Loading...
HomeMy WebLinkAboutDERR-2024-010265 WESTECH EQUIPMENT 195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307 801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054 PRESSURE/VACUUM VENT CAP LEAK RATES AND OPENING PRESSURES Facility Name: Harmon’s #14 – Draper Owner: Harmon’s Taylorsville, LLC Address: 672 East 11400 South Address: 3540 South 4000 West, Suite 500 City, State, Zip: Draper, Utah 84020 City, State, Zip: West Valley City, Utah 84120 Facility I.D.#: 4002328 Phone #: 385-255-1734 Testing Company: Westech Phone #: 801-266-2545 Date: 7/24/24 This procedure is to determine pressure/vent cap specifications. See 40 CFR 63 CCCCCC for the inspection procedure. Tank Number 1/2 Product Grade RUL/PUL PV Manufacturer OPW Model Number 623V PRESSURE TEST Passing 2” Leak Rate (CFH) <0.05 Measured 2” Leak Rate (CFH) New Cap Passing Positive Opening Pressure (Inches WC) 2.5 – 6.0 Measured Positive Opening Pressure (Inches WC) New Cap VACUUM TEST Passing -4” Leak Rate (CFH) <0.21 Measured -4” Leak Rate (CFH) New Cap Passing Negative Opening Pressure (Inched WC) 6.0 – 10.0 Measured Negative Opening Pressure (Inched WC) New Cap Test Results ☒Pass ☐Fail ☐Pass ☐Fail ☐Pass ☐Fail ☐Pass ☐Fail Comments: New PV cap installed 7/24/24. Tester’s Name Taber DeHart, UT-0394 Tester’s Signature