category: DS
SDWIS Severity Code: Significant Deficiency
Distribution | DS001 | UTAH26069 DISTRIBUTION SYSTEM
44A. Open end of vent line covered with #14 mesh screen
Rule: R309-550-6(6)(b)Rule states the open end of the air relief vent pipe from automatic valves shall be
provided with a #14 mesh, non-corrodible screen and a downward elbow, and where
possible, be extended to at least one foot above grade. This significant deficiency must
be corrected within 120 days of notification or have a corrective action plan approved
by DDW.
Notes:no screen
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: D004 AIR RELIEF VALVE PIPE LACKS NO. 14 SCREEN
Sanitary Survey Category: DS
SDWIS Severity Code: Significant Deficiency
Distribution | DS001 | UTAH26069 DISTRIBUTION SYSTEM
44D. Open end of vent line down-turned.
Rule: R309-550-6(6)(b)Rule states the open end of the air relief vent pipe from automatic valves shall be
provided with a #14 mesh, non-corrodible screen and a downward elbow, and where
possible, be extended to at least one foot above grade. This significant deficiency must
be corrected within 120 days of notification or have a corrective action plan approved
by DDW.
Notes:not downturned
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: D006 AIR RELIEF VALVE PIPE NOT DOWNTURNED
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST001 | STORAGE FACILITY ST001
72B. Overflow line covered with #4 mesh non-corrodible screen
Rule: R309-545-13(3)Rule requires overflow pipes to be screened with #4 mesh non-corrodible screens
installed at a location least susceptible to damage by vandalism. This significant
deficiency must be corrected within 120 days of notification or have a corrective action
plan approved by DDW.
Notes:no screeen
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V012 END OF STORAGE TANK OVERFLOW PIPE LACKS NO. 4 SCREEN
Sanitary Survey Category: TR
SDWIS Severity Code: Minor Deficiency
Treatment - General | TP001 | LITTLE DEER CREEK WTP
95B. There are adequate spill containment provisions for acid and caustic liquids.
Rule: R309-525-11(6)(a)(iv)(B), R309-525-
11(8)(b)(viii)
Rule requires liquid chemical storage tanks to have an overflow and receiving basin or
drain capable of receiving accidental spills or overflows, and meeting all the
requirements of R309-525-23.
Notes:no spill containment for chemical storage tanks
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: TG59 LACKS CONTAINMENT PROVISIONS TO HANDLE SOLUTION TANK SPILLS OR
OVERFLOWS
Sanitary Survey Category: TR
SDWIS Severity Code: Minor Deficiency
Treatment - General | TP001 | LITTLE DEER CREEK WTP
95F. Chemical storage tank access opening properly covered?
Rule: R309-105-7, 8 & 18, R309-100 through
605
Trigger for regulatory followup to address concerns.
Notes:storage tank lids not secure and have hole in lid
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: TGR9 TRIGGER FOR REGULATORY FOLLOWUP TO ADDRESS CONCERNS