HomeMy WebLinkAboutDDW-2024-010537
195 North 1950 West • Salt Lake City, UT Mailing Address: P.O. Box 144830 • Salt Lake City, UT 84114-4830 Telephone (801) 536-4200 • Fax (801) 536-4211 • T.D.D. (801) 903-3978
www.deq.utah.gov Printed on 100% recycled paper
State of Utah
SPENCER J. COX Governor DEIDRE HENDERSON Lieutenant Governor
Department of Environmental Quality
Kimberly D. Shelley Executive Director DIVISION OF DRINKING WATER Nathan Lunstad P.E. Director
August 20, 2024
Max Covey Jordanelle SSD PO BOX 519 10500 N 14200 W
Heber City, UT 84032
Subject: Notice of Increased Monitoring and Confirmation Sampling Requirements for
Jordanelle SSD; UTAH26086
Max Covey: According to the Division of Drinking Water’s (the Division) records, thallium was recently
detected in the water leaving the Keetley WTP (TP003) at 0.0036 mg/L. The maximum contaminant level for thallium is 0.002mg/L. Pursuant to R309-205-5, the Keetley WTP (TP003) is now subject to confirmation sampling and increased monitoring requirements. Please collect a thallium sample from the Keetley WTP (TP003) as soon as possible and submit
the results to the Division. Additionally, the Keetley WTP (TP003) is now required to be sampled each quarter for thallium. Compliance with the thallium standard will be based on the running annual average (RAA). If the RAA for thallium is greater than 0.002 mg/L after one year of quarterly sampling, the system will
be considered in violation of the thallium standard and public notice will be required.
The current monitoring requirements for the Keetley WTP (TP003) are given below. An updated monitoring schedule can be viewed anytime online at waterlink.utah.gov.
Facility with new
requirements
Analyte(s)
Required
# Of
samples
Sampling
Frequency Next Due Date Rule
Reference
TP003 Keetley WTP Thallium 1 Quarterly 07/01/2024-
09/30/2024
R309-205-
5(3)(g)
Antimony 1 Quarterly 07/01/2024-09/30/2024 R309-205-5(3)(g)
Max Covey Page 2 of 2
August 20, 2024
Carbon 1 Monthly 07/01/2024-
07/31/2024 R309-205-12
Nitrate 1 Yearly 01/01/2025-12/31/2025 R309-205-5
Pesticides 2 Every Three Years 01/01/2023-12/31/2025 R309-205-6(1)
Sulfate, Sodium, TDS 1 Yearly 01/01/2025-12/31/2025 R309-205-5
Volatile Organics 1 Every Three Years 01/01/2026-12/31/2028 R309-205-6(2)
Radionuclides 1 Every six years 01/01/2020-12/31/2025 R309-205-5
Inorganics and Metals 1 Yearly 01/01/2025-12/31/2025 R309-205-5
Thank you for your efforts in maintaining a safe drinking water system. If you have questions concerning the systems source sampling requirements, please contact David Kruse at 385-566-7789 (dbkruse@utah.gov).
Sincerely,
Mark Berger Monitoring and Standards - Implementation Manager Enclosures: Monitoring Schedule cc: Max Covey, Jordanelle SSD, mcovey@jssd.us Dwight Hill, Wasatch County Health Department, dhill@wasatch.utah.gov Mark Berger, Division of Drinking Water, mberger@utah.gov David Kruse, Division of Drinking Water, dbkruse@utah.gov