HomeMy WebLinkAboutDERR-2024-010378IMPACT VALVE LEAK DETECTOR MONITOR CERTIFICATION OVERFILL OPERABILITY PV VENT CAP STAGE 1 PD 11000 N. MoPac Expressway, Suite 500 Austin, Texas 78759 Phone: (512) 451-6334 Fax: (512) 459-1459 Date Printed and Mailed: 8/26/2024 UTAH DEPARTMENT OF ENV. QUALITY UST PO Box 144840 SALT LAKE CITY, UT 84114 Test Date: 8/22/2024 Order Number: 2370464 Dear Regulator, Enclosed are the results of recent testing performed at the following facility: 7-ELEVEN 41600 5652 W 4700 S State ID 4002593 West Valley, UT 84128 Testing performed: Sincerely, Dawn Kohlmeyer Manager, Field Reporting 7-ELEVEN 41600 5652 W 4700 S State ID 4002593 West Valley UT 84128 41600 Tanknology, Inc. 7-ELEVEN, INC. P.O. BOX 711 DALLAS TX 75221 972-828-7575 08/22/2024 RUL PUL Vaporless LD- 2000 Vaporless LD- 2000 Vaporless LD- 2000 30 30 175 2 20 3 30 30 175 2 20 3 32 32 110 2 20 3 UT151 David Mathie NW1-2370464 Low Sulfur Diesel TTNK1:1 TTNK2:1 TTNK3:1 Impact Valve Inspection Impact Valve Operational Inspection Work Order:2370464 Date:8/22/2024 Site Name/ID:7-ELEVEN 41600 Address:5652 W 4700 S State ID 4002593 City:West Valley State:UT Zip:84128 How Inspected: Line Test NFPA 30A PEI RP1200 Other STP PRESSURE Dispenser Number Grade Secure Mount? Valve Lock?Pass/ Fail Comments 1/2 40 Pass Fail Not Tested 1/2 85 Pass Fail Not Tested 1/2 91 Pass Fail Not Tested 3/4 85 Pass Fail Not Tested 3/4 91 Pass Fail Not Tested 5/6 85 Pass Fail Not Tested 5/6 91 Pass Fail Not Tested 7/8 85 Pass Fail Not Tested 7/8 91 Pass Fail Not Tested 9/10 40 Pass Fail Not Tested 9/10 85 Pass Fail Not Tested 9/10 91 Pass Fail Not Tested Technician Comments: Technician Name:David Mathie Signature: Environmental Compliance for Petroleum Systems ©2024 Tanknology Inc., Austin, TX. All rights reserved. tanknology.com 7-ELEVEN 41600 7-ELEVEN, INC. 5652 W 4700 S State ID 4002593 West Valley UT 84128 4002593 Tanknology, Inc. P.O. BOX 711 DALLAS TX 75221 972-828-7575 800-964-1250 08/22/2024 1 2 3 RUL PUL DSL VR350 VR350 VR350 19782 7901 11904 118.38 118.38 118.38 UT151 David Mathie 5652 W 4700 S State ID 4002593 7-ELEVEN 41600 5652 W 4700 S State ID 4002593, West Valley, UT 84128 41600 Tanknology, Inc. 7-ELEVEN, INC. P.O. BOX 711 DALLAS, TX 75221 972-828-7575 08/22/2024 ANNULAR ANNULAR SB FILL STP SB FILL STP SB FILL RUL PUL/DSL RUL RUL PUL PUL DSL UT151 David Mathie 5652 W 4700 S State ID 4002593 7-ELEVEN 41600 5652 W 4700 S State ID 4002593, West Valley, UT 84128 41600 Tanknology, Inc. 7-ELEVEN, INC. P.O. BOX 711 DALLAS, TX 75221 972-828-7575 08/22/2024 STP UDC UDC UDC UDC UDC DSL 1/2 3/4 5/6 7/8 9/10 UT151 David Mathie 2 inch