HomeMy WebLinkAboutDDW-2024-010275Sanitary Survey - Deficiency Report PWS Number:UTAH27011 Deficiency Points:85 Survey Date:07/29/2024 Survey Name:NEW HARMONY WATER SYSTEM Surveyor:Tom McOmie Sanitary Survey Category: SO SDWIS Severity Code: Significant Deficiency Springs | WS002 | COMMANCHE SPRING 60. Drain has minimum of 12 inch clearance above flood rim of receiving basin Rule: R309-515-7(7)(d), R309-545 Overflow pipes on junction and collection boxes shall comply with R309-545 and discharge a minimum of 12 inches above the ground surface or rim of the receiving basin. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:The drain while it has a screen the discharge does not meet the minimum 12 inch from the bottom of the pipe to the ground. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: SS14 SPRING BOX OVERFLOW OR DRAIN LACKS FREE FALL OF 12 TO 24 INCHES Sanitary Survey Category: SO SDWIS Severity Code: Significant Deficiency Springs | WS002 | COMMANCHE SPRING 63. No deep-rooted vegetation is within the 50 ft collection area. Rule: R309-515-7(7)(f)All deep-rooted vegetation within the fenced collection area shall be removed by a means not negatively affecting water quality. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:Willows need to be cut down from the spring area. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: SS07 DEEP ROOTED VEGETATION IN SPRING COLLECTION AREA Sanitary Survey Category: SO SDWIS Severity Code: Minor Deficiency Springs | WS002 | COMMANCHE SPRING 66. Is a spring box vent present? ... if yes, answer the following question(s) Rule: R309-515-7(7)(d), R309-545-15 Rule requires junction boxes and collection boxes to comply with R309-545 with respect to venting. Therefore, a junction or collection box requires a vent to be fitted with #14 mesh or finer non-corrodible screen, be fitted with a protective heavy-gauge screen or covering if 6 inches in diameter or greater, be down-turned and shielded to prevent the entrance of contaminants, be located and sized to avoid blockage during winter, and have the end of the vent discharge a minimum of 24 inches above the earth on buried structures. Notes:No vent. Deficiency Points: 5 Days until points become effective on IPS: 0 SDWIS Deficiency Description: SS11 SPRING BOX LACKS A MEANS OF VENTING Sanitary Survey Category: FW SDWIS Severity Code: Minor Deficiency Storage Tanks | ST002 | SOUTH TANK 114A. Mild deterioration or spalling? Rule: R309-545-6(1) and 545-9(1)Rule requires all water storage tanks to have suitable watertight roofs and sidewalls that shall also exclude birds, animals, insects, and excessive dust. Notes:Pooling water on the roof. Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: V021 STORAGE TANK ROOF OR SIDEWALLS SHOW SIGNS OF MILD OR MODERATE DETERIORATION Sanitary Survey Category: TR SDWIS Severity Code: Minor Deficiency Gaseous Chlorination | TP001 | WELL #1 CHLORINATOR 158B. Bottle of ammonium hydroxide (56 % ammonia solution) is available for chlorine leak detection Rule: R309-520-7(2)(l)(i)Rule requires a bottle of ammonium hydroxide (56% ammonia solution) to be available for leak detection. Notes:System does not have a ammonia leak detection bottle. Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: TD14 NO AMMONIA HYDROXIDE SOLUTION FOR CHLORINE LEAK DETECTION