HomeMy WebLinkAboutDDW-2024-010496Sanitary Survey - Deficiency Report
PWS Number:UTAH18027 Deficiency Points:520 Survey Date:08/13/2024
Survey Name:JORDAN VALLEY WCD Surveyor:Danielle Zebelean
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Wells | WS011 | 300 E 4500 S WELL
295B. Air vacuum relief valve on well discharge piping screened with #14 mesh screen
Rule: R309-515-6(12)(d)(v)Rule requires the exhaust/relief piping on an air release/vacuum relief valve on the well
discharge piping to be covered with a #14 mesh corrosion-resistant screen. This
significant deficiency must be corrected within 120 days of notification or have a
corrective action plan approved by DDW.
Notes:Missing screen
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: S029 END OF AIR RELEASE VACUUM RELIEF VALVE PIPING LACKS NO. 14 SCREEN
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Wells | WS025 | 1510 W 14600 S WELL
421B. Air vacuum relief valve on well discharge piping screened with #14 mesh screen
Rule: R309-515-6(12)(d)(v)Rule requires the exhaust/relief piping on an air release/vacuum relief valve on the well
discharge piping to be covered with a #14 mesh corrosion-resistant screen. This
significant deficiency must be corrected within 120 days of notification or have a
corrective action plan approved by DDW.
Notes:Missing Screen
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: S029 END OF AIR RELEASE VACUUM RELIEF VALVE PIPING LACKS NO. 14 SCREEN
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Wells | WS032 | 1100 E 4500 S WELL
536B. Pump to waste line equipped with #4 non-corrodible mesh screen
Rule: R309-515-6(12)(d)(ix)The discharge end of the pump-to-waste line shall be covered with a No. 4 mesh
corrosion-resistant screen. This significant deficiency must be corrected within 120
days of notification or have a corrective action plan approved by DDW.
Notes:Missing Screen
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: S010 END OF WELL PUMP-TO-WASTE LINE LACKS NO. 4 SCREEN
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Wells | WS042 | 1590 E 4670 S WELL
702. Wellhead is sealed to prevent contamination.
Rule: R309-515-6(6)(i)R309-515-6(6)(i) and R309-515-6(12)(b,c,d)require a sanitary seal be installed and
maintained at the wellhead and discharge piping. This significant deficiency should be
corrected within 120 days of notification or have a corrective action plan approved by
Notes:Opening in Well case where vent extends from
Deficiency Points: 50
Days until points become effective on IPS: 120
SDWIS Deficiency Description: S013 WELL LACKS THE REQUIRED WELL SEAL
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Wells | WS042 | 1590 E 4670 S WELL
703B. Vent down-turned
Rule: R309-515-6(12)(d)(iii)Guidance states provisions should be made for venting the well casing, however if
vented R309-515-6(12)(d)(iii) and R309-550-6(6)(b) requires vents be downturned or
shielded to prevent the entrance of surface water or rainwater.
Notes:Vent not downturned
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: S007 WELL CASING VENT IS NOT DOWNTURNED
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Wells | WS045 | MONITOR DR WELL
767B. Pump to waste line equipped with #4 non-corrodible mesh screen
Rule: R309-515-6(12)(d)(ix)The discharge end of the pump-to-waste line shall be covered with a No. 4 mesh
corrosion-resistant screen. This significant deficiency must be corrected within 120
days of notification or have a corrective action plan approved by DDW.
Notes:Missing Pump to Waste Screen
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: S010 END OF WELL PUMP-TO-WASTE LINE LACKS NO. 4 SCREEN
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Wells | WS054 | 8773 S 1300 W - DW1
809B. Pump to waste line equipped with #4 non-corrodible mesh screen
Rule: R309-515-6(12)(d)(ix)The discharge end of the pump-to-waste line shall be covered with a No. 4 mesh
corrosion-resistant screen. This significant deficiency must be corrected within 120
days of notification or have a corrective action plan approved by DDW.