Pressure Decay Test TP201.3 Store Information Testing Company Site Name :7-ELEVEN 41600 Name :TANKNOLOGY INC. Address :5652 W 4700 S State ID 4002593 West Valley, UT 84128 Address :11000 N. MoPac Expressway Suite 500 Austin, TX 78759 Phone :385-246-4634 Phone :(800) 800-4633 Stage I System?DUAL Stage II System?NONE Total # of Nozzles :10 Products per Nozzle :3 Tanks Manifolded ?No Drop-Out tank present?NO Total # of Tanks Tested :2 Tank Information : Product Grade : Tank Capacity, gallons : Gasoline, gallons : Ullage, gallons : Testing Information : Start Time : Initial Pressure, wcg : Pressure @ 1 minute(s) : Pressure @ 2 minutes : Pressure @ 3 minutes : Pressure @ 4 minutes : Pressure @ 5 minutes : Allowable Final Pressure : Pass/Fail (Enter "GF" Gross Failure) TNK1 RUL 19782 11906 7876 12:44 2.00 2.00 2.00 1.99 1.99 1.98 1.88 Pass TNK2 PUL 7901 3101 4800 12:52 2.00 2.00 2.00 2.00 1.99 1.99 1.81 Pass Total 27683 15007 12676 All Comments: Tester :David Mathie Test Date :8/22/2024 Signature :Work Order :2370464 WO: 2370464 PVVC tested ==>RUL Manifolded Final Test Result (Pass / Fail) ==>Fail PVVC Manuf. ==>OPW Model Number ==>623V-2203 Is this Original or Replacement? Original If this cap is being replaced, check here: Manf Spec (CFH) Measured Leak Rate in ml/Min; Cracking (in H2O) Calc CFH (ml/min x .00212) Result (Pass /Fail) Pos Leak Rate(CFH)0.05 20 0.0424 Pass Low High Measured Pos Cracking (in H2O)2.50 6.00 2.09 Fail Neg Leak Rate (CFH)0.21 100 0.2120 Fail Low High Measured Neg Cracking (in H2O)-10.00 -6.00 -2.16 Fail PVVC tested ==>RUL Manifolded Final Test Result (Pass / Fail) ==>Pass PVVC Manuf. ==>OPW Model Number ==>723V Is this Original or Replacement? Replacement Manf Spec (CFH) Measured Leak Rate in ml/Min; Cracking (in H2O) Calc CFH (ml/min x .00212) Result (Pass /Fail) Pos Leak Rate(CFH)0.05 4 0.0085 Pass Low High Measured Pos Cracking (in H2O)2.50 6.00 3.61 Pass Neg Leak Rate (CFH)0.21 15 0.0318 Pass Low High Measured Neg Cracking (in H2O)-10.00 -6.00 -7.83 Pass PVVC tested ==>PUL Manifolded Final Test Result (Pass / Fail) ==>Fail PVVC Manuf. ==>OPW Model Number ==>623V-2203 Is this Original or Replacement? Original If this cap is being replaced, check here: Manf Spec (CFH) Measured Leak Rate in ml/Min; Cracking (in H2O) Calc CFH (ml/min x .00212) Result (Pass /Fail) Pos Leak Rate(CFH)0.05 20 0.0424 Pass Low High Measured Pos Cracking (in H2O)2.50 6.00 2.12 Fail Neg Leak Rate (CFH)0.21 100 0.2120 Fail Low High Measured Neg Cracking (in H2O)-10.00 -6.00 -2.21 Fail PVVC tested ==>PUL Manifolded Final Test Result (Pass / Fail) ==>Pass PVVC Manuf. ==>OPW Model Number ==>723V Is