HomeMy WebLinkAboutDDW-2024-010285Sanitary Survey - Deficiency Report
PWS Number:UTAH12004 Deficiency Points:255 Survey Date:08/08/2024
Survey Name:EUREKA TOWN Surveyor:David Heaton
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Wells | WS003 | VULCAN WELL
97. Wellhead is sealed to prevent contamination.
Rule: R309-515-6(6)(i)R309-515-6(6)(i) and R309-515-6(12)(b,c,d)require a sanitary seal be installed and
maintained at the wellhead and discharge piping. This significant deficiency should be
corrected within 120 days of notification or have a corrective action plan approved by
Notes:Wellhead gasket needs to be replaced.
Deficiency Points: 50
Days until points become effective on IPS: 120
SDWIS Deficiency Description: S013 WELL LACKS THE REQUIRED WELL SEAL
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Wells | WS007 | TINTIC JUNCTION WELL 1
185. Wellhead secured to protect quality water
Rule: R309-105-10(5)All water system facilities shall be secure. This significant deficiency must be corrected
within 120 days of notification or have a corrective action plan approved by DDW.
Notes:Wellhead is out in the open next to a public access dirt road. It is not inside of the wellhouse
or fenced.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: S002 WELL HOUSE NOT PROTECTED AGAINST VANDALISM
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST001 | STORAGE FACILITY ST001
245C. Access opening lid properly gasketed
Rule: R309-545-14(2)Rule requires the access opening to a tank to be furnished with a gasket between the lid
and frame. This significant deficiency must be corrected within 120 days of notification
or have a corrective action plan approved by DDW.
Notes:Gasket needs to be replaced.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V009 STORAGE TANK LID LACKS A FUNCTIONING GASKET BETWEEN THE LID AND
FRAME
Sanitary Survey Category: SM
SDWIS Severity Code: Significant Deficiency
Pump Stations | PF002 | SOUTH TANK BOOSTER STATION
268. There are no undocumented drinking water facilities (i.e. tanks, pump stations, treatment facilities, etc.) or recent modifications that have
not gone through DDW review
Rule: R309-100-5(2), R309-500-6, R309-500-9,
R309-500-9(2) and (3)
Rule requires complete plans & specification for all public drinking water projects to
be approved in writing by the Director. Any facility found that has not started DDW
review shall be considered unapproved. This significant deficiency must be corrected
within 120 days of notification or have a corrective action plan approved by DDW.
Notes:There are two active pump stations. The South Tank/Beck Street pump station (this one) and
the Tintic pump station.
Deficiency Points: 50
Days until points become effective on IPS: 120
SDWIS Deficiency Description: G001 UNAPPROVED FACILITY IN SERVICE
Sanitary Survey Category: TR
SDWIS Severity Code: Minor Deficiency
Treatment - Chlorination General | TP001 | TINTIC WELL GAS CHLORINATOR
283. Free chlorine residual test equipment on-site or available?
Rule: R309-520-7(1)(j)Rule requires chlorine residual test equipment available capable of measuring residuals
to the nearest 0.1 mg/l in the range below 0.5 mg/l, to the nearest 0.3 mg/l between 0.5
mg/l and 1.0 mg/l and to the nearest 0.5 mg/l above 1.0 mg/l.
Notes:Operator keeps test equipment on his truck, but does not have equipment at each chlorinator.
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: TD78 LACKS EQUIPMENT FOR CHLORINE RESIDUAL TESTING
Sanitary Survey Category: TR
SDWIS Severity Code: Significant Deficiency
Treatment - Chlorination General | TP001 | TINTIC WELL GAS CHLORINATOR
287. POE is before first connection/customer?
Rule: R309-215 R309-215 & R309-520-6(4)(d)
Notes:There are five homes that receive their water before chlorination.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: T028 INCORRECT COMPLIANCE CHLORINE RESIDUAL SAMPLING LOCATION
Sanitary Survey Category: MR
SDWIS Severity Code: Significant Deficiency
Treatment - Chlorination General | TP001 | TINTIC WELL GAS CHLORINATOR
290. Daily operating records reflect chemical dosages and total quantities used
Rule: R309-105-14(3)(a)Rule requires all water system using chemical addition or specialized equipment for the
treatment of drinking water to regularly complete operational reports. This significant
deficiency must be corrected within 120 days of notification or have a corrective action
plan approved by DDW.
Notes:Operator currently using a monthly average for records.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: TG20 DAILY RECORDS DO NOT REFLECT DOSAGES ACCURATELY
Sanitary Survey Category: TR
SDWIS Severity Code: Minor Deficiency
Treatment - Chlorination General | TP003 | VULCAN WELL CHLORINATOR
298. Free chlorine residual test equipment on-site or available?
Rule: R309-520-7(1)(j)Rule requires chlorine residual test equipment available capable of measuring residuals
to the nearest 0.1 mg/l in the range below 0.5 mg/l, to the nearest 0.3 mg/l between 0.5
mg/l and 1.0 mg/l and to the nearest 0.5 mg/l above 1.0 mg/l.
Notes:Operator keeps test equipment on his truck, but does not have equipment at each chlorinator.
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: TD78 LACKS EQUIPMENT FOR CHLORINE RESIDUAL TESTING
Sanitary Survey Category: MR
SDWIS Severity Code: Significant Deficiency
Treatment - Chlorination General | TP003 | VULCAN WELL CHLORINATOR
305. Daily operating records reflect chemical dosages and total quantities used
Rule: R309-105-14(3)(a)Rule requires all water system using chemical addition or specialized equipment for the
treatment of drinking water to regularly complete operational reports. This significant
deficiency must be corrected within 120 days of notification or have a corrective action
plan approved by DDW.
Notes:Operator currently using a monthly average for records.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: TG20 DAILY RECORDS DO NOT REFLECT DOSAGES ACCURATELY