HomeMy WebLinkAboutDDW-2024-010450Sanitary Survey - Deficiency Report
PWS Number:UTAH11001 Deficiency Points:90 Survey Date:08/13/2024
Survey Name:BRIAN HEAD TOWN WATER
SYSTEM
Surveyor:Luke Treutel
Sanitary Survey Category: SM
SDWIS Severity Code: Significant Deficiency
General Maintenance and Environment | DS001 | UTAH11001 DISTRIBUTION SYSTEM
39. Are there any visual indications of unsanitary conditions?
Rule: R309-200-6, R309-105-18, R309-215-4(3)R309-200-6 The Secondary Maximum Contaminant Levels for public water systems
deals with substances which affect the aesthetic quality of drinking water. They are
presented here as recommended limits or ranges and are not grounds for rejection. The
taste of water may be unpleasant and the usefulness of the water may be impaired if
these standards are significantly exceeded.
R309-105-18 The Director or the local health department shall be informed by
telephone by a water supplier of any "emergency situation". The term "emergency
situation...
R309-215-4(3) If the water fails to meet minimum standards, then certain public
notification procedures shall be carried out, as outlined in R309-220. Water suppliers
shall also keep analytical records in their possession, for a required length of time, as
outlined in R309-105-17.
Notes:The Crystal Mtn Well house showed evidence of vermin. The well house must be cleaned and
sealed or fortified in some way to prevent pests from entering building.
Deficiency Points: 50
Days until points become effective on IPS: 120
SDWIS Deficiency Description: M017 WATER STAGNATION, BIOFILM OR SEDIMENTS CONTRIBUTES TO DRINKING
WATER CONTAMINATION
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Springs | WS007 | DECKER SPRING
107. Area of equal or higher elevation within 50 feet of spring collection devices is fenced.
Rule: R309-515-7(7)(e)Rule requires a stock-tight fence around the spring collection area.
Notes:Observed livestock grazing on spring area. Exception from 2010 included condition that no
grazing would occur.
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: SS02 SPRING COLLECTION AREA NOT FENCED
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Wells | WS009 | CRYSTAL MT WELL
157B. Air vacuum relief valve on well discharge piping screened with #14 mesh screen
Rule: R309-515-6(12)(d)(v)Rule requires the exhaust/relief piping on an air release/vacuum relief valve on the well
discharge piping to be covered with a #14 mesh corrosion-resistant screen. This
significant deficiency must be corrected within 120 days of notification or have a
corrective action plan approved by DDW.
Notes:Mesh screen is missing.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: S029 END OF AIR RELEASE VACUUM RELIEF VALVE PIPING LACKS NO. 14 SCREEN