this Original or Replacement? Replacement Manf Spec (CFH) Measured Leak Rate in ml/Min; Cracking (in H2O) Calc CFH (ml/min x .00212) Result (Pass /Fail) Pos Leak Rate(CFH)0.05 6 0.0127 Pass Low High Measured Pos Cracking (in H2O)2.50 6.00 3.57 Pass Neg Leak Rate (CFH)0.21 17 0.0360 Pass Low High Measured Neg Cracking (in H2O)-10.00 -6.00 -7.83 Pass PVVC tested ==> Manifolded Final Test Result (Pass / Fail) ==> PVVC Manuf. ==>Model Number ==> Is this Original or Replacement? Manf Spec (CFH) Measured Leak Rate in ml/Min; Cracking (in H2O) Calc CFH (ml/min x .00212) Result (Pass /Fail) Pos Leak Rate(CFH) Low High Measured Pos Cracking (in H2O) Neg Leak Rate (CFH) Low High Measured Neg Cracking (in H2O) PVVC tested ==> Manifolded Final Test Result (Pass / Fail) ==> PVVC Manuf. ==>Model Number ==> Is this Original or Replacement? Manf Spec (CFH) Measured Leak Rate in ml/Min; Cracking (in H2O) Calc CFH (ml/min x .00212) Result (Pass /Fail) Pos Leak Rate(CFH) Low High Measured Pos Cracking (in H2O) Neg Leak Rate (CFH) Low High Measured Neg Cracking (in H2O) 11000 N. MOPAC EXPRESSWAY, SUITE 500, AUSTIN, TX 78759 (800) 800-4633 QP-08-03-FF-02 Pressure Vacuum Vent Cap TP-201.1E Field Form Rev C 1/27/2011 Site Overall Test Results: Pass Total +ve LR: 0.0212 Total -ve LR: 0.0678 Test Date 8/22/2024 Technician Name David Mathie WO #2370464 Facility Name / Loc #7-ELEVEN 41600 41600 Street 5652 W 4700 S State ID 4002593 City, St, Zip West Valley, UT 84128 Pressure Vacuum Vent Cap Test Form TP-201.1E 7-ELEVEN 41600 5652 W 4700 S State ID 4002593 West Valley, UT 84128 41600 Tanknology, Inc. 7-ELEVEN, INC. 972-828-7575 800-800-4633 08/22/2024 RUL 1 19782 118.375 OPW PUL 2 7901 118.375 OPW DSL 3 11904 118.375 OPW UT151 David Mathie P.O. BOX 711 DALLAS, TX 75221 Overfill Prevention Equipment Inspection OPW 61 and 71 Series Overfill Prevention Device Inspection Date:8/22/2024 Customer Name:7-ELEVEN, INC. Location #:7-ELEVEN 41600 Location Address:5652 W 4700 S State ID 4002593 ,West Valley ,UT , 84128 OPW Model Number:7160 PART 1) Proper height setting calculation Maximum Tank Volume per: Tank Chart A gallons Max shut off requirement for Flapper is 95% B 95% Multiply Maximum tank volume by 95% C gallons Use tank chart to determine height of calculated volume D inches Measure top of fill riser threads, or face seal adapter when used, to tank top E inches Tank diameter From Chart F inches Upper Tube in tank (G) F - D = G G inches Subtract 2 inches from upper tube in tank G - 2"= H H inches Calculated minimum upper tube length (I) H + E = I I inches Actual measured upper tube length (Without fill adapter) (J) J