Notes:pump to waste screens were not held on well. Looks like there is a #4 and #14 which may be
why they need to take the screens off to run to waste instead of just a #4.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: S010 END OF WELL PUMP-TO-WASTE LINE LACKS NO. 4 SCREEN
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Wells | WS055 | 1324 W POLO LN - DW2
830B. Pump to waste line equipped with #4 non-corrodible mesh screen
Rule: R309-515-6(12)(d)(ix)The discharge end of the pump-to-waste line shall be covered with a No. 4 mesh
corrosion-resistant screen. This significant deficiency must be corrected within 120
days of notification or have a corrective action plan approved by DDW.
Notes:pump to waste screens were not held on well. Looks like there is a #4 and #14 which may be
why they need to take the screens off to run to waste instead of just a #4.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: S010 END OF WELL PUMP-TO-WASTE LINE LACKS NO. 4 SCREEN
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Wells | WS056 | 9800 S 1300 W-DW3
851B. Pump to waste line equipped with #4 non-corrodible mesh screen
Rule: R309-515-6(12)(d)(ix)The discharge end of the pump-to-waste line shall be covered with a No. 4 mesh
corrosion-resistant screen. This significant deficiency must be corrected within 120
days of notification or have a corrective action plan approved by DDW.
Notes:pump to waste screens were not held on well. Looks like there is a #4 and #14 which may be
why they need to take the screens off to run to waste instead of just a #4.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: S010 END OF WELL PUMP-TO-WASTE LINE LACKS NO. 4 SCREEN
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Wells | WS057 | 10621 S 1300 W - DW4
872B. Pump to waste line equipped with #4 non-corrodible mesh screen
Rule: R309-515-6(12)(d)(ix)The discharge end of the pump-to-waste line shall be covered with a No. 4 mesh
corrosion-resistant screen. This significant deficiency must be corrected within 120
days of notification or have a corrective action plan approved by DDW.
Notes:pump to waste screens were not held on well. Looks like there is a #4 and #14 which may be
why they need to take the screens off to run to waste instead of just a #4.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: S010 END OF WELL PUMP-TO-WASTE LINE LACKS NO. 4 SCREEN
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Wells | WS058 | 11059 S 1300 W - DW5
893B. Pump to waste line equipped with #4 non-corrodible mesh screen
Rule: R309-515-6(12)(d)(ix)The discharge end of the pump-to-waste line shall be covered with a No. 4 mesh
corrosion-resistant screen. This significant deficiency must be corrected within 120
days of notification or have a corrective action plan approved by DDW.
Notes:pump to waste screens were not held on well. Looks like there is a #4 and #14 which may be
why they need to take the screens off to run to waste instead of just a #4.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: S010 END OF WELL PUMP-TO-WASTE LINE LACKS NO. 4 SCREEN
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Wells | WS058 | 11059 S 1300 W - DW5
901. Well discharge line has a pressure gauge.
Rule: R309-515-6(12)(d)(iv)Rule requires the discharge piping to be equipped with (in order of placement from the
wellhead) a smooth nosed sampling tap, a check valve, a pressure gauge, a means of
measuring flow, and a shutoff valve.
Notes:Pressure Gauge not working on Well Discharge line
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: S025 NO PRESSURE GAUGE ON WELL DISCHARGE PIPING
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST011 | 6000 W 4700 S - 6 MG CONCRETE
1122C. Vent covered with #14 or finer non-corrodible mesh screen.
Rule: R309-545-15(4)Rule requires a water storage tank vent to be fitted with #14 mesh or finer non-
corrodible screen and vents 6-inches or greater in diameter to be fitted with additional
heavy gauge screen or substantial covering to protect the #14 mesh screen from
vandalism or damage. This significant deficiency must be corrected within 120 days of
notification or have a compliance action plan approved by DDW.
Notes:Vent screen not properly secured
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V007 STORAGE TANK VENT LACKS NO. 14 SCREEN
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST017 | 5700 W 10200 S - 3 MG CONCRETE
1213B. Overflow line covered with #4 mesh non-corrodible screen
Rule: R309-545-13(3)Rule requires overflow pipes to be screened with #4 mesh non-corrodible screens
installed at a location least susceptible to damage by vandalism. This significant
deficiency must be corrected within 120 days of notification or have a corrective action
plan approved by DDW.
