Loading...
HomeMy WebLinkAboutDDW-2024-010445Sanitary Survey - Deficiency Report PWS Number:UTAH11010 Deficiency Points:100 Survey Date:08/19/2024 Survey Name:PAROWAN CITY WATER SYSTEM Surveyor:Tom McOmie Sanitary Survey Category: SO SDWIS Severity Code: Significant Deficiency Springs | WS002 | MAIN CANYON SPRING 69. No deep-rooted vegetation is within the 50 ft collection area. Rule: R309-515-7(7)(f)All deep-rooted vegetation within the fenced collection area shall be removed by a means not negatively affecting water quality. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:Trees located with in 50ft of spring box. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: SS07 DEEP ROOTED VEGETATION IN SPRING COLLECTION AREA Sanitary Survey Category: SO SDWIS Severity Code: Significant Deficiency Springs | WS002 | MAIN CANYON SPRING 70. No roots seen in collection boxes and junctions. Rule: R309-105-10(4)(a), R309-515-8(1)(a)Spring collection areas shall be periodically (preferably annually) cleared of deep- rooted vegetation to prevent root growth from clogging collection lines. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:Some roots in spring box. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: SS08 ROOTS IN SPRING COLLECTION PIPES Sanitary Survey Category: FW SDWIS Severity Code: Significant Deficiency Storage Tanks | ST001 | MAIN CANYON TANK 143C. Access opening lid properly gasketed Rule: R309-545-14(2)Rule requires the access opening to a tank to be furnished with a gasket between the lid and frame. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:Needs new gasket. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: V009 STORAGE TANK LID LACKS A FUNCTIONING GASKET BETWEEN THE LID AND FRAME Sanitary Survey Category: FW SDWIS Severity Code: Significant Deficiency Storage Tanks | ST003 | HWY 91 TANK 163. Is a tank overflow present? ... if yes, answer the following question(s) Rule: R309-545-13 Rule requires all storage tanks to be provided with an overflow that discharges at an an elevation between 12 and 24 inches above the ground surface or the rim of the receiving basin. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes: Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: VL01 STORAGE TANK LACKS AN OVERFLOW