HomeMy WebLinkAboutDDW-2024-010275Sanitary Survey - Deficiency Report
PWS Number:UTAH27011 Deficiency Points:85 Survey Date:07/29/2024
Survey Name:NEW HARMONY WATER
SYSTEM
Surveyor:Tom McOmie
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Springs | WS002 | COMMANCHE SPRING
60. Drain has minimum of 12 inch clearance above flood rim of receiving basin
Rule: R309-515-7(7)(d), R309-545 Overflow pipes on junction and collection boxes shall comply with R309-545 and
discharge a minimum of 12 inches above the ground surface or rim of the receiving
basin. This significant deficiency must be corrected within 120 days of notification or
have a corrective action plan approved by DDW.
Notes:The drain while it has a screen the discharge does not meet the minimum 12 inch from the
bottom of the pipe to the ground.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: SS14 SPRING BOX OVERFLOW OR DRAIN LACKS FREE FALL OF 12 TO 24 INCHES
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Springs | WS002 | COMMANCHE SPRING
63. No deep-rooted vegetation is within the 50 ft collection area.
Rule: R309-515-7(7)(f)All deep-rooted vegetation within the fenced collection area shall be removed by a
means not negatively affecting water quality. This significant deficiency must be
corrected within 120 days of notification or have a corrective action plan approved by
DDW.
Notes:Willows need to be cut down from the spring area.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: SS07 DEEP ROOTED VEGETATION IN SPRING COLLECTION AREA
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Springs | WS002 | COMMANCHE SPRING
66. Is a spring box vent present? ... if yes, answer the following question(s)
Rule: R309-515-7(7)(d), R309-545-15 Rule requires junction boxes and collection boxes to comply with R309-545 with respect
to venting. Therefore, a junction or collection box requires a vent to be fitted with #14
mesh or finer non-corrodible screen, be fitted with a protective heavy-gauge screen or
covering if 6 inches in diameter or greater, be down-turned and shielded to prevent the
entrance of contaminants, be located and sized to avoid blockage during winter, and
have the end of the vent discharge a minimum of 24 inches above the earth on buried
structures.
Notes:No vent.
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: SS11 SPRING BOX LACKS A MEANS OF VENTING
Sanitary Survey Category: FW
SDWIS Severity Code: Minor Deficiency
Storage Tanks | ST002 | SOUTH TANK
114A. Mild deterioration or spalling?
Rule: R309-545-6(1) and 545-9(1)Rule requires all water storage tanks to have suitable watertight roofs and sidewalls
that shall also exclude birds, animals, insects, and excessive dust.
Notes:Pooling water on the roof.
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: V021 STORAGE TANK ROOF OR SIDEWALLS SHOW SIGNS OF MILD OR MODERATE
DETERIORATION
Sanitary Survey Category: TR
SDWIS Severity Code: Minor Deficiency
Gaseous Chlorination | TP001 | WELL #1 CHLORINATOR
158B. Bottle of ammonium hydroxide (56 % ammonia solution) is available for chlorine leak detection
Rule: R309-520-7(2)(l)(i)Rule requires a bottle of ammonium hydroxide (56% ammonia solution) to be available
for leak detection.
Notes:System does not have a ammonia leak detection bottle.
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: TD14 NO AMMONIA HYDROXIDE SOLUTION FOR CHLORINE LEAK DETECTION