Loading...
HomeMy WebLinkAboutDDW-2024-010300Sanitary Survey - Deficiency Report PWS Number:UTAH22059 Deficiency Points:55 Survey Date:07/30/2024 Survey Name:SUMMIT WATER DISTRIBUTION COMPANY Surveyor:Nagendra Dev Sanitary Survey Category: FW SDWIS Severity Code: Minor Deficiency Storage Tanks | ST001 | LOWER HIDDEN COVE TANK 288. Storage tank roof is sloped to prevent ponding Rule: R309-545-9(4)Rule requires drainage of storage tank roofs to eliminate water ponding. Notes:Evidence of ponding on roof Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: V003 WATER PONDING ON STORAGE TANK ROOF OR TANK ROOF NOT SLOPED TO DRAIN Sanitary Survey Category: FW SDWIS Severity Code: Minor Deficiency Storage Tanks | ST002 | UPPER HIDDEN COVE TANK 302. Storage tank roof is sloped to prevent ponding Rule: R309-545-9(4)Rule requires drainage of storage tank roofs to eliminate water ponding. Notes:Evidence of ponding on roof Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: V003 WATER PONDING ON STORAGE TANK ROOF OR TANK ROOF NOT SLOPED TO DRAIN Sanitary Survey Category: TR SDWIS Severity Code: Significant Deficiency Gaseous Chlorination | TP007 | STORAGE WELL CHLORINATOR 575. Chlorine cylinder is restrained in position to prevent upset. Rule: R309-520-7(2)(h)Rule requires chlorine cylinders to be restrained in position to prevent upset. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:No chlorine cylinder in place Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: TD15 CHLORINE CYLINDERS NOT RESTRAINED