HomeMy WebLinkAboutDDW-2024-010445Sanitary Survey - Deficiency Report
PWS Number:UTAH11010 Deficiency Points:100 Survey Date:08/19/2024
Survey Name:PAROWAN CITY WATER
SYSTEM
Surveyor:Tom McOmie
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Springs | WS002 | MAIN CANYON SPRING
69. No deep-rooted vegetation is within the 50 ft collection area.
Rule: R309-515-7(7)(f)All deep-rooted vegetation within the fenced collection area shall be removed by a
means not negatively affecting water quality. This significant deficiency must be
corrected within 120 days of notification or have a corrective action plan approved by
DDW.
Notes:Trees located with in 50ft of spring box.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: SS07 DEEP ROOTED VEGETATION IN SPRING COLLECTION AREA
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Springs | WS002 | MAIN CANYON SPRING
70. No roots seen in collection boxes and junctions.
Rule: R309-105-10(4)(a), R309-515-8(1)(a)Spring collection areas shall be periodically (preferably annually) cleared of deep-
rooted vegetation to prevent root growth from clogging collection lines. This significant
deficiency must be corrected within 120 days of notification or have a corrective action
plan approved by DDW.
Notes:Some roots in spring box.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: SS08 ROOTS IN SPRING COLLECTION PIPES
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST001 | MAIN CANYON TANK
143C. Access opening lid properly gasketed
Rule: R309-545-14(2)Rule requires the access opening to a tank to be furnished with a gasket between the lid
and frame. This significant deficiency must be corrected within 120 days of notification
or have a corrective action plan approved by DDW.
Notes:Needs new gasket.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V009 STORAGE TANK LID LACKS A FUNCTIONING GASKET BETWEEN THE LID AND
FRAME
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST003 | HWY 91 TANK
163. Is a tank overflow present? ... if yes, answer the following question(s)
Rule: R309-545-13 Rule requires all storage tanks to be provided with an overflow that discharges at an an
elevation between 12 and 24 inches above the ground surface or the rim of the receiving
basin. This significant deficiency must be corrected within 120 days of notification or
have a corrective action plan approved by DDW.
Notes:
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: VL01 STORAGE TANK LACKS AN OVERFLOW