HomeMy WebLinkAboutDDW-2024-010256Sanitary Survey - Deficiency Report
PWS Number:UTAH09072 Deficiency Points:25 Survey Date:07/29/2024
Survey Name:QUALITY INN BRYCE Surveyor:Brian Pattee
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Wells | WS001 | WELL # 1
59A. Vent screened with #14 mesh screen
Rule: R309-515-6(12)(d)(iii)Guidance states provisions should be made for venting the well casing, however if
vented R309-515-6(12)(d)(iii) and R309-550-6(6)(a)require vents be fitted with a #14
mesh or finer non-corrodible screen.
Notes:One side of the Well head mushroom vent has a screen missing
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: S006 END OF WELL CASING VENT LACKS NO. 14 SCREEN