inches PART 2) Device certification criteria evaluation Criteria 1 Does the overfill prevention device meet the 95% requirement? Criteria 1a If the final shutoff volume is installed greater than 95%, is there at least 250 gallons of ullage above the overfill device activation point to ensure that none of the tank top fittings are exposed to product, meeting the criteria established in EPA 280.20iic and per OPW installation guidelines. Criteria 2 Is the Actual measured upper tube length 6.5 inches or more than the fill riser? (J must be 6.5" or more than E) Criteria 3 Does the overfill prevention device function as required? (Inspect the device for damage, contamination, freedom of movement, weakening due to wear and corrosion) PART 3) Device Certification PASS / FAIL Technician certifies that the device is operationally compliant. TNK1 19782.000 0.95 18792.900 106.375 36.250 118.375 12.000 10.000 46.250 49.750 Yes NA Yes Yes Pass TNK2 7901.000 0.95 7505.950 106.875 42.000 118.375 11.500 9.500 51.500 56.375 Yes NA Yes Yes Pass TNK3 11904.000 0.95 11308.800 105.875 40.000 118.375 12.500 10.500 50.500 53.750 Yes NA Yes Yes Pass 0.95 Comments: Signature of Technician: Date: 8/22/2024 David Mathie WO: NW1- 2370464 Site Diagram (This site diagram is for reference only and is not drawn to scale) Work Order:2370464 Site ID / Name:41600 / 7-ELEVEN 41600 Address:5652 W 4700 S State ID 4002593 City:West Valley State:UT Zip:84128 W.O.# NW1-2370464 +AAE- I10100 AUG 22, 2024 12:42 PM 7-11 41600 4682 S 5600 W WEST VALLEY,UT W01276256905001 SYSTEM STATUS REPORT ALL FUNCTIONS NORMAL +AAMAAQ- I90200 AUG 22, 2024 12:42 PM SOFTWARE REVISION LEVEL VERSION 336.01 SOFTWARE+ACM- 346336-100-B CREATED - 20.04.26.20.30 S-MODULE+ACM- 330160-100-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS BIR +AAMAAQ- I11B00 AUG 22, 2024 12:42 PM 7-11 41600 4682 S 5600 W WEST VALLEY,UT W01276256905001 SERVICE NOTICE SESSION REPORT START TIME END TIME AUG 22, 2024 11:34 AM AUG 22, 2024 12:38 PM APR 9, 2024 9:19 AM APR 9, 2024 11:47 AM AUG 23, 2023 12:12 PM AUG 23, 2023 12:55 PM AUG 31, 2022 9:22 AM AUG 31, 2022 10:54 AM +AAMAAQ- I20100 AUG 22, 2024 12:42 PM 7-11 41600 4682 S 5600 W WEST VALLEY,UT W01276256905001 IN-TANK INVENTORY TANK PRODUCT VOLUME TC VOLUME ULLAGE HEIGHT WATER TEMP 1 RUL 11892 11808 7890 68.36 0.50 70.20 2 PUL 3103 3088 4798 49.05 0.00 66.89 3 DSL 3288 3280 8616 39.06 0.00 65.26 +AAMAAQ- I30100 AUG 22, 2024 12:42 PM 7-11 41600 4682 S 5600 W WEST VALLEY,UT W01276256905001 LIQUID STATUS REPORT SENSOR LOCATION STATUS 1 RUL ANNULAR SENSOR NORMAL 2 DSL-PUL ANNULAR SENSOR NORMAL 3 RUL SPILL BKT SENSOR NORMAL 4 RUL