HomeMy WebLinkAboutDDW-2024-010474Sanitary Survey - Deficiency Report
PWS Number:UTAH22140 Deficiency Points:30 Survey Date:08/23/2024
Survey Name:ZIONS PEAK CAMP Surveyor:Matt Hinckley
Sanitary Survey Category: DS
SDWIS Severity Code: Significant Deficiency
Distribution | DS001 | UTAH22140 DISTRIBUTION SYSTEM
44A. Open end of vent line covered with #14 mesh screen
Rule: R309-550-6(6)(b)Rule states the open end of the air relief vent pipe from automatic valves shall be
provided with a #14 mesh, non-corrodible screen and a downward elbow, and where
possible, be extended to at least one foot above grade. This significant deficiency must
be corrected within 120 days of notification or have a corrective action plan approved
by DDW.
Notes:ONE OF THE SYSTEM AIR VAC LACKS NO. 14 SCREEN.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: D004 AIR RELIEF VALVE PIPE LACKS NO. 14 SCREEN
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Wells | WS001 | ZIONS PEAK CAMP WELL
67. Well discharge line has a smooth-nosed sampling tap, which samples the well water before any chemical injection. (first item from the
wellhead).
Rule: R309-515-6(12)(d)(iv)Rule requires the discharge piping to be equipped with a smooth nosed sampling tap, a
check valve, a pressure gauge, a means of measuring flow, and a shutoff valve. (smooth
nosed sampling tap being the first item from the well head and the shut-off valve as the
last item)
Notes:WELL DISCHARGE LINE IS LACKING SMOOTH NOSED SAMPLING TAP BEING THE
FIRST ITEM FROM THE WELL HEAD.
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: S023 NO SMOOTH NOSED SAMPLING TAP ON DISCHARGE PIPING