Notes:Screen not properly in place and also smaller than a #4
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V012 END OF STORAGE TANK OVERFLOW PIPE LACKS NO. 4 SCREEN
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST026 | BLUFFDALE TANK AT JVWTF
1339B. Overflow line covered with #4 mesh non-corrodible screen
Rule: R309-545-13(3)Rule requires overflow pipes to be screened with #4 mesh non-corrodible screens
installed at a location least susceptible to damage by vandalism. This significant
deficiency must be corrected within 120 days of notification or have a corrective action
plan approved by DDW.
Notes:Missing Screen
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V012 END OF STORAGE TANK OVERFLOW PIPE LACKS NO. 4 SCREEN
Sanitary Survey Category: PU
SDWIS Severity Code: Significant Deficiency
Pump Stations | PF007 | 3145 W 11400 S BOOSTER STATION
1398B. End of air relief piping covered with #14 mesh screen
Rule: R309-550-6(6)(b), R309-540-6(2)The open end of the air relief vent pipe from automatic valves shall be provided with a
#14 mesh, non-corrodible screen. This significant deficiency must be corrected within
120 days of notification or have a corrective action plan approved by DDW.
Notes:Blown off screens on the air vacs
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: PS10 PUMP STATION OR HYDROPNEUMATIC TANK A/V VALVE RELIEF PIPING LACKS
NO. 14 SCREEN
Sanitary Survey Category: PU
SDWIS Severity Code: Significant Deficiency
Pump Stations | PF013 | 5820 S 3800 W (TERMINAL)
1452B. End of air relief piping covered with #14 mesh screen
Rule: R309-550-6(6)(b), R309-540-6(2)The open end of the air relief vent pipe from automatic valves shall be provided with a
#14 mesh, non-corrodible screen. This significant deficiency must be corrected within
120 days of notification or have a corrective action plan approved by DDW.
Notes:Missing Screen
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: PS10 PUMP STATION OR HYDROPNEUMATIC TANK A/V VALVE RELIEF PIPING LACKS
NO. 14 SCREEN
Sanitary Survey Category: PU
SDWIS Severity Code: Significant Deficiency
Pump Stations | PF013 | 5820 S 3800 W (TERMINAL)
1452C. End of air relief piping terminates at least 6 inches above floor
Rule: R309-550-6(6)(b), R309-540-6(2)Rule requires that an air release valve discharge line terminate a minimum of 6 inches
above the floor.
Notes:End of air relief ends on the floor at a 90 angle
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: PS11 A/V VALVE RELIEF PIPING OF PUMP STATION OR HYDROPNEUMATIC TANK
NOT PROTECTED FROM CONTAMINATION OR NOT AT LEAST 6 INCHES ABOVE
FLOOR
Sanitary Survey Category: PU
SDWIS Severity Code: Significant Deficiency
Pump Stations | PF018 | 3600 WEST 10200 SOUTH PUMP STATION
1497B. End of air relief piping covered with #14 mesh screen
Rule: R309-550-6(6)(b), R309-540-6(2)The open end of the air relief vent pipe from automatic valves shall be provided with a
#14 mesh, non-corrodible screen. This significant deficiency must be corrected within
120 days of notification or have a corrective action plan approved by DDW.
Notes:All air vacs are missing screens, on the pump cans, discharge lines, and air vac in the
basement
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: PS10 PUMP STATION OR HYDROPNEUMATIC TANK A/V VALVE RELIEF PIPING LACKS
NO. 14 SCREEN
Sanitary Survey Category: TR
SDWIS Severity Code: Significant Deficiency
Dual-Media (also called Rapid Sand) - Filtration | TP002 | JVWTP
2207. Filter media is evaluated to verify it meets the manufacturer's specifications for depth and effective media size?
Rule: R309-525-15(4)R309-525-15(4)
Notes:Will provide reports at Aug 6 survey
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: T033 MEDIA DEPTHS NOT MEETING REQUIREMENTS
Sanitary Survey Category: TR
SDWIS Severity Code: Minor Deficiency
Dual-Media (also called Rapid Sand) - Filtration | TP002 | JVWTP
2208. What is the depth of media required for this filtration system? Explain in comments...
Rule: R309-105-7, 8 & 18, R309-100 through
605
Trigger for regulatory followup to address concerns.
Notes:Will provide reports at Aug 6 survey
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: TGR9 TRIGGER FOR REGULATORY FOLLOWUP TO ADDRESS CONCERNS