STP SENSOR NORMAL 5 PUL SPILL BKT SENSOR NORMAL 6 PUL STP SENSOR NORMAL 7 DSL SPILL BKT SENSOR NORMAL 8 DSL STP SENSOR NORMAL 9 DISP 1-2 SENSOR NORMAL 10 DISP 3-4 SENSOR NORMAL 11 DISP 5-6 SENSOR NORMAL 12 DISP 7-8 SENSOR NORMAL 13 DISP 9-10 SENSOR NORMAL +AAMAAQ- I30200 AUG 22, 2024 12:42 PM 7-11 41600 4682 S 5600 W WEST VALLEY,UT W01276256905001 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 RUL ANNULAR AUG 22, 2024 12:22 PM FUEL ALARM AUG 23, 2023 11:55 AM FUEL ALARM AUG 31, 2022 10:14 AM FUEL ALARM 2 DSL-PUL ANNULAR AUG 22, 2024 12:17 PM FUEL ALARM AUG 23, 2023 12:29 PM FUEL ALARM AUG 31, 2022 10:19 AM FUEL ALARM 3 RUL SPILL BKT AUG 22, 2024 11:47 AM FUEL ALARM AUG 23, 2023 12:07 PM FUEL ALARM AUG 31, 2022 10:29 AM FUEL ALARM 4 RUL STP AUG 22, 2024 11:54 AM FUEL ALARM AUG 23, 2023 12:10 PM FUEL ALARM AUG 31, 2022 10:01 AM FUEL ALARM 5 PUL SPILL BKT AUG 22, 2024 11:57 AM FUEL ALARM AUG 23, 2023 12:19 PM FUEL ALARM AUG 31, 2022 10:32 AM FUEL ALARM 6 PUL STP AUG 22, 2024 11:57 AM FUEL ALARM AUG 23, 2023 12:20 PM FUEL ALARM AUG 31, 2022 10:03 AM FUEL ALARM 7 DSL SPILL BKT AUG 22, 2024 12:08 PM FUEL ALARM AUG 23, 2023 12:23 PM FUEL ALARM AUG 31, 2022 10:36 AM FUEL ALARM 8 DSL STP AUG 22, 2024 11:57 AM FUEL ALARM AUG 23, 2023 12:24 PM FUEL ALARM AUG 31, 2022 10:05 AM FUEL ALARM 9 DISP 1-2 AUG 22, 2024 12:05 PM FUEL ALARM AUG 23, 2023 11:08 AM FUEL ALARM AUG 31, 2022 9:51 AM FUEL ALARM 10 DISP 3-4 AUG 22, 2024 12:05 PM FUEL ALARM AUG 23, 2023 11:09 AM FUEL ALARM AUG 31, 2022 9:51 AM FUEL ALARM 11 DISP 5-6 AUG 22, 2024 12:06 PM FUEL ALARM AUG 23, 2023 11:09 AM FUEL ALARM AUG 31, 2022 9:51 AM FUEL ALARM 12 DISP 7-8 AUG 22, 2024 12:07 PM FUEL ALARM AUG 23, 2023 11:15 AM FUEL ALARM AUG 31, 2022 9:52 AM FUEL ALARM 13 DISP 9-10 AUG 23, 2023 11:10 AM FUEL ALARM AUG 31, 2022 9:52 AM FUEL ALARM +AAMAAQ- IA0100 AUG 22, 2024 12:42 PM TYPE CODE LENGTH SERIAL NO. D/CODE TANK 1 RUL MAG D004 126.00 262176 1294 TANK 2 PUL MAG D004 126.00 410604 4304 TANK 3 DSL MAG D004 126.00 380557 2404 +AAMAAQ- 931 TANK 1 SETUP CONDITIONS PRODUCT: RUL PRODUCT CODE 1 HIGH WATER LIMIT 1.0 OVERFILL LIMIT: 17803 HIGH PRODUCT LIMIT: 18792 LOW PRODUCT: 1504 SUDDEN LOSS LIMIT: 99 LEAK LIMIT: 99 THERMAL COEFF: 0.000690 DELIVERY DELAY: 5 TANK FULL CAPACITY: 19782 0 0 0 0 3/4 HEIGHT CAPACITY: 16033 0 0 0 0 1/2 HEIGHT CAPACITY: 9897 0 0 0 0 1/4 HEIGHT CAPACITY: 3718 0 0 0 0 TANK DIAMETER: 118.38 TANK TILT ADDER: 0.00 MANIFOLDED TANKS: NONE TANK CONFIGURED: NO +AAMAAQ- 932 TANK 2 SETUP CONDITIONS PRODUCT: PUL PRODUCT CODE 2 HIGH WATER LIMIT 1.0 OVERFILL LIMIT: 7110 HIGH PRODUCT LIMIT: 7505 LOW PRODUCT: 651 SUDDEN LOSS LIMIT: 99 