Test Date: 7/30/2024
Order Number: 2374364
Dear Regulator,
Enclosed are the results of recent testing performed at the following facility:
Jackson Foods #154
4607 W. 6200 S.
West Jordan, UT 84008
Testing performed:
Sincerely,
Dawn Kohlmeyer
Manager, Field Reporting
2 inch Pressure Decay Test
TP201.3
Store Information Testing Company
Site Name :Jackson Foods #154 Name :TANKNOLOGY INC.
Address :4607 W. 6200 S.
West Jordan, UT 84008
Address :11000 N. MoPac Expressway Suite 500
Austin, TX 78759
Phone :-Phone :(800) 800-4633
Stage I System?DUAL
Stage II System?STUB UP
Total # of Nozzles :12
Products per Nozzle :3
Tanks Manifolded ?Yes
Drop-Out tank present?NO
Total # of Tanks Tested :2
Tank Information :
Product Grade :
Tank Capacity, gallons :
Gasoline, gallons :
Ullage, gallons :
Testing Information :
Start Time :
Initial Pressure, wcg :
Pressure @ 1 minute(s) :
Pressure @ 2 minutes :
Pressure @ 3 minutes :
Pressure @ 4 minutes :
Pressure @ 5 minutes :
Allowable Final Pressure :
Pass/Fail (Enter "GF" Gross Failure)
1
REG UNLEAD
19951
13790
6161
2
PREMIUM
15104
6873
8231
11:18
2.00
1.60
1.93
Fail
Total
35055
20663
14392
All
11:18
2.00
1.60
1.93
Fail
Comments:
test balls in atg riser fill caps on
Tester :David Mathie Test Date :7/30/2024
Signature :Work Order :2374364
WO: 2374364
PVVC tested ==>RUL Manifolded
Final Test Result (Pass / Fail) ==>Fail
PVVC Manuf. ==>OPW Model Number ==>623V-2203
Is this Original or
Replacement?
Original
If this cap is being
replaced, check here:
Manf Spec
(CFH)
Measured
Leak Rate
in ml/Min;
Cracking
(in H2O)
Calc CFH
(ml/min
x
.00212)
Result
(Pass /Fail)
Pos Leak Rate(CFH)0.05 25 0.0530 Fail
Low High Measured
Pos Cracking (in H2O)2.50 6.00 1.71 Fail
Neg Leak Rate (CFH)0.21 100 0.2120 Fail
Low High Measured
Neg Cracking (in H2O)-10.00 -6.00 -2.30 Fail
PVVC tested ==>RUL Manifolded
Final Test Result (Pass / Fail) ==>Pass
PVVC Manuf. ==>OPW Model Number ==>723V
Is this Original or
Replacement?
Replacement Manf Spec
(CFH)
Measured
Leak Rate
in ml/Min;
Cracking
(in H2O)
Calc CFH
(ml/min
x
.00212)
Result
(Pass /Fail)
Pos Leak Rate(CFH)0.05 6 0.0127 Pass
Low High Measured
Pos Cracking (in H2O)2.50 6.00 3.56 Pass
Neg Leak Rate (CFH)0.21 13 0.0276 Pass
Low High Measured
Neg Cracking (in H2O)-10.00 -6.00 -7.21 Pass
PVVC tested ==>PUL Manifolded
Final Test Result (Pass / Fail) ==>Fail
PVVC Manuf. ==>OPW Model Number ==>623V-2203
Is this Original or
Replacement?
Original
If this cap is being
replaced, check here:
Manf Spec
(CFH)
Measured
Leak Rate
in ml/Min;
Cracking
(in H2O)
Calc CFH
(ml/min
x
.00212)
Result
(Pass /Fail)
Pos Leak Rate(CFH)0.05 25 0.0530 Fail
Low High Measured
Pos Cracking (in H2O)2.50 6.00 0.04 Fail
Neg Leak Rate (CFH)0.21 100 0.2120 Fail
Low High Measured
Neg Cracking (in H2O)-10.00 -6.00 -0.11 Fail
PVVC tested ==>PUL Manifolded
Final Test Result (Pass / Fail) ==>Pass
PVVC Manuf. ==>OPW Model Number ==>723V
Is this Original or
Replacement?
Replacement Manf Spec
(CFH)
Measured
Leak Rate
in ml/Min;
Cracking
(in H2O)
Calc CFH
(ml/min
x
.00212)
Result
(Pass /Fail)
Pos Leak Rate(CFH)0.05 4 0.0085 Pass
Low High Measured
Pos Cracking (in H2O)2.50 6.00 3.87 Pass
Neg Leak Rate (CFH)0.21 12 0.0254 Pass
Low High Measured
Neg Cracking (in H2O)-10.00 -6.00 -8.05 Pass
PVVC tested ==> Manifolded
Final Test Result (Pass / Fail) ==>
PVVC Manuf. ==>Model Number ==>
Is this Original or
Replacement?
Manf Spec
(CFH)
Measured
Leak Rate
in ml/Min;
Cracking
(in H2O)
Calc CFH
(ml/min
x
.00212)
Result
(Pass /Fail)
Pos Leak Rate(CFH)
Low High Measured
Pos Cracking (in H2O)
Neg Leak Rate (CFH)
Low High Measured
Neg Cracking (in H2O)
PVVC tested ==> Manifolded
Final Test Result (Pass / Fail) ==>
PVVC Manuf. ==>Model Number ==>
Is this Original or
Replacement?
Manf Spec
(CFH)
Measured
Leak Rate
in ml/Min;
Cracking
(in H2O)
Calc CFH
(ml/min
x
.00212)
Result
(Pass /Fail)
Pos Leak Rate(CFH)
Low High Measured
Pos Cracking (in H2O)
Neg Leak Rate (CFH)
Low High Measured
Neg Cracking (in H2O)
11000 N. MOPAC EXPRESSWAY, SUITE 500, AUSTIN, TX 78759
(800) 800-4633
QP-08-03-FF-02 Pressure Vacuum Vent Cap TP-201.1E Field Form
Rev C 1/27/2011
Site Overall Test Results: Pass
Total +ve LR: 0.0212
Total -ve LR: 0.0530
Test Date 7/30/2024
Technician Name David Mathie
WO #2374364
Facility Name / Loc #Jackson Foods #154 154
Street 4607 W. 6200 S.
City, St, Zip West Jordan, UT 84008
Pressure Vacuum Vent Cap Test Form TP-201.1E
Site Diagram
(This site diagram is for reference only and is not drawn to scale)
Work Order:2374364
Site ID / Name:154 / Jackson Foods #154
Address:4607 W. 6200 S.
City:West Jordan State:UT Zip:84008