HomeMy WebLinkAboutDDW-2024-010499Sanitary Survey - Deficiency Report
PWS Number:UTAH23067 Deficiency Points:25 Survey Date:08/01/2024
Survey Name:CLEAN HARBORS -
ARAGONITE
Surveyor:Hunter Payne
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST001 | RAW WATER STORAGE TANK
101C. Access opening lid properly gasketed
Rule: R309-545-14(2)Rule requires the access opening to a tank to be furnished with a gasket between the lid
and frame. This significant deficiency must be corrected within 120 days of notification
or have a corrective action plan approved by DDW.
Notes:Gasket does not provide a complete seal.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V009 STORAGE TANK LID LACKS A FUNCTIONING GASKET BETWEEN THE LID AND
FRAME