LEAK LIMIT: 99 THERMAL COEFF: 0.000690 DELIVERY DELAY: 5 TANK FULL CAPACITY: 7901 0 0 0 0 3/4 HEIGHT CAPACITY: 6356 0 0 0 0 1/2 HEIGHT CAPACITY: 3964 0 0 0 0 1/4 HEIGHT CAPACITY: 1551 0 0 0 0 TANK DIAMETER: 118.38 TANK TILT ADDER: 0.00 MANIFOLDED TANKS: NONE TANK CONFIGURED: NO +AAMAAQ- 933 TANK 3 SETUP CONDITIONS PRODUCT: DSL PRODUCT CODE 3 HIGH WATER LIMIT 1.0 OVERFILL LIMIT: 10713 HIGH PRODUCT LIMIT: 11308 LOW PRODUCT: 855 SUDDEN LOSS LIMIT: 99 LEAK LIMIT: 99 THERMAL COEFF: 0.000450 DELIVERY DELAY: 5 TANK FULL CAPACITY: 11904 0 0 0 0 3/4 HEIGHT CAPACITY: 9696 0 0 0 0 1/2 HEIGHT CAPACITY: 5944 0 0 0 0 1/4 HEIGHT CAPACITY: 2172 0 0 0 0 TANK DIAMETER: 118.38 TANK TILT ADDER: 0.00 MANIFOLDED TANKS: NONE TANK CONFIGURED: NO +AAMAAQ- I61100 AUG 22, 2024 12:42 PM LEAK TEST METHOD - - - - - - - - - - - - TEST ON DATE : ALL TANK APR 26, 2020 START TIME : DISABLED TEST RATE :0.20 GAL/HR DURATION : 2 HOURS TST EARLY STOP:DISABLED +AAMAAQ- I70300 AUG 22, 2024 12:42 PM LIQUID TYPE SENSOR LOCATION TYPE 1 RUL ANNULAR TRI-STATE (SINGLE FLOAT) 2 DSL-PUL ANNULAR TRI-STATE (SINGLE FLOAT) 3 RUL SPILL BKT NORMALLY CLOSED 4 RUL STP TRI-STATE (SINGLE FLOAT) 5 PUL SPILL BKT NORMALLY CLOSED 6 PUL STP TRI-STATE (SINGLE FLOAT) 7 DSL SPILL BKT NORMALLY CLOSED 8 DSL STP TRI-STATE (SINGLE FLOAT) 9 DISP 1-2 TRI-STATE (SINGLE FLOAT) 10 DISP 3-4 TRI-STATE (SINGLE FLOAT) 11 DISP 5-6 TRI-STATE (SINGLE FLOAT) 12 DISP 7-8 TRI-STATE (SINGLE FLOAT) 13 DISP 9-10 TRI-STATE (SINGLE FLOAT) 14 TRI-STATE (SINGLE FLOAT) 15 TRI-STATE (SINGLE FLOAT) 16 TRI-STATE (SINGLE FLOAT) +AAMAAQ- I80800 AUG 22, 2024 12:42 PM RELAY SETUP REPORT R 1: TYPE: STANDARD NORMALLY OPEN - NO ALARM ASSIGNMENTS - R 2: TYPE: STANDARD NORMALLY OPEN - NO ALARM ASSIGNMENTS - R 3: TYPE: STANDARD NORMALLY OPEN - NO ALARM ASSIGNMENTS - R 4: TYPE: STANDARD NORMALLY OPEN - NO ALARM ASSIGNMENTS - +AAMAAQ- I10200 AUG 22, 2024 12:43 PM 7-11 41600 4682 S 5600 W WEST VALLEY,UT W01276256905001 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 4 PROBE / G.T. 162489 161702 2 INTERSTITIAL BD 200220 199650 3 INTERSTITIAL BD 199929 199536 4 UNUSED 9650979 9530588 5 UNUSED 9624572 9523550 6 UNUSED 9615970 9522460 7 UNUSED 9614061 9520478 8 UNUSED 9615863 9522351 9 RELAY BOARD 14993 14985 10 UNUSED 9622891 9531152 11 UNUSED 9611200 9526991 12 UNUSED 9611586 9524223 13 UNUSED 9609441 9521282 14 UNUSED 9606781 9517403 15 UNUSED 9611608 9525487 16 UNUSED 9610964 9524419 COMM 1 ELEC DISP INT. 100617 100555 COMM 2 UNUSED 9618022 9523766 COMM 3 SERIAL SAT BD 480473 480187 COMM 4 UNUSED 9615512 9527208 COMM 5 RS485 SERIAL BD 9609806 68199 COMM 6 MT COMM BOARD 9604207 404414